7.10 LL Logic
LL-low, low AL1-very low, AL2-low.
In this logic if “UP Scale” condition has been selected than in OPEN sensor
condition ALARM 1 and ALARM 2 will be in the NORMAL condition and will work
according to the following tables 7.4, 7.5, 7.6, 7.7.
If “DOWN Scale” Condition has
been selected for this logic than in OPEN sensor condition ALARM 1 and ALARM 2
will be in the ABNORMAL State of operation.
7.11 Process value on Display
PV>105% OR
PV< -5% OR PV
open
-5%
0%
100%
105%
zero
span
mV
group
OPEN
UNDER
-19999
99999
OVER
-19999
99999
15mV
OPEN
UNDER
-19999
99999
OVER
-19999
99999
30mV
OPEN
-250
0
5000
5250
0
5000
75mV
OPEN
-250
0
5000
5250
0
5000
30mV
Table 7.1.
Note
: If maximum value of zero and span then process value will display OVER/UNDER
message until value crosses 5% of selected group of mV(15mV or 30mV or 75mV). If
value of zero and span is less than maximum value of zero and span then process value
will display open message until value crosses 5% of selected group of mV (15mV or 30mV
or 75mV). Process value greater than5% of selected group of mV (15mV or 30mV or
75mV) then display will show OPEN message. Retransmission o/p will follow 5% of
display range and then it will give fixed o/p depending up on input OPEN sensor selection.
7.12 Retransmission output during OPEN sensor
I/P
0-20 mA O/P
4-20 mA O/P
UP Scale O/P
DW Scale O/P
UP Scale O/P
DW Scale O/P
SGI
21.00
0.0
20.8
3.2
Table 7.2.
I/P
0-10 V O/P
0-5 V O/P
1-5 V O/P
UP Scale
O/P
DW Scale
O/P
UP Scale
O/P
DW Scale
O/P
UP Scale
O/P
DW Scale
O/P
SGI
10.50
0.0
5.25
0.0
5.20
0.80
Table 7.3.
Above mention value in the table 7.2, 7.3 will come only after calibration for specific o/p
type i.e. Voltage/Current.