Max-Air Systems ME E 008-013 Series Скачать руководство пользователя страница 3

ME C 004 Series LV/HV | Mod

 

(con't)

  Installation, Operation and Maintenance Instructions

Rev: 10/10/22

Website

Max-Air Technology, Inc.  •  114 Resource Drive •  Wentzville, MO 63385  •   United States of America

Tel +1.636.272.4934 • Toll Free 888.842.9998 •  Fax 636.272.4937  •  www.maxairtech.com  •  [email protected]

3

Fi

le

 Na

m

e:

 M

ax

-A

ir_

IO

M

_ME

_E

00

8~

01

3_

LV

H

V_

M

od

_c

on

ve

rt

ed.

pdf

shaft. Pull the hex key to the RIGHT SLOWLY until you hear a "click" from 

the associated (#1) cam switch and snug up on the cam setscrew. Do not 

move the actuator. No need to overtighten the cam setscrew.

5. Set the CCW auxiliary switch. 

a. Using the 2.5mm hex key on CAM #3 (Fig 7) loosen the cam set 

screw and rotate the cam CCW by pushing the hex key to the RIGHT 

a few degrees. Lightly snug up on the set screw until resistance is felt 

against the cam shaft. Pull the hex key to the LEFT SLOWLY until you hear 

a "click" from the associated (#3) cam switch and continue a few more 

degrees in the same direction. (This assures the AUX switch trips before 

the actuator reaches its end of travel. Snug up on the cam setscrew.

6. Set the signal processing for the actuator. (ref Fig 8)

Use the table below to set the eight (8) DIP switches to establish signal 

type, response and fault modes of operation.

DIP

S1

S2

S3

S4

S5

S6

S7

S8

MODE

INPUT

FEEDBACK

RESPONSE

LOSS OF SIGNAL

4-20MA

ON

OFF

OFF

ON

OFF

OFF = DIR

CW

OFF

ON

CCW

ON

OFF

LAST

ON

ON

2-10VDC

OFF

ON

ON

OFF

ON

ON = REV

CW

ON

OFF

CCW

OFF

ON

LAST

ON

ON

7. Set the signal response. (ref Fig 8) Remove power. Manually position the 

actuator to about 50% open, and then re-apply power. The actuator will travel 

in a CW direction until it reaches its full CW end of travel position (set by cam#2 

in step 4 above). Press and hold the "SET" button on the logic PCB for 2 seconds. 

The PCB will enter local setting mode. LED9 will illuminate. 

- Press and hold the "UP" button until the actuator reaches it full OPEN (CCW) 

position (LED 2 ON), and generate a 20mA signal. Press the "MODE" button for 2 

seconds to set the full CCW position. 

- Press and hold the "DN" button until the actuator reaches it full CLOSED (CW) 

position (LED 1 ON), and generate a 4mA signal. Press the "MODE" button for 2 

seconds to set the full CW position.

- Check the feedback (4mA) and adjust VR2 if necessary. Turning VR2 CW 

decreases the feedback value. Turning VR2 CCW increases the feedback value.

- The 20mA feedback value is generated by the microprocessor and is not 

adjustable.

- Press the "SET" button to SAVE these settings.

8.  After setting the analog response, check the operation of the actuator in 

response to your input signals to make sure operation is as intended. After 

verification that all settings are correct, generate a 4mA input signal to drive 

the actuator to its full CW position, and wait for it to stop. 

9. Set the CW mechanical stop. (Fig 9) Use the 5mm hex key on the RIGHT side 

stop screw and turn it clockwise until it bottoms out against the internal stop 

boss on the final output drive. Turn the hex key ONE turn CCW, then use the 

17mm box wrench to lock the stop screw in positon. Do not tighten the stop 

screw so hard as to crush the sealing washer. 

10. Generate a 20mA input signal to drive the actuator to its full CCW position, 

and wait for it to stop. 

11. Set the CCW mechanical stop. (Fig 10) Use the 5mm hex key on the LEFT 

side stop screw and turn it clockwise until it bottoms out against the internal 

stop boss on the final output drive. Turn the hex key ONE turn CCW, then use 

the 17mm box wrench to lock the stop screw in positon. Do not tighten the stop 

screw so hard as to crush the sealing washer. 

When the actuator reaches its end of travel electrically, you should be able 

to rotate the handwheel at least 1/2 or more turns before you reach the 

mechanical stop. This is true for both ends of travel. If the handwheel is "locked", 

the mechanical stops have been set incorrectly and must be reset. Any time the 

EOT cams need to be moved, the mechanical stops MUST be reset. 

This completes the calibration of the actuator. 

LED 9

ME E 008~013 Series LV/HV | Mod

 

(con't)

  Installation, Operation and Maintenance Instructions

Fig 6 - CCW  EOT Cam adjustment

Fig 7 - CCW AUX Cam adjustment

DIP

 Switch setting

feedback calibration

status LEDs

4 button programming

Fig 8 - Analog Settings

Fig 9 - Right side (CW)

mechanical stop

Fig 10 - Left side (CCW)

mechanical stop