Matelec FPC-15007-CON Скачать руководство пользователя страница 3

3

FRONT

SIDE VIEW

Top

Bottom

Top

Bottom

DOC:  APP 15005
VER 1.0

WIRING CONNECTION DETAIL

FPC-15006-CON

ON STEADY

Pump contacts are switched ‘On’

SLOW FLASH

Pump run has been interrupted by a control circuit

ON STEADY

Pump is in auto mode and will start upon inputs from level switches

SLOW FLASHING

Pump has been interrupted by ‘maximum run time’ feature

ON STEADY

A high level is or has been present

FLASHING SLOWLY

A low level is or has been present

ON STEADY

The thermal overload protection on the pump circuit has been tripped and requires

manual reset

ON STEADY

Pump is in manual mode and will run continuously regardless of level switch status for a 

prescribed period only

TO RESET FAULT, PRESS MUTE BUTTON FOR 3 SECONDS

AN ACKNOWLEDGEMENT BEEP WILL SOUND WHEN FAULTS ARE CLEARED 

POWER ON

Light will illuminate when there is power connected to the panel and the main isolator

switch is switched on

MUTE

Press to silence buzzer

Press and hold for 3 seconds to clear faults

Press and Hold for more than 3 seconds to test buzzer and strobe

WARNING: HIGH VOLTAGE

ALL ELECTRICAL CONNECTIONS MUST BE CARRIED OUT

BY A SUITABLY QUALIFIED ELECTRICIAN

ACCESS BY AUTHORISED PERSONNEL ONLY

OVERLOAD

MUTE

MAN

WIRING CONNECTION DETAIL

APP-15005

ON STEADY

Pump contacts are switched ‘On’

SLOW FLASH

Pump run has been interrupted by a control circuit

ON STEADY

Pump is in auto mode and will start upon inputs from level switches

SLOW FLASHING

Pump has been interrupted by ‘maximum run time’ feature

ON STEADY

A high level is or has been present

FLASHING SLOWLY

A low level is or has been present

ON STEADY

The thermal overload protection on the pump circuit has been tripped and requires

manual reset

ON STEADY

Pump is in manual mode and will run continuously regardless of level switch status for a 

prescribed period only

TO RESET FAULT, PRESS MUTE BUTTON FOR 3 SECONDS

AN ACKNOWLEDGEMENT BEEP WILL SOUND WHEN FAULTS ARE CLEARED 

POWER ON

Light will illuminate when there is power connected to the panel and the main isolator

switch is switched on

MUTE

Press to silence buzzer

Press and hold for 3 seconds to clear faults

Press and Hold for more than 3 seconds to test buzzer and strobe

WARNING: HIGH VOLTAGE

ALL ELECTRICAL CONNECTIONS MUST BE CARRIED OUT

BY A SUITABLY QUALIFIED ELECTRICIAN

ACCESS BY AUTHORISED PERSONNEL ONLY

OVERLOAD

MUTE

MAN

INDICATOR LIGHTS GUIDE

INDICATOR LIGHTS GUIDE

SET THERMAL OVERLOADS TO SUIT PUMP

240Vac

MAINS POWER

SUPPLY

STOP/LOW

LEVEL

FLOAT SWITCH

START/MEDUIM

LEVEL

FLOAT SWITCH

HIGH ALARM

LEVEL

FLOAT SWITCH

COMMON

N/O C

LOSE ON RISE

COMMONCOMMON

N/O C

LOSE ON RISE

COMMON

N/O C

LOSE ON RISE

PUMP  

240Vac

INPUT 2

STOP

LEVEL

START

LEVEL

HIGH

LEVEL

INPUT 3

INPUT 4

COMMON

FAULT

Volt/Free

BMS

PUMP  

SUPPLY

FLOAT SWITCH CONNECTIONS

12Vdc CONNECTIONS

240Vac CONNECTIONS

BLUE NOT

REQUIRED

E

A

N

E

A

N

Probe Holder

s/s Probe rodes 

PUMP

415Vac

  

415Vac

MAINS POWER

SUPPLY

COMMON

FAULT

Volt/Free

BMS

PROBES

E1

COMMON

E1

Stop

E2

Start

E3

High

Low/Voltage

SUPPLY

415Vac CONNECTIONS

A2

A3

N

E

A1

PUMP

P2

P3

E

P1

T1

T2

Therm.

12Vdc

BRIDGE

IF NOT

REQUIRED

Mounting

Frame/

Wall

INSTALLATION

CONNECTION

MOUNTING

1. Controller enclosure must be   

    mounted in a vertical position.

2. Ensure mounting method does 

    not compromise enclosure

    weather proof rating.

3. Ensure access to main isolator is 

    not restricted.

4. Ensure cables/conduits entering 

    the panel have mechanical

    protection and that the

    penetrations are sealed and do   

    not compromise the weather 

    proof rating of the enclosure.

Note: 

Controller  must  be  earthed  and  all  electrical  connections  must  be  carried  out  by  a  suitably  qualified

Electrician.

MAIN ISOLATOR

Содержание FPC-15007-CON

Страница 1: ...Single Pump Controller Installation and Operating Instructions MODEL FPC 15007 CON MAIN ISOLATOR DOC FPC 15007 CON VER 1 0 P U M P C O N T R O L OWNER S OPERATION COMMISIONING MANUAL ...

Страница 2: ...by a suitably qualified Electrician SAFETY WARNING All electrical connections must be carried out by a suitably qualified and registered electrician SAFETY 2 HRH 5 DATA SHEET 7 INSTALLATION 3 CIRCUIT DIAGRAM 10 Mounting Connection NOTES 11 AT A GLANCE 12 Indicators GETTING STARTED 4 Push Buttons Operations Features Your Single Pump Controller reflects the superior quality and attention to detail i...

Страница 3: ...A1 PUMP P2 P3 E P1 T1 T2 Therm 12Vdc BRIDGE IF NOT REQUIRED Mounting Frame Wall INSTALLATION CONNECTION MOUNTING 1 Controller enclosure must be mounted in a vertical position 2 Ensure mounting method does not compromise enclosure weather proof rating 3 Ensure access to main isolator is not restricted 4 Ensure cables conduits entering the panel have mechanical protection and that the penetrations a...

Страница 4: ... in Manual Mode after 5 minutes the pump will revert to Auto 6 Off High Level Alarm automatically resets upon open circuit of high level input High Level alarm has 15 minute delay On High Level Alarm can only be reset manually High Level Alarm has 5 second delay Mode A Standard Configuration Start Stop High Level operation When the Pump Start input is closed contact triggered the Duty Pump will be...

Страница 5: ...cts This run on occurs even if Pressure switch contacts open during this initial period If however run time exceeds 11 seconds the pump will stop immediately upon open circuit occurring If the Pressure Switch Input closes circuit as well as the Low Pressure Switch Input a low pressure timer will begin counting If this condition exists for a period of 60 seconds then both pumps are shut down and th...

Страница 6: ...larm will automatically reset once the High Level input opens circuit The controller will also use the alternate High Level Alarm Delay Typically used for Storm Water applications High Level Alarm delay in this mode is 15 minutes Setting this DIP Switch to On will cause the High level Alarm to remain active until the controller is reset The High Level Alarm will use the standard High Level Alarm a...

Страница 7: ...ction PUMP UP Function PUMP DOWN Sensitivity adjustable by a potentiometer 5 100kΩ Measuring frequency 10Hz prevents polarization of liquid and raising oxidation of measuring probes Galvanically separated supply voltage UNI 24 240VAC DC Output contact 1xchangeover SPDT 8A 250V AC1 1 MODULE mounting onto a DIN rail Monitoring of two levels Ω Connection Function Device description Tank with monitore...

Страница 8: ...sistance Voltage n electrodes Current in probes Time response Max capacity of probe cable Time delay t Time delay after switching on t1 Accuracy Accuracy in setting mechanical Output Number of contacts Current rating Switching voltage Switched voltage Min switched output DC Mechanical life AC1 Electrical life Other information Operational temperature Storing temperature Electrical strenght Operati...

Страница 9: ...se a tank made of a conductive material you can use it as probe C In case you require monitoring of one level only it is neccessary to connect inputs H and D and connect them to one probe in this case sensitivity is lowered by half 2 5 50kΩ Probe C can be connected with a protective wire of supply system PE To prevent undesirable switching out output contacts by various influences sediment on prob...

Страница 10: ...40N 12V 0V Transformer 12Vac T1 P1 P2 P3 A1 A2 Contactor 18A 240Vac Contactor 1 Strobe Light Buzzer Inline Relay 12Vdc R1 Common Fault BMS Volt Free 1 2 3 4 5 6 O N A1 A2 C D H Conductivity Relay CR1 A1 A2 C D H Conductivity Relay CR2 PROBE INPUT Low Voltage Stop Common Start High 95 96 NC Contact TOL1 Thermal Switch 18 15 NO Contact CR1 1 18 15 NO Contact CR2 1 R1 1 CIRCUIT DIAGRAM ...

Страница 11: ...11 NOTES ...

Страница 12: ... ALARM ON A high level alarm has been present for the preset time FLASHING A low level alarm is present ON STEADY Pump switched on to run ON STEADY A pump fault overload has occurred FLASHING A prime loss fault has occurred Silences the siren and if held down for 3 seconds clears all faults If selected the LED indicator will confirm if on the particular pump is set to Automatic Pumping Mode Turns ...

Отзывы: