8
Suggested cable requirement:
Model
Typical
Amperage
Wire size
Terminal
Torque Value
Dimensions
d (mm)
D (mm)
2.2KW LS
22A
11 AWG
4.5
9.5
1.3 ~ 1.4 Nm
Please follow below steps to implement AC input connection:
1. Before making AC input connection, be sure to disconnect all circuit breakers or disconnectors first.
2. Remove insulation sleeve 10mm for two conductors. And shorten phase L and neutral conductor N 3 mm.
3. Insert AC input wires according to polarities indicated on terminal block and tighten the terminal screws.
L
→
LINE (brown or black)
N
→
Neutral (blue)
4. Make sure the wires are securely connected.
AC Output (Motor) Connection
WARNING! All wiring must be performed by a qualified personnel.
WARNING! It's very important for system safety and efficient operation to use appropriate cable for AC output
connection. To reduce risk of injury, please use the proper recommended terminal and cable size as below.
Recommended terminal types:
Suggested cable requirement:
Model
Typical
Amperage
Wire size
Terminal
Torque Value
Dimensions
d (mm)
D (mm)
2.2KW LS
15A
13 AWG
4.5
9.5
1.3 ~ 1.4 Nm
Please follow below steps to implement AC output connection:
1. Remove insulation sleeve 10mm for two conductors if applying single-phase output or three conductors if
applying three-phase output. And shorten these conductor 3 mm.
2. Please follow below steps to complete output wire connection.