Evacuate/reclaim via the piecing pliers to ensure the 
system is empty of  R-600a before any system work is 
performed. 

GAS 

LEAi< 

LOCATOII 

The recovery cylinder must be evacuated  (no air inside) 
prior to accepting  R-600a. 

The recovery cylinder must not be filled more than 45% 
safe fill level and refrigerants must not be mixed. 

The  recovery cylinder  must  be clearly  marked  with  R-
600a  and  Flammable  Warning  labels. 

Ensure proper ventilation during recovery/reclaiming of  R-

600a. 

Start vacuum pump/recovery pump prior to piercing the 
compressor process tube. 

Follow recovery/reclaim OEM  instructions for the specific 

equipment used. 

SYSTEM  REPAIR 

Ensure no residual  R-600a refrigerant is left within the 
system prior to repair  (simple venting is not sufficient). 

Evacuate and charge with dry nitrogen for leak checks. 

Repair leaks or replace system parts as required. 

R-600A Specifications

When re-brazing,  the system must be purged with dry 
nitrogen and at least one access point open to the 
atmosphere. 

When re-brazing,  proper ventilation is required along with 
constant monitoring for the presence of R600a refrigerant. 

The filter dryer must be replaced any time the sealed 
system is serviced. 

No system should be open to the atmosphere for longer 

than  15 minutes to avoid moisture migration into the 
system components. 

LEAK  DETECTION 

After removal of the  R-600a,  the unit can be charged with 
dry nitrogen or helium. 

Electronic leak detection or soap solution can be used to 
check for  nitrogen/helium  leaks. 

Never use a halide torch or lighted match to check the 

system for leaks at any time. 

The high side of the refrigeration system  (compressor 
discharge to outlet of drier) must be leak tested with the 
compressor running. 

18

Содержание MLBV215

Страница 1: ...I G I N A L R E F R I G E R A T I O N E X P E R T S S I N C E 1 8 9 2 F O R M O D E L M L R E 2 2 4 OWNER S GUIDE MARVEL UNDERCOUNTER REFRIGERATION T H E O R I G I N A L R E F R I G E R AT I O N E X...

Страница 2: ...marketing marvelrefrigera tion com and we might feature your Marvel home design on our website and social media Thank you again for investing in Marvel for your home XXXXXXXXXXXX XXXXXXXXXXXX MARVEL...

Страница 3: ...Your Appliance Electrical Maintenance Care and Cleaning Stainless Steel Maintenance Extended Non Use Operating Instructions Interior Adjustments Energy Savng Tips Service Obtaining Service Product Li...

Страница 4: ...nd care must be exercised when installing maintaining or operat ing this appliance Recognize Safety Symbols Words and Labels WARNING WARNING You can be killed or seriously injured if you do not follow...

Страница 5: ...lace The owners manual is shipped inside the product in a plastic bag along with the warranty registration card and other accessory items Important Keep your carton and packaging until your appliance...

Страница 6: ...rrupters GFCI are prone to nui sance tripping which will cause the appliance to shut down GFCI s are generally not used on circuits with power equip ment that must run unattended for long periods of t...

Страница 7: ...ver shelf is secure on the shelf supports by pressing down on the shelf before loading the shelf CAUTION Grasp the shelf by the front with both hands and rotate the front of the shelf up then lift the...

Страница 8: ...rcuit Not shared with other appliances 5 When initially loading your new product or whenever large quantities of warm contents are placed within refrigerated storage compartment minimize door openings...

Страница 9: ...upon the installation location environmental and usage conditions Choosing a Cleaning Product The choice of a proper cleaning product is ultimately that of the consumer and there are many products fro...

Страница 10: ...rsonal preference and provides the proper storage for your stored contents 11 When on vacation or away from home for extended pe riods set the appliance to warmest acceptable tem perature for the stor...

Страница 11: ...low ice to thaw naturally 4 Clean and dry the interior of the unit Ensure all water has been removed from the unit 5 The door must remain open to prevent formation of mold and mildew Open door a minim...

Страница 12: ...rt section In all correspondence regarding service be sure to give the service number serial number and proof of purchase Try to have information or description of nature of the problem how long the a...

Страница 13: ...in question The part that caused the damage must be returned to Marvel in its entirety The part must be clearly labeled with the serial number of the unit it was removed from the date and the service...

Страница 14: ...y labor 2021 04 23 050H 1 I I I Year Warranty Claims Day Factory use Only Units must be registered prior to warranty submittal Customers may register at www marvelrefrigeration com A proof of purchase...

Страница 15: ...er and part description Some parts will require color or voltage information Marvel requires the return of original parts we will inform you when the parts order is taken This requirement will be note...

Страница 16: ...Of PROPERTY IN ACCORDANCE WITH FEDERAL OR LOCAL REGULATIONS FLAHHABLE REFRIGERANT USED R 600A Specifications Gloves and Eye Protection must be used R 600a is considered non toxic but is flammable when...

Страница 17: ...ended that a simple LPG gas detector is on site during service Ensure that all R 600a is removed from the system prior to brazing any part of the sealed system Only a clean dry leak free system should...

Страница 18: ...uate and charge with dry nitrogen for leak checks Repair leaks or replace system parts as required R 600A Specifications When re brazing the system must be purged with dry nitrogen and at least one ac...

Страница 19: ...microns prior to charging Weigh in the R 600a charge using a refrigerant scale run compressor an extra two minutes to clear the charging hoses Seal the Schrader Type access port a proper cap and seal...

Страница 20: ...um temperature temperature cool cool No Gas 0 PSIG to 25 Room Cool to hot temperature cool System Diagnosis Guide Condenser Capillary Evaporator Wattage Tube Very hot Warm Cold Normal Hot to warm Cool...

Страница 21: ...21...

Страница 22: ...nce accident or improper use maintenance instal lation service repair acts of God fire flood or other natural disasters The product must be installed operated and maintained in accordance with the Mar...

Страница 23: ...e without notice Such revisions do not entitle the buyer to corresponding changes improvements additions replacements or compensation for previously purchased products www marvelrefrigeration com 1260...

Отзывы: