background image

 

 

 

Ref No.: m92A/om/101 

 

                                                                                                                                                         Issue No.: 15 

 

2 | 

P a g e

 

 

9000 U 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

 

 

 

9000U  Series  are  rugged  4  wire  isolator  designed  to  accept  custom-built  and 
wide  range  of  voltage  and  current  input  signals.

 

Signal  is  then  isolated  and 

converted to standard instrumentation signals, acceptable to commercially off the 
shelf (COTS) automation products. 

 

9000U  Series  offer  a  wide  range  of  input  /  output  signal  types  like  mA,  mV, 
VDC which are factory settable as per customer requirements. 

 

Built in transmitter power supply (TPS) can drive filed transmitters in case of 4-
20mA DC input signal.  

 

9000U Series act as signal distributor when used with more number of outputs. 

 

9000U Series are flexible for DIN rail mounting and easily installable.  

 

ISOLATED CONVERTER 

9000

 U SERIES

 

 
 

 

 
 

 

Three pot Isolation 

 

Mains / DC operated 

 

DIN Rail / Back panel  mounted 

 

Built in transmitter powering 

 

Accepts non-std. signal input 
option 

 

Up to four isolated outputs of 
different types available 

 
 

D

IMENSION

 

 

F

OR 

SOP/

 

DOP

 

 

55mm x 75mm x 110mm   

 85V-265VAC

45-65Hz

100-300VDC

 

F

OR 

TOP/

 

FOP

 

 

100mm x 75mm x 110mm 
 

 

S

PECIFICATION

 

 

Input  

 

Input Type 

Voltage/ Current/ Potentiometric/ RTD(PT100) 

Input Range 

For Voltage : Min: 0 to ±10mV, Max: 0 to ±600VDC 
For Current : Min: 0 to ±1mA, Max: 0 to ±100mA 
For Potentiometric : 0 to 10K 

 

For RTD(PT100): Zero range:-200˚C to 0˚C, 
Span range:100˚C to 850˚C 

Input Impedance 

For Current I/

< 51 

; For Voltage I/P > 1 M

 

Output

 

 

Output  Type 

Voltage/ Current (Reverse range in output is supported with 9000U) 

Output  Range 

For Voltage : Min: 0 to ±100mV, Max: 0 to ±10VDC 
For Current : Min: 0 to ±1mA, Max: 0 to ±10mA/+20mA 

Response Time 

< 50 ms  

Accuracy      

± 0.1% of FS / 0.25% of FS in RTD I/P 

Output Load resistance 

For 0/4mA  to 20mA : 

 750 

 

For -10mA to +10mA : 

 910 

 

For -1mA to +1mA and 0 to 1mA : 

 9.1K 

 

For 0 to ±1V : 

 200 

 

For 0 to ±5V : 

 1K 

 

For 0 to ±10V :  

 2.7 K

Ω

 

Auxiliary Output 

Transmitter Power Supply 24VDC 
Max current Limit: 26mA  

Power Supply

 

 

Power Supply 

85-265VAC 45Hz to 65Hz,100-300VDC / 18-36VDC on request. 

Power Consumption 

Less than 10VA 

CMRR 

>100dB 

NMRR 

>70dB 

Isolation 

Power to Input / Output, Input to Output, Output to Output –  
2.0KV AC for 1 minute 

Environmental 

 

Operating temperature 

0 to 55ºC 

Temp. Co-efficient 

100 PPM 

Relative humidity  

30 to 95% RH (Non-Condensing) 

Protection 

Conformal Coating on PCB 

Physical 

 

Mounting Type 

DIN RAIL (35 mm) Mounting 

Dimensions 

55mm x 75mm x 110mm  [For SOP/DOP] 
100mm x 75mm x 110mm [For TOP/FOP] 

Weight 

Less than 250 gm [For SOP/DOP],   
Less than 450 gm [For TOP/FOP] 

Terminal 

 

Terminal Block 

UL,CSA standard  

Terminal Cable Size 

2.5mm

2

  

 

Isolated Convertor 
9000 U Series 

Отзывы: