4.8 Frequency

Range

Accuracy

Resolution

2kHz

±1.5% of rdg ±5digits 

1Hz

5. Accessories

5.1 Supplied with the multimeter

Test Leads  
Battery 

HYTL- 266 

Operating Manual  

9V NEDA 1604 or 6F22

HYS004249A1

5.2 Optional accessory

“K”type  thermocouple  

HYTP - 010

 INSULATION TESTER UNIT 

261

6. Battery replacement

If the sign“BAT”appears on the LCD display, it indicates 
that battery should be replaced. Remove the battery cover 
of case. Replace the exhausted battery with a new one.

       Warning

Before attempting to open the battery cover, be sure that 
test leads have been disconnected from measurement 
circuits to avoid electric shock hazard.

4.5 DC Voltage

Input Impedance: >9M

 

Ω

Over protection:

 

250Vrms AC for 200mV range

                          1000V DC or 750V AC for other range

4.6 Resistance

Overload protection: 250V DC or 250Vrms AC on all ranges.
Open circuit voltage: 700mV 

Range

Accuracy

Resolution

200mV

±5.0% of rdg ±1digit 

0.1mV

2V

±5.0% of rdg ±1digit 

1mV

20V
200V
1000V

±5.0% of rdg ±1digit 
±5.0% of rdg ±1digit 
±0.8% of rdg ±2digits 

10mV
0.1V
1V

Range

Accuracy

Resolution

200

Ω

±1.0% of rdg ±3digits 

0.1

Ω

2k

Ω

±1.0% of rdg ±1digit 

1

Ω

20k

Ω

200k

Ω

2M

Ω

±1.0% of rdg ±1digit 
±1.0% of rdg ±5digits 
±1.0% of rdg ±5digits 

10

Ω

100

Ω

1k

Ω

4.7 Temperature

Range

Accuracy

Resolution

0°C to 400

32

to 752

°C

(

°F 

°F)

400°C to 750

752

to 1382

°C

(

°F 

°F)

0°C to 
750°C

°F 

°F

32

to 

1382

1°C

°F

1

±1.0% of rdg ±3digits ±2.0% of rdg ±1digit 

Display

Terminals and 
earth ground
Measuring Method
Overrange Indication 
Polarity indication
Operating Temperature 
Storage Environment

Power 

Accessories
Low Battery Indication
Optional Accessories
Dimension 
Weight 

3 1/2 digit LCD, 
with automatic polarity indication

1000V dc or 750V rms ac (sine)

“1” Figure only in the display
“-” displayed for negative polarity
0°C to 40°C (32°F to 104°F)

9V alkaline or carbon-zinc battery
(NEDA 1604 )
Operating manual ,set of test leads
“BAT” to left of display
Thermocouple ( K type )
90(W) X 230(D) X 43(H) mm
320g( including battery )

Dual-slope integration A-D converter 

-10°C to 50°C (14°F to 122°F)

3.8 Measuring frequency

4. Specifications

Accuracy is specified for a period of one year after 
calibration and at 18°C to 28°C (64°F to 82°F) with relative 
humidity to 80%.

1. Connect the black test lead to the COM jack and the red 
    test lead to the V

Ω

 jack.

2.Set the rotary switch at Hz position and connect test leads 
    across the source or load under measurement.

NOTE:

1. Reading is possible at input voltage above 10V rms, 
    but the accuracy is not guaranteed.
2. In noisy environment, it is preferable to use shield cable
    for measuring small signal.

3.3 Measuring voltage

1. Connect the black test lead to the COM jack and the red 
    test lead to the V

Ω

 jack.

2. Set the rotary switch at the desired V      or V ~ range 
    position and connect test leads across the source or 
    load under measurement. The polarity of the red lead 
    connection will be indicated along with the voltage value 
    when making DC voltage measurement.
3. When only the figure“ 1 ”is displayed, it indicates 
    overrange situation and the higher range has to be 
    selected.

3.4 Measuring resistance

1. Connect the black test lead to the COM jack and the red 
    test lead to the V  jack.
2. Set the rotary switch at desired   position and connect 
    test leads across the resistor under measurement.

NOTE:

1. If the resistance being measured exceeds the maximum 
    value of the range selected or the input is not connected, 
    an overrange indication“ 1 ”will be displayed.
2. When checking in - circuit resistance, be sure the circuit 
    under test has all power removed and that all capacitors 
    have been discharged fully.

Ω

Ω

3.6 Continuity test

1. Connect the black test lead to the COM jack and the red 
    test lead to the V

Ω

 jack. 

    (The polarity of the red lead is positive“ + ”)
2. Set the rotary switch at      position and connect test 
    leads across two points of the circuit under testing. 
    If continuity exists (i.e., resistance less than about 50

Ω

), 

    built -in buzzer will sound. 

3.7 Measuring temperature

1. Set the rotary switch at °C or °F position and the LCD 
    display will show the current environment temperature.
2. Insert“ K ”type thermocouple into the temperature 
    measuring socket on the front panel and contact the 
    object to be measured with the thermocouple probe. 
    Read LCD display.

       Warning

To avoid electric shock, be sure the thermocouple has been
removed before changing to another function measurement.

3.5 Testing diode

1. Connect the black test lead to the COM jack and the red 
    test lead to the V

Ω

 jack. (The polarity of red lead is“ + ”)

2. Set the rotary switch at       position and connect red 
    lead to the anode, black lead to the cathode of the diode
    under testing. The meter will show the approx. forward 
    voltage of the diode. If the lead connection is reversed, 
    only figure“ 1 ”displayed.

09

10

11

4.2 AC Current

Range

Accuracy

Resolution

20A

±5.0% of rdg ±5digits 

10mA

Frequency Range: 50Hz to 60Hz
Response: Average, Calibrated in rms of sine wave
Overload protection: 1200A within 60 seconds. 
Jaw Opening: 2" (5cm

200A
400A
1000A

±2.5% of rdg ±5digits 
±2.5% of rdg ±5digits 
±3.0% of rdg ±5digits 

100mA
1A
1A

Note

>600A

4.3 Insulation test

Range

Accuracy

Resolution

±2.0% of rdg ±2digits 
±4.0% of rdg ±2digits 
±5.0% of rdg ±2digits 

Note

20M

Ω

2000M

Ω

1M

Ω

1k

Ω

>500M

Ω

4.4 AC Voltage

Range

Accuracy

Resolution

200V

±1.0% of rdg ±4digits 

0.1V

Input Impedance: >9M on all ranges
Overload protection: 1000V DC or 750V AC on all ranges
Frequency Range: 50Hz to 500Hz
Response: Average, calibrated in rms of sine wave

750V

±1.0% of rdg ±4digits 

1V

< 600A

< 500M

Ω

HYS006730

6. Depress the PUSH 500V push-push switch, the 500V on 
    red LED lamp will light. Clamp meter display reading is 
    the insulation resistance value. If the reading is below 
    19M

Ω

, change clamp meter and insulation tester unit to 

    20M

Ω

 range, can be increase the accuracy.

7. If the insulation tester unit is not use, the power switch 
    must shift to power OFF position, and the test leads must 
    leave the E. L input connect. That can be increase battery
     life and prevent electrical shock hazard.

4.1 General

(With option 500V insulation tester unit)

Содержание M266 Series

Страница 1: ...0 1000 OFF 1000 200 V 750 V 1000 200 20k 20M 2000M Ω Ω Ω Ω A A EXTERNAL UNIT WITH 261 OPTION 500V INSULATION TESTER EXTERNAL UNIT MAX 1000A CAT ll 1000V CAT lll 600V M266 CLAMP METER M266SERIES DIGITAL CLAMP MULTIMETER OPERATOR S INSTRUCTION MANUAL ...

Страница 2: ...with safety standards can be guaranteed only if used with test leads supplied If necessary they must be replaced with the same model or same electronic ratings Measuring leads must be in good condition 1 2 During use Never exceed the protection limit values indicated in specifications for each range of measurement When the meter is linked to measurement circuit do not touch unused terminals When t...

Страница 3: ...ities are observed the meter can not be used any more and it has to be checked out Never use the meter unless the back cover and the battery cover are in place and fastened fully Do not use abrasives or solvents on the meter use a damp cloth and mild detergent only 2 Description This meter is one of a series portable 3 1 2 digital clamp meter for measuring DC and AC Voltage AC current resistance c...

Страница 4: ...ransformer jaws When the finger press on the TRIGGER is released the jaws will close again 2 3 Data hold A push switch Push ON Push OFF All ACA ACV DCV Hz ranges with this feature 2 4 Input jacks This meter has three input jacks that are protected against overload to the limits shown During use connect the black test lead to COM jack and connect red test lead to V jack The red test lead is depende...

Страница 5: ...PANEL 1 TRANSFORMER JAWS 2 TRIGGER 3 DATA HOLD SWITCH 4 ROTARY SWITCH 5 LCD DISPLAY 6 INPUT JACKS 7 DROP PROOF WRIST STRAP 8 TEMPERATURE MEASURING SOCKET 9 BARRIER OR TACTILE INDICATOR 1 9 3 8 4 5 6 7 2 HOLD BAT ...

Страница 6: ... higher range have to be selected 3 2 Insulation Test Option 500V insulation tester unit 1 Connect the insulation tester unit VΩ COM EXT three banana plugs to the clamp meter VΩ COM EXT 2 Set the rotary switch of clamp meter at 2000MΩ position 3 Set the insulation tester unit range switch to the 2000MΩ position 4 Uses the insulation tester unit of the test leads connects its L E input connect to b...

Страница 7: ...t test leads across the resistor under measurement NOTE 1 If the resistance being measured exceeds the maximum value of the range selected or the input is not connected an overrange indication 1 will be displayed 2 When checking in circuit resistance be sure the circuit under test has all power removed and that all capacitors have been discharged fully Ω Ω 6 Depress the PUSH 500V push push switch ...

Страница 8: ...nment temperature 2 Insert K type thermocouple into the temperature measuring socket on the front panel and contact the object to be measured with the thermocouple probe Read LCD display Warning To avoid electric shock be sure the thermocouple has been removed before changing to another function measurement 3 5 Testing diode 1 Connect the black test lead to the COM jack and the red test lead to th...

Страница 9: ... left of display Thermocouple K type 90 W X 230 D X 43 H mm 320g including battery Dual slope integration A D converter 10 C to 50 C 14 F to 122 F 4 Specifications Accuracy is specified for a period of one year after calibration and at 18 C to 28 C 64 F to 82 F with relative humidity to 80 1 Connect the black test lead to the COM jack and the red test lead to the VΩ jack 2 Set the rotary switch at...

Страница 10: ... 5digits 100mA 1A 1A Note 600A 4 3 Insulation test Range Accuracy Resolution 2 0 of rdg 2digits 4 0 of rdg 2digits 5 0 of rdg 2digits Note 20MΩ 2000MΩ 1MΩ 1kΩ 500MΩ 4 4 AC Voltage Range Accuracy Resolution 200V 1 0 of rdg 4digits 0 1V Input Impedance 9M on all ranges Overload protection 1000V DC or 750V AC on all ranges Frequency Range 50Hz to 500Hz Response Average calibrated in rms of sine wave ...

Страница 11: ...igit 0 1mV 2V 5 0 of rdg 1digit 1mV 20V 200V 1000V 5 0 of rdg 1digit 5 0 of rdg 1digit 0 8 of rdg 2digits 10mV 0 1V 1V Range Accuracy Resolution 200Ω 1 0 of rdg 3digits 0 1Ω 2kΩ 1 0 of rdg 1digit 1Ω 20kΩ 200kΩ 2MΩ 1 0 of rdg 1digit 1 0 of rdg 5digits 1 0 of rdg 5digits 10Ω 100Ω 1kΩ 4 7 Temperature Range Accuracy Resolution 0 C to 400 32 to 752 C F F 400 C to 750 752 to 1382 C F F 0 C to 750 C F F ...

Страница 12: ...ry K type thermocouple HYTP 010 INSULATION TESTER UNIT 261 6 Battery replacement If the sign BAT appears on the LCD display it indicates that battery should be replaced Remove the battery cover of case Replace the exhausted battery with a new one Warning Before attempting to open the battery cover be sure that test leads have been disconnected from measurement circuits to avoid electric shock haza...

Отзывы: