MasterGuard 380LSb Скачать руководство пользователя страница 3

Figure 4

Figures 1, 2, 3, & 4 are reprinted with permission from NFPA 72, National Fire Alarm

Code®, Copyright ©2002, National Fire Protection Association, Quincy, MA 02169. This

reprinted material is not the complete and official position of the National Fire Protection

Association on the referenced subject which is represented only by the standard in its

entirety. National Fire Alarm Code® and NFPA 72® are registered trademarks of the

National Fire Protection Association, Inc., Quincy, MA 02169.

PLACEMENT OF SMOKE ALARMS

THIS EQUIPMENT SHOULD BE INSTALLED IN ACCORDANCE

WITH THE NATIONAL FIRE PROTECTION ASSOCIATION'S

STANDARD 72 (National Fire Protection Association, Batterymarch

Park, Quincy, MA 02269).

For your information, the National Fire Protection Association's

Standard 72, reads as follows:

NFPA 72, 2007 Edition, Chapter 11, Section 11.5.1.1 Where

required by applicable laws, codes or standards for a specific type of

occupancy, approved single and multiple-station smoke alarms shall

be installed as follows:

1) In all sleeping rooms and guest rooms

2) Outside of each separate dwelling unit sleeping area, within 6.4m

(21ft) of any door to a sleeping room, the distance measured

along a path of travel

3) On every level of a dwelling unit, including basements

4) On every level of a residential board and care occupancy (small

facility), including basements and excluding crawl spaces and

unfinished attics

5) In the living area(s) of a guest suite

6) In the living area(s) of a residential board and care occupancy

(small facility)

The installation of additional alarms of either the smoke or heat type

should result in a higher degree of protection. Adding alarms to

rooms that are normally closed off from the required alarms

increases the escape time because the fire does not need to build to

the higher level necessary to force smoke out of the closed room to

the required alarms. As a consequence, it is recommended that the

householder consider the installation of additional fire protection

devices. However, it should be understood that NFPA 72 does not

require additional smoke alarms over and above those called for in

Figures 1, 2, 3 and 4 where required smoke alarms are shown.

Figure 3: IN DWELLING UNITS WITH MORE THAN ONE

SLEEPING AREA, A SMOKE ALARM SHOULD BE PROVIDED TO

PROTECT EACH SLEEPING AREA IN ADDITION TO SMOKE

ALARMS REQUIRED IN BEDROOMS.

In addition to smoke alarms outside of the sleeping areas and in

each bedroom, NFPA 72 requires the installation of a smoke alarm

on each additional level of the dwelling unit, including the basement.

These installations are shown in Figure 4. The living area smoke

alarm should be installed in the living room or near the stairway to

the upper level, or in both locations. The basement smoke alarm

should be installed in close proximity to the stairway leading to the

floor above. Where installed on an open-joisted ceiling, the smoke

alarm should be placed on the bottom of the joists. The smoke

alarm should be positioned relative to the stairway so as to intercept

smoke coming from a fire in the basement before the smoke enters

the stairway.

Figure 2: A SMOKE ALARM SHOULD BE LOCATED BETWEEN

THE SLEEPING AREA AND THE REST OF THE DWELLING UNIT

AS WELL AS IN EACH BEDROOM.

In dwelling units with more than one bedroom area or with

bedrooms on more than one floor, more than one smoke alarm is

required, as shown in Figure 3.

Figure 1:

A SMOKE ALARM SHOULD BE LOCATED ON EVERY

LEVEL OF DWELLING UNIT, INCLUDING BASEMENT, WITHIN

EACH SLEEPING ROOM AND OUTSIDE SLEEPING AREAS.

Where to Locate the Required Smoke Alarms

. The major threat

from fire in a dwelling unit occurs at night when everyone is asleep.

Persons in sleeping areas can be threatened by fires in the remain-

der of the unit; therefore, smoke alarms are best located in each

bedroom and between the bedroom areas and the rest of the unit as

shown in Figure 2.

Figure 1

Figure 2

Figure 3

Figure 4: A SMOKE ALARM SHOULD BE LOCATED ON EACH

LEVEL IN ADDITION TO EACH BEDROOM.

550-0480

Page 3-3

Are More Smoke Alarms Desirable?

The required number of

smoke alarms might not provide reliable early warning protection for

those areas separated by a door from the areas protected by the

required smoke alarms. For this reason, the use of additional smoke

alarms for those areas for increased protection is recommended,

including smoke alarms with visual signals to alert and warn hearing

impaired occupants to a fire. The visual signal must be in the line of

sight of the individual to be seen and effective. The additional areas

include the basement, bedrooms, dining room, furnace room, utility

room, and hallways not protected by the required smoke alarms.

The installation of smoke alarms in kitchens, attics (finished or unfin-

ished), or garages is not normally recommended, because these

locations occasionally experience conditions that can result in

improper operation.

IMPORTANT CONSIDERATION

NFPA recommends replacing smoke alarm(s) every ten (10)

years; why:

Dust, dirt, and other environmental contaminants can affect your

smoke alarm over a prolonged period.

Fast changing industry consensus standards and codes on all

smoke alarms make it advisable to periodically upgrade your

device to maximize life safety.

Assurance that your smoke alarm needs are kept abreast with the

constantly improving electronic technology.

Smoke alarms are recognized as one of the lowest cost ways to

protect dwelling inhabitants against the danger of fire(s). It makes

good common sense to periodically replace and update your

smoke alarm that contributes so much to life safety.

Отзывы: