Marvair Marine SMM05ACP Скачать руководство пользователя страница 8

SMM Air Conditioner 

 

12 VDC Owner’s Manual 5/09 

 

Page 8 of 13 

Chapter 6 – Troubleshooting 

Troubleshooting Guide 

PROBLEM/SYMPTOM  

LIKELY 

CAUSE(S) 

 

CORRECTION 

The unit does not 

operate. 

  1. Power supply problem. 

 

2. Tripped breaker/disconnect. 
3. Thermostat 

  1. Check voltage at power supply.  Check wiring to 

unit and external breakers or fuses. 

2. Check circuit protection devices for continuity. 
3. Setpoint may be too high if in cooling mode or too 

low if in heating mode; check unit and reset.  

Thermostat may be out of calibration or otherwise 

defective.  Also check for loose connection(s). 

Blower runs but 
compressor does not 

start. 

  1. Power supply problem. 

 

2. Thermostat 

 

 

 
 

3. Safety switches are 

tripping out unit. 

 

4. Loose or defective 

wires. 
 

5. Compressor 

 

 
 

 

6. Refrigerant leakage or 

loss. 

7. Control board 

 

 

  1. Check voltage at power supply.  Voltage at unit 

must be + 10% of rated nameplate voltage. 

2. Check the thermostat and unit for loose wires.  

Secure any loose connection. Check location of 

sensor and make sure that it does not touch the 

indoor coil.  The sensor and/or thermostat should 
be replaced if defective. 

3. Check for water flow.  Check refrigerant charge.  

Check switches for loose wire connection, broken 

or burned contacts.   

4. Tug on wires to see if they will separate from their 

connections.  Replace terminals if they are loose 
or weak. 

5. Check for electrical shorts, ground and open 

circuits.  Replace compressor if defective.  If 

electrical checks are ok, install a start capacitor 
and direct wire to see if the compressor will start.  

If this fails, remove and replace the compressor. 

6. Locate leak(s), reclaim, repair, evacuate and 

recharge unit with refrigerant. 

7. Verify that power is being provided from the 

control board.  Replace control board if it is 

defective. 

Compressor runs, but 
blower will not run. 

  1. Blower motor capacitor 

 

2. Blower motor. 

 

3. Power supply problem. 

 

4. Control board 

  1. Verify capacitance, check for electrical shorts and 

ground.  If defective, replace. 

2. Check for electrical shorts, ground and open 

circuits.  Replace blower motor if it is defective. 

3. Check voltage at power supply.  Voltage at unit 

must be + 10% of rated nameplate voltage. 

4. Verify that power is being provided from the 

control board.  Replace control board if it is 

defective. 

Содержание Marine SMM05ACP

Страница 1: ...interizing the System 7 Chapter 6 Troubleshooting 8 Chapter 7 Wiring Diagram 10 Chapter 8 Spare Parts List 11 Chapter 8 Warranty 12 Manufactured By Marvair Division of AIRXCEL Inc P O Box 400 Cordele...

Страница 2: ...point out helpful suggestions that will result in improved installation reliability or operation DANGER Self contained units or evaporators of split systems should never be installed in engine rooms...

Страница 3: ...ESSURE FAULT shutdown Supply Air Grille s Some installations will have more than one supply air grille Standard main supply air grilles are generally made of aluminum or wood frames with two or four w...

Страница 4: ...me cases In such severe conditions seek the advice of your local factory service representative They will be most familiar with solutions to localized situations Marvair works closely with our servici...

Страница 5: ...of your air conditioner Electrical The SMM model is designed to operate of a nominal 12 volt DC power supply an inverter is not required The unit will operate on a DC voltage from 9 volts to 17 volts...

Страница 6: ...as a dedicated breaker turn it on Verify that water is being discharged overboard Instructions for the Thermostat Cooling Cycle 1 Adjust the cooling temperature set point on the thermostat higher than...

Страница 7: ...ct water line at ball valve 3 Insert line into a bucket of potable anti freeze 4 Run air conditioner until a solid stream of anti freeze is being discharged overboard 5 Reconnect water line at ball va...

Страница 8: ...ndoor coil The sensor and or thermostat should be replaced if defective 3 Check for water flow Check refrigerant charge Check switches for loose wire connection broken or burned contacts 4 Tug on wire...

Страница 9: ...tional unit s if necessary 7 Add refrigerant Noise operation 1 Copper tubing is vibrating 2 Indoor blower assembly 3 Loose cabinet or components 4 Improper unit installation 1 Adjust by bending slight...

Страница 10: ...SMM Air Conditioner 12 VDC Owner s Manual 5 09 Page 10 of 13 Chapter 7 Wiring Diagram...

Страница 11: ...10343 Controller Compressor 50425 Evaporator Coil 60158 Blower Assembly 30067 Blower relay RELAY BOARD 50196 Condenser water coil 60159 High Pressure Switch Manual Reset 400 psig 70383 Filter Drier Re...

Страница 12: ...heir designated Service Representative The responsibility of the Owner of the Equipment includes the following 1 To operate the equipment according to the manufacturer s instructions 2 To provide easy...

Страница 13: ...HIS WARRANTY AND SERVICE POLICY CONSTITUTE THE EXCLUSIVE REMEDY OF ANY PURCHASER OF A MARVAIR REVERSE CYCLE AIR CONDITIONER AND IS IN LIEU OF ALL OTHER WARRANTIES EXPRESSED OR IMPLIED INCLUDING WITHOU...

Отзывы: