IMPORTANT:  Employ ESD precautions to avoid static discharge when touching the 
CAN Bridge circuit board.  ESD can cause damage leading to catastrophic or 
intermittent product failure modes.  
 
The following paragraphs describe each switch setting in more detail.  The format Sb:s, 
where b is the bank number and s is the switch number within that bank, will be used.  
The “as shipped” settings are shown with an asterisk “*”. 
 
The CB-500 must be reset (power cycled) before switch settings take effect. 

Switch S1:1  

Selects Node Communication Type for internal radios.  A 
Radio System must consist of only one Server (master) and 
only one Client (slave) per channel.  The Server is the 
initiator of the radio pair.  Before the radios link, the Client 
will only listen for a Server and the Server will transmit to find 
a Client. 

 

Radio Operation 

S1:1 

Server ON 

Client OFF* 

Switch S1:2  

Reserved.  Should be in the OFF* position. 

 

Switches S1:3,4,5,6 

Selects the operating channel.  A master/slave pair must be 
set to the same channel to operate properly.   

 

Channel 

S1:3 

S1:4 

S1:5 

S1:6 

Freq (GHz) 

1*

 

OFF* 

OFF* 

OFF* 

OFF* 

2.405* 

OFF 

OFF 

OFF 

ON 

2.410 

OFF 

OFF 

ON 

OFF 

2.415 

OFF 

OFF 

ON 

ON 

2.420 

OFF 

ON 

OFF 

OFF 

2.425 

OFF 

ON 

OFF 

ON 

2.430 

OFF 

ON 

ON 

OFF 

2.435 

OFF 

ON 

ON 

ON 

2.440 

ON 

OFF 

OFF 

OFF 

2.445 

10 

ON 

OFF 

OFF 

ON 

2.450 

11 

ON 

OFF 

ON 

OFF 

2.455 

12 

ON 

OFF 

ON 

ON 

2.460 

13 

ON 

ON 

OFF 

OFF 

2.465 

14 

ON 

ON 

OFF 

ON 

2.470 

15 

ON 

ON 

ON 

OFF 

2.475 

16 

ON 

ON 

ON 

ON 

2.480 

 
 

 
 
 

Содержание CB-500

Страница 1: ...ireless link can communicate at a separation of up to 200 feet A full 64 node DeviceNet can be implemented depending on scan rates and frame density Since actual CAN messages are transferred the Wirel...

Страница 2: ...Radio complies with FCC Part 15B no user license required Configuration Options Configuration via internal dip switches Radio link master or slave Standard versus extended CAN frame formats Host Inte...

Страница 3: ...s than 200 feet separation without significant RF obstacles The actual transfer rate in any application is dependent upon the quality of the RF link Structural components such as steel walls or deckin...

Страница 4: ...alidate agency approvals To access configuration switches first use a flat screwdriver to pry off the two decorative covers at the right and left ends of the lid Four pry slots are provided as shown b...

Страница 5: ...stem must consist of only one Server master and only one Client slave per channel The Server is the initiator of the radio pair Before the radios link the Client will only listen for a Server and the...

Страница 6: ...encountered retry count exceeded Note Both units must have this enabled for the feature to work properly Switches S2 5 6 Selects the number of retries The radio will retransmit an unsuccessful packet...

Страница 7: ...hausted Scanner retries must be set at a level that mitigates data loss at the system level Strong Indicates the best data throughput Data packets are being transferred to the radio at a rate equivale...

Страница 8: ...AN packets Power Indicator The power indicator implies the presence of electrical power It is a hardwired LED that does not indicate the quality of the power detected Heavy 50 100 of the available ban...

Страница 9: ...ce Suggested specifications are listed below Panel Fastener 1 2 inch plywood 5 8 x 8 wood screw 1 8 inch aluminum 10 32 machine screw to threaded hole or bolt 1 2 inch plaster board Wall anchor with 6...

Страница 10: ...uires a SELV power supply with power output intrinsically limited to under 8 amps at a maximum of 30VDC If a protective device is used with a power supply that exceeds this requirement it must be rate...

Страница 11: ...ter Operation of this equipment in a residential environment is likely to cause harmful interference to other residential devices in which case the user will be required to correct the interference at...

Страница 12: ...Technical Manual Wireless CAN Bridge 500 CB 500 Matric Technical Manual 185 0053 V8 Page 12 of 12 For technical support contact Matric 2099 Hill City Road Seneca PA 16346 814 677 0716 www matric com...

Отзывы: