11.7. Connections of Sensor
11.7.1.
Transmissible pressure gauge: working voltage 4~13VDC, output 0~10VDC. Wiring method is shown as below.
11.7.2.
24V pressure transmitter: working voltage range 10~30VDC, output 4~20mA.
Sensor with two cables
Sensor with three cables
Note:
“Pressure transmitter with two cables will be connected from end 1 to 24V electric terminal and from end 2 to Al1 terminal.
Note:
The blue cable will be connected to Al1 terminal and the brown cable will be connected to 24V electric terminal.
Note:
(+) end of the temperature sensor connection will be connected to 24V electric terminal and its (-) end will be connected to Al1
terminal. In addition, if it is required to operate above the set temperature, the
F3.06
parameter will be set to
011
. If it is required to operate
below the set temperature, the
F3.06
parameter will be set to
010
.
11.7.3.
10V pressure transmitter: working voltage range 10DC, output 4~20mA
11.7.4.
Closed contact floater connection is as follows:
-
There are 3 cables, the blue and black ones will be used for connection.