User Manual
39
40005E (Enhanced Bargraph Indicator)
REF NO: m42B/om/101
Issue No:02
A4.tp
Alarm 4 Type
lo
/
Hi
0 : LOW
1: HIGH
0 (for all 2
channels)
(A4.tP)
CS.mp
Control Set point
mapping
See DO(Digital
Output)
Configuration
Refer
note 1
Digital Output is
required
(CS.mP)
CS.tp
Control Set point type
lo
/
Hi
0 : LOW
1: HIGH
0 (for all 2
channel)
Control Output is
required
(CS.tP)
W.D.op
Watchdog Output
dsbl
/
enbl
0 : Disable
1: Enable
Refer
note 1
-
(W.d.oP)
W.D.mp
Watchdog Mapping
See DO(Digital
Output)
Configuration
Refer
note 1
Digital Output is
required
(W.d.mP)
DO(Digital Output) Configuration:
Total numbers of relays in 40005E are 5. For one channel maximum Five numbers of DOs
can be assigned. Among them one DO can only be assigned for control operation and four remaining
DOs can be assigned for Alarm/Trip operatoin. Below example shows different configuration and
different mapping of different DOs to 2 channels.
Table 15 DO(Digital Output) Mapping Number and its description
Chan
nel
Numb
er
AS1 .
Mapping
DO
number
for
ASP1
AS2 .
Mapping
DO
number
for
ASP2
AS3 .
Mapping
DO
number
for
ASP3
AS4 .
Mapping
DO
number
for
ASP4
CSP.
Mapping
DO
number
for CSP
Watch -
dog
Mappin
g
DO
number
for
W.D.MP
1
Relay 3
3
Relay 3
3
None
0
Relay 2
2
Relay 1
1
Relay 5
5
2
None
0
Relay 4
4
Relay 4
4
Relay 4
4
None
0
Note 1:
1)
None means no DO(Digital Output) is assigned to particular channel.
2)
DO number = 0 represents “
None
” . DO Number = 1 to 5 represents “
Relay No. 1 to Relay
No. 5
3)
If one particular DO is mapped to any channel in control set point mapping
(
C.S.MP.)
configuration, it can not be mapped to any other channel in any type of mapping( In
above example, Relay-1is mapped to channel number 1in control set point mapping
configuration shown in
. So it can not be assigned to any other channel in Control set
point mapping
( C.S.mp.) or
Alarm Set point 1 mapping
(A1.MP)
or
Alarm Set point 2
Mapping
(A2.MP) or
Alarm Set point 3 mapping
(A3.MP)
or
Alarm Set point 4
Mapping
(A4.MP)
as shown in Table 15.
4)
Maximum one channel can be assigned to control set point mapping
(C.S.MP)
configuration.
In above example, Relay-1 can not be assigned to second channel.
5)
Same number of DO (other than mapped to control set point mapping) can be mapped to
multiple number of Channels in Alarm set point 1 mapping
(A1.MP)
, Alarm set point 2
mapping
(A2.MP) ,
Alarm set point 3 mapping
(A3.MP)
and Alarm set point 4 mapping
(A4.MP).
In above example, Relay 4 is assigned to channel 2 in
AS2. Mapping , AS3.