Recommendations:
Control and load cables must be ad equally separated, if possible in separated cable trays.
If there are crossing lines, try to mount it on perpendicular crossing.
It is recommended that power line filters be installed at the cabinet input to achieving successful filtering of
electromagnetic interference, this filter acts as a barrier between polluted energy and clean energy goes into the
cabinet. The filter must be connected to an effective ground plane and where proximity does not couple radiated noise
to the clean lines.
Nr. of Points X Power Consumption (W)
RECOMMENDATIONS
POWER CONSUMPTION
Points
24Vdc
48Vdc
60Vdc
125Vdc
127Vac
220Vac
Points
24Vdc
48Vdc
60Vdc
125Vdc
4
1,9
3,3
4,1
3,9
3,9
6,8
4
2,7
4,1
4,9
6,3
12
3,7
5,5
5,7
9,1
7,9
11,5
12
6,1
7,8
8,2
16,4
20
5,6
7,2
8,0
11,8
11,9
16,3
20
9,6
11,1
12,1
23,9
28
7,4
9,4
10,2
15,7
14,7
23,2
28
13,0
14,9
16,0
32,7
36
9,2
11,1
11,8
19,7
18,7
28,0
36
16,4
18,2
19,2
41,6
44
11,0
12,9
14,0
23,6
22,7
34,9
44
19,8
21,5
23,1
50,4
52
11,9
14,6
16,2
27,6
26,7
39,7
52
22,3
24,8
27,0
59,2
60
13,5
16,3
17,9
31,5
29,5
46,6
60
25,5
28,1
30,3
68,0
Annunciators without repeater relays (RRO)
Annunciators with repeater relays (RRO)