background image

 
 
 
 
 
TROUBLE SHOOTING 

 

 

 

16

 

 July 2010 / DC Distribution / EN 

 

8 TROUBLE 

SHOOTING 

 
Please contact your local Mastervolt Service Centre if you cannot correct a problem with the aid of the malfunction 
table below. See www.Mastervolt.com for an extended list of Mastervolt Service Centres. 
 

Failure  

Possible cause  

What to do  

Display has switched off. 

Turn on display. 

No display function. 

Error in the network wiring.  

Check wiring for errors. 

 

No powering device available 
on the MasterBus. 

The 

MasterView Easy 

display must be powered 

by the network. This means that at least one 
device in the network should have powering 
capabilities (Section 4.3). The DC Distribution is 
no powering device. 

No communication.  

Error in the wiring. 

Check the MasterBus cables. 

No terminating device placed 
at the ends of the network. 

MasterBus needs a terminating device on both 
ends of the network. Check if installed (See 
section 4.3). 

MasterBus network is 
configured as a ring network. 

Ring networks are not allowed. Check the 
connections of the network (Section 4.3). 

 

T-connections in the 
MasterBus network. 

Check if T-connections are made in the network. 
T-connections are not allowed (see section 4.3). 

Error in the wiring.  

Check the UTP patch cables and terminating 
devices (Section 4.3). 

MasterView display shows 
no DC Distribution. 

Display not set up to show all 
devices. 

Check manual of the display. 

No voltage in one group of 
DC Distribution. 

Fuse(s) blown. 

Investigate the cause of the blown fuse. Then 
replace the fuse. 

Wrong setting of the language 
at the DC Distribution. 

Adjust the language setting. See chapter 5, 
Configuration General. 

Wrong language is 
displayed. 

Wrong setting of the language 
at displaying device. 

Each separate connected device can have its 
own language setting. See user’s manual of the 
connected device. 

Alarm messages do not 
appear (correctly).  

One of the fuses has 
loosened. 

Check the fastenings of all fuses. 

The communication LEDs 
blink alternately, indicating 
an alarm situation. 

All fuses can trigger an alarm 
situation. 

Look at your display to find out which fuse has 
blown. Investigate the cause of the blown fuse. 
Then replace the fuse. 

The alarm situation of a 
fuse stays “On”, after 
replacing the fuse. 

Detection only functions above 
5V DC. If you did not yet 
connect the battery, the alarm 
situation stays the same. 

Connect the battery and watch the alarm 
situation changing to Off. 

The alarm situation of a 
fuse is “On”, while no fuse 
is installed at that position. 

If no fuse is installed, you need 
to disable the alarm function at 
that position. 

Disable the alarm function to avoid a constant 
alarm situation with a fuse not installed. 

 
 

Содержание 77020200

Страница 1: ...O DC Distribution 500 DC Connection Device MASTERVOLT Snijdersbergweg 93 1105 AN Amsterdam The Netherlands Tel 31 20 3422100 Fax 31 20 6971006 www Mastervolt com Copyright 2010 Mastervolt v 1 3 July 2...

Страница 2: ...d via the MasterBus communication platform The DC Distribution features three different menus a monitoring menu which shows the state OK or Alarm in one or more fuses a configuration menu to enter DC...

Страница 3: ...tions 5 2 6 Warning regarding the use of batteries 5 3 OPERATION 6 3 1 Introduction 6 3 2 Connecting your components 6 3 3 Features 7 3 4 MasterBus displays 7 3 5 Event based programming 7 3 6 Communi...

Страница 4: ...ersion includes 20 pages 1 2 GUARANTEE SPECIFICATIONS Mastervolt guarantees that this unit has been built according to the legally applicable standards and specifications Should work take place which...

Страница 5: ...have access to the user s manual be familiar with the contents of this manual This applies in particular to this chapter Safety Guidelines and Measures 2 4 MAINTENANCE AND REPAIR 1 If the electrical...

Страница 6: ...ed DC connections to install up to four different components Besides it provides the MasterBus network see chapter 4 with information about the fuse state To view the MasterBus information you need a...

Страница 7: ...n for DC Distribution application See figure 3 Figure 3 MasterAdjust software 3 5 EVENT BASED PROGRAMMING An event is a condition to be met at which you want another device to perform a task If a fuse...

Страница 8: ...ces can be added to the existing network in a very easy way by just extending the network This gives the MasterBus network a high degree of flexibility for extended system configuration not only today...

Страница 9: ...not make ring networks The electric power for the network comes from the connected devices At least one device in the network should have powering capabilities see specifications One powering device...

Страница 10: ...is enabled this screen reads On Disable a fuse when no component is connected This will prevent unexpected alarms On Enabled On Enabled Off Disabled Name Fuse 1 Name of fuse 1 in your DC Distribution...

Страница 11: ...t data Figure 10 shows the meaning of the event data Input is a pulse followed by a longer signal 1 0 On changes the status to On at the first signal Off changes the status to Off at the first signal...

Страница 12: ...d wrenches may be helpful during the installation of the DC Distribution CAREFUL Use isolated tools Materials DC Distribution Up to four fuses together maximum 500A per group See section 3 2 Five fuse...

Страница 13: ...the screw on the positive strip first and fastening it with the fuse installed Fasten the parts in the right order see figure 11 a e Fasten the M8 hexagonal screws with a 9 12 Nm 80 105 InLbs torque...

Страница 14: ...or MasterBus 5 Display for MasterBus data 6 Charger 7 Inverter 8 Load fuse 9 Load 10 DC wiring 11 MasterBus wiring Figure 13 shows an example of the DC Distribution in combination with the MasterShunt...

Страница 15: ...100m 330ft MasterBus cable 77050200 50 pcs MasterBus connectors 77050000 Complete set to assemble MasterBus cables Delivery includes 100m 330ft UTP cable 50 pcs modular jacks and crimping tool 7704905...

Страница 16: ...and terminating devices Section 4 3 MasterView display shows no DC Distribution Display not set up to show all devices Check manual of the display No voltage in one group of DC Distribution Fuse s blo...

Страница 17: ...n Available languages English Nederlands Deutsch Francais Castellano Italiano Norsk Svenska Suomi Dansk Maximum fuse current 300 A Maximum current ingoing group chargers 500 A Maximum current outgoing...

Страница 18: ...the centre to centre distances of the mounting holes and the DC fastening threads are displayed If you combine the DC Distribution with other MasterConnect devices especially dimension 200 mm 7 87 in...

Страница 19: ...declares that Product 77020200 DCDistribution 500 12 24 48V Is in conformity with the provision of the EC EMC directive 89 336 EEC and amendments 92 31 EEC 93 68 EEC The following harmonised standard...

Страница 20: ...Snijdersbergweg 93 1105 AN Amsterdam The Netherlands Tel 31 20 3422100 Fax 31 20 6971006 Email info Mastervolt com...

Отзывы: