- 10 -
Malfunction
Possible Cause
Corrective Action
The output value is
too high.
・
Short-circuited between the electrode and the
duct or pipe because of material stuck onto the
electrode surface.
・
No electrical charge because of condensation on
the electrode.
・
The electrode touches the inner surface of the
pipe.
・
Component failure.
・
A very large quantity of materials is still flowing.
Notes
・
Loosen the M5 bolt and nut to remove the probe
from the Dust Monitor.
Be sure to securely tighten the screw after
cleaning the probe.
・
Contact us for extension of the insulation.
(Additional fee to be charged)
・
If the probe is too short, the electric charge
cannot be detected correctly.
・
Remove the sensor and check if
any material is stuck onto the
electrode surface.
If so, turn off the power supply,
and then clean the electrode with
moist cloth.
Notes
・
Check to see if at least 10 mm of
the insulation is out of the socket.
・
Pull out more of the insulation if
necessary.
Notes
・
Remove the sensor and check if
any condensation is on the
electrode.
If so, turn off the power supply,
and then clean the electrode with
moist cloth.
・
Measure the length of the
electrode and the inner diameter
of the pipe and check to see if the
electrode touches the inner
surface.
If so, change the length of the
probe.
Notes
The output value
does not change.
・
Power is not supplied from the power source.
・
The cable between the sensor and the converter is
disconnected or incorrectly connected.
・
Some materials are stuck onto the electrode
surface.
・
The electrode touches the inner surface of the
pipe.
・
Device failure.
・
Check the connections to the
terminal block.
・
Check and correct the cable
connection.
・
Remove the sensor and check if
any material is stuck onto the
electrode surface.
If so, turn off the power supply,
and then clean the electrode with
moist cloth.
Notes
・
Measure the length of the
electrode and the inner diameter
of the pipe and check to see if the
electrode touches the inner
surface.
If so, change the length of the
probe.
Notes
The Alarm LED
lights up.
・
1) Be in the Maintenance mode.
・
2) Device failure.
・
1) If so, change it in the normal
setting mode.
・
2) Contact us.