Modena Installation
and Service Manual 6
08/06
SECURING THE HEATER TO THE WALL
(Fig. 4)
Select a suitable site for the heater. Remove the front panel and wall plate from the heater (Fig.2). Mark
the position of the four securing holes using the wall plate as a template, ensuring the wall plate is level
and that the letter ‘T’ is at the top.
Drill and plug the wall with suitable wall plugs. Secure the wall plate to the wall using suitable screws
ensuring the wall plate is level. Secure the heater body to the wall plate using the M5 nuts and
washers provided.
GAS CONNECTION
The gas inlet connection is located on the gas valve underneath the heater at the right hand side (Fig.4).
The gas supply may connect to the heater up the wall or by concealed connection below the heater.
Concealed pipes should not be routed through walls without being protected by sleeving or conduit. No
more than 2.5m of 8mm dia pipe must be used to avoid unnecessary pressure drops.
An isolation tap should be provided on the gas inlet to the heater.
If a concealed gas connection is to be made, the supply pipe should always be sleeved through walls
and floors using the shortest possible route.
When making the gas connection ensure that the front panel will not foul the pipe or isolation tap.