- 8 -
Fig.4. Connection
※About the
grounding
construction of Zener barriers.
Please comply to A-class grounding (With the ground resistance of 10Ω or less) alone.
Important : EMC-cable gland is used for Sensor.
Again, when wiring. Figure.11. becomes points of wiring.
White
Ele
ct
ro
ni
c
su
bs
tr
at
e
of
S
en
so
r
Housing of Sensor
Exclusive line Shielded cable
Please connect earth terminal separately.
A-class grounding.
EMC cable
gland
Sensor
PFM-M01PEX
Zener barrier
Z961/Z964
Output unit
PFM-KCU
Black
Brown
Brown
Brown
Brown
Yellow
Yellow
Yellow
Yellow
White
White
White
Green
Green
Green
Green
Black
Black
Hazardous area
Safety area
Power supply
AC110V/220V
(-15〜+10%)
Alarm contact
(SPDT)
Ac250V,2A DC30V,2A
Upper limit 1
(SPDT)
Ac250V,2A DC30V,2A
Upper limit 2
(SPDT)
Ac250V,2A DC30V,2A
Analog output signal
DC4〜20mA
Load Max. 500Ω
Line-connecting terminal:
Max. 1.5mm
2
(Output unit)
!
Fig.10. Connection diagram
(Component part)
Packing
Body
Shield-ring
Rubber bush
Clamping member
Cap
(2)
Completion drawing
(1)
85
(3)
5
(4)
Packing
(1)
Please pass Cap, Clamping member, and Rubber
bush through the cable.
Please peel off the cable covering from
the verge by the length of 85mm.
(2)
Please make the shield line asunder.
Please wrap an asunder shield line
as shown in left figure.
(3)
Please pass Shield-ring through the cable.
Please peel off the cover of the core wire by 5mm.
Please use solderless terminal with insulating
coating of Stick-type by three (brown, yellow, and
white) core wires.
A green core wire must use the pressure terminal of
R type(R1.25-4).
(4)
Please pass Body and Packing through the cable, and
install it so that the shield line may surely come
in contact with the Shield-ring.
Fig.11. becomes points of wiring.