4.0   ELECTRICAL CONNECTIONS

4.1.

Battery connection

A battery of 12V, 70Ah, is needed to start off the
generator.

The battery must not be smaller than the rated
capacity.

It should be connected to the terminal of the generator (fig.
15) with cables of section 25 mm

2

 up to distances of 16'

6" and with cables of section 35 mm

2

 for longer distances,

and following the sequence of operations described below:
- First connect the positive pole (

+

) of the battery to the

terminal marked with the symbol (

+

) on the generator.

- Then connect the negative pole (

-

) of the battery to the

terminal marked with the symbol (

-

) on the generator.

- Wipe the connections with special mineral grease to

protect against oxidation and corrosion.
The generator includes an electronic device to auto-
matically recharge the start-up battery, giving
15 A, at a voltage of 12 V, when fully charged.

Install the battery in a well-ventilated area, away
from the generator and from any device which might
produce heat or sparks.
Periodically check the state of the connections of the
terminals and the water level of the battery. If the
cables need to be disconnected, follow the instruc-
tions for connection in reverse order.
Do not invert the poles of the connecting cables
since serious damage might be caused to the gen-
erator and the battery.
Do not connect other loads to the battery.

In order to reduce galvanic currents to a minimum, the
(

-

) of the battery of the electric generator should not be

connected to the (

-

) of the other batteries on board.

4.2

Control panel connection

Two different types of terminal boards are available; to
be installed on bridge and connectable to the genset in
order to command the start/stop functions.
Both types of boards are equipped with 65' cable with a
plug-in socket terminal end to be fitted on the genset.
Plug in one end of the connection cable in the socket
placed on the inner board of the genset and the
opposite end in the remote control panel ( fig.16 ref.1 ).

       WARNING

     DANGER

remain empty to allow air to pass through when the
unit is switched off. (see fig. 9)

It is recommended that the drain hose from the anti-siphon
valve be fed into the bilge, as small amounts of water might
be drained through it during normal operation. The cooling
circuit is connected to the heat exchanger fitting as shown
in Fig. 10.

2.6

Drainage system

The exhaust system of the generator must be separate
from that of the main motors

The length of the tube from the highest point of the
exhaust system to the muffler should not exceed 80".
This is to prevent the water left in the exhaust system
from returning to the motor after filling the water
lock muffler, when the unit is turned off.

1

- Water lock muffler

This dampens the noise of the exhaust and stops the
water flowing back towards the motor. The muffler
should be installed no less than 40" away from the
generator and positioned at a height as per fig. 4/5.

2

- Silencer

This further reduces noise. It should be installed no
more than 40" from the exhaust through-hull.

3

- Exhaust through-hull

This must be installed in a position that is constantly
above sea level in all the vessel’s possible conditions
of use.

3.0  FUEL CIRCUIT

The unit is fed by diesel fuel through the tubes marked

fuel inlet

”(fig. 12 ref. 2 ) and “

fuel outlet

” (fig. 13 ref. 3).

This fuel outlet is used for the return of the excess fuel.
There is no need for filters in connections to the fuel tank,
since the unit already contains a fuel filter; however it is
advisable to fit a shut-off onto the fuel supply line down-
stream of the tank and a single-acting valve (check valve)
to prevent the fuel system emptying for any reason. Use
a valve with a 50 millibar opening. (Max head 31".)
The fuel lines should be in diesel fuel-resistant rubber, of
inner diameter 8 mm (.31").

For further information, read the engine instruction
manual, supplied by the engine manufacturer.

       WARNING

INFORMATION

11

Содержание Marine IS 9.5

Страница 1: ...IS9 5 13501 INSTALLATION MANUAL ...

Страница 2: ...Fig 1 Fig 2 1 2 Fig 3 Fig 4 2 32 7 8 31 1 1 16 3 8 22 3 8 3 3 3 5 32 7 8 27 1 8 2 2 3 8 MAX 40 MAX 40 MAX 40 MIN 12 MIN 8 M AX 80 MIN 13 5 IS9 5 ...

Страница 3: ...Fig 6 3 Fig 6 MAX 40 MAX 40 MIN 12 MIN 8 M A X 8 0 MIN 13 5 IS9 5 MAX 40 MIN 6 MAX 40 MIN 12 MIN 8 MAX 40 IS9 5 MAX 16 6 MIN 13 5 M A X 8 0 IS9 5 MIN 6 MAX 40 MIN 12 MIN 8 MAX 40 MAX 16 6 MIN 12 M A X 8 0 MIN 13 5 ...

Страница 4: ...Fig 9 1 Fig 8 Fig 12 Fig 11 Fig 10 1 2 3 4 Anti siphon valve 4 ...

Страница 5: ...Fig 14 Fig 13 1 2 1 3 Fig 15 1 5 ...

Страница 6: ...Fig 16 Fig 17 GEN LOAD MAIN 1 6 ...

Страница 7: ...Fig 18 IS9 5 7 ...

Страница 8: ... that significant attention must be paid in order to prevent serious danger which could lead to injury or death A condition which may occur during the lifetime of a product system or plant that has the potential for human injury damage to property damage to the environment or economic loss Indicatesthatparticularattentionmustbepaidinordertopreventseriousconsequenseswhich could reselt to tangible g...

Страница 9: ...SYSTEM SUPPLIED BY MASE HASBEENMODIFIEDTOPREVENTSOLIDOBJECTS FROMENTERINGTHESYSTEMANDBLOCKINGIT IFOTHERMATERIALSAREUSED MORECAREAND MOREFREQUENTCLEANINGISNECESSARY The baffle system might cause the following problems a If installed with the slots facing the bow In this case during navigation and with the electric generator off pressure is accumulated in the water infeed duct which might cause the ...

Страница 10: ...5 Components The raw water intake system must be separate from the one for the engines propelling the boat 1 Direct raw water intake 1 2 If the unit is installed more than 40 above the water line a check valve should be fitted after the sea intake fig 8 ref 1 to prevent the water circuit emptying when the motor is off If this empties the rotor of the water pump might be damaged during start up for...

Страница 11: ...e end of the connection cable in the socket placed on the inner board of the genset and the opposite end in the remote control panel fig 16 ref 1 WARNING DANGER remain empty to allow air to pass through when the unit is switched off see fig 9 Itisrecommendedthatthedrainhosefromtheanti siphon valvebefedintothebilge assmallamountsofwatermight bedrainedthroughitduringnormaloperation Thecooling circui...

Страница 12: ...on power can be picked up both at 120 VbetweenpointsF1 F2 andP1 P2 andat240Vbetween points P1 and F2 at the same time as shown in the diagram in fig 15 ref 3 If the serial connector fig 15 ref 3 is used to draw a voltage of 120V 60Hz the current drawn off must not exceed 50 of the rated current Ensurethatthesumoftheloadstobesupplieddoesnot exceed the nominal power of the electric generator The gen...

Отзывы: