9 Operation
Maschinenfabrik Reinhausen GmbH 2022
95
8595017/00 EN
TAPCON
®
250
Configuring DIOs
1. Go to menu item
Settings > DIO configuration
.
2. Where necessary, select the buttons ▲ or ▼ to sort the properties in a
column alphabetically.
3. Configure the properties as desired.
4. Press the
Accept
button.
5. Confirm the security prompt with
Yes
to save the changes.
9.1.10 Event management
The device is equipped with event management, which allows you to detect
various device operating statuses and to adapt the behavior of the device.
An overview of all possible events is given in the Event messages chapter.
9.1.10.1 Displaying and acknowledging events
Displaying events
► Go to
Events
.
ð
A list of currently pending events appears.
Acknowledging events
Acknowledgeable events must be acknowledged in the event overview so
that they are no longer displayed. All other events are automatically removed
once the cause has been fixed (e.g. limit value is no longer exceeded).
To acknowledge the events, proceed as follows:
► To acknowledge the events, highlight the desired events in the
col-
umn, then press the
Acknowledge
button.
ð
The events have been acknowledged.
9.1.10.2 Displaying event memory
Past events are stored in the event memory. The following information is dis-
played:
Column Description
#
Consecutive number of events
No.
Event number for clear identification
Event category:
▪ Error (red)
▪ Warning (yellow)
▪ Info (gray)
Event
Event text