Masport PG36-3 Gas Inbuilt
6
INSTALLATION
Min. 6"
(152mm)
Min. 8"
(203mm)
30-1/2"
(775mm)
T
o
p
o
f
Unit
Min.
32"
(1016mm)
to
Ceiling"
Clearances for Bay or Flush Front
Clearances for Barcelona Trim
NOTE: The minimum floor clearance must
be maintained from the top surface of the
carpeting, tile, etc.
Minimum Clearance from Top of Unit to:
Mantel* Minimum
7"
(177mm)
Ceiling from top of unit.
32"
(1016mm)
Side Wall Clearance
Bay or Flush Front
6"
(152mm)
Barcelona Trim
8"
(203mm)
Horizontal Flue Clearances
Top
2"
(51mm)
Side
1-1/2" (38mm)
Bottom
1-1/2" (38mm)
Vertical Flue Clearances 1-1/4" (32mm)
Alcove Clearances**:
Max. Depth
36"
(914mm)
Min. Width
48"
1219mm)
Min. Height
72"
1829mm)
* see mantle clearance instructions
(pages 7 & 8).
**Approved for one sidewall installation
only when using Barcelona Trim
CLEARANCES
The clearances listed below are Minimum dis-
tances unless otherwise stated:
A major cause of chimney related fires is
failure to maintain required clearances
(air space) to combustible materials. It is
of the greatest importance that this fire-
place and flue system be installed only in
accordance with these instructions.
Clearance to Combustibles from:
Back
0"
(0mm)
Side
0"
(0mm)
Floor
0"
(0mm)
Diagram 1
LOCATING YOUR
GAS STOVE
1) When selecting a location for your stove,
ensure that the clearances outlined on this
page are met.
2) Provide adequate clearances for servic-
ing.
3) The appliance must be installed on a flat,
solid, continuous surface (e.g. wood, met-
al, concrete). This may be the floor, or
raised up on a platform to enhance its visual
impact. If the appliance is going to be in-
stalled on carpeting, combustible linoleum
tile or other combustible material other than
wood flooring, the appliance must be in-
stalled on a metal or wood panel extending
the full width and depth of the appliance.
4) The PG36 Co Axial Flue Gas Fireplace can
be installed in a recessed position or framed
out into the room as in A, B, C, D. See
Diagram 1.
MANUFACTURED
MOBILE HOME
ADDITIONAL
REQUIREMENTS
1) Ensure that structural members are not cut
or weakened during installation.
2) Ensure proper grounding using the #8
ground lug provided. See page 28.
A)
Flat on Wall
B)
Flat on Wall Corner
C)
Recessed into Wall/Alcove
D)
Corner
5) This appliance is Listed for bedroom instal-
lations when used with a Listed Millivolt
Thermostat. Some areas may have further
requirements, check local codes before
installation.
6) The PG36 Co Axial Flue Gas Fireplace is
approved for alcove installations, which
meet the clearances listed on this page.
7) We recommend that you plan your installa-
tion on paper using exact measurements
for clearances and floor protection before
actually installing this appliance. Have an
authorized inspector, dealer, or installer
review your plans before installation.
Note: For flue terminations see page 10.
WARNING
Fire hazard is an
extreme risk
if these clearances
are not adhered to.
For more Barcelona Framing and Installa-
tion Notes, see page 8.
BARCELONA FRAMING NOTE: If the Bar-
celona Trim is to be installed, the
front face of the fireplace must be
made of non-combustible material.
See Diagram 1.
Diagram 1