Operating procedure for PI
Set rotary switch to 250/500/1000V. Clear the memory before
making a 

PI

measurement. Press the 

PI

key to enable

measurement, PI is shown on the display. After the 

TEST

button

is pressed and latched, HVDC (High Voltage DC) is applied for a
10 minute period. 10 seconds after the voltage is applied, the
tester starts to measure and record data - every 10 seconds for
the first minute, and every minute thereafter. (6 measurements are
taken in the first minute and 9 in the remainder.) 

PI

= (Last Value) /

(6th Value), stored in number 

00

of PI Memory.

DAR

(Dielectric Absorption Ratio) Key

Definition of DAR
DAR is the ratio of the insulation resistance measured after 30
seconds and 60 seconds. This is a faster version of the PI
measurement, which is useful when time is short. For good
insulation, the insulation resistance increases with time as the
capacitive leakage current and absorption current decrease. The
higher the DAR value, the better the insulation property. The
quality of the insulation is excellent for a DAR greater than 4.0,
good for 3.0 - 4.0, fair for 2.0 - 2.9, suspect for 1.5 - 1.9, poor for
1.0 - 1.4, and dangerous for less than 1.0.

Operating Procedure for DAR
Set rotary switch to 250/500/1000V. Clear memory before making

DAR 

measurement. Press the 

DAR

key to enable a

measurement, 

DAR

is shown on the display. After the 

TEST

button is pressed and latched, HVDC is applied for 60 seconds,
with measurements and data taken 10 seconds after the voltage is
applied, and then every 10 seconds. (A total of 6 measurements
with data are taken.) 

DAR

= (Last Value) / (3rd Value), stored in

location 

00

of DAR memory.

LIMITS

key

Press this key to enable or disable the "out of limits" alarm. This
function causes an alarm to sound if the measured value is not
within preset limits. High and Low limits can be set on each range
using the set up key.

SETUP

Function

Press 

SHIFT

and then 

SETUP

to set the auto power off time, the

upper and lower limits.

Setting Auto Power Off Time

Press 

SHIFT

then 

SETUP

, the display shows 

0005

(indicating 5

mintues. If the APO time has been changed previously another
number may be displayed), with the right hand digit blinking and

APO

blinking in the upper right corner of the display. Use 

and

to select the digit to be changed, and increase or

decrease the number with 

and 

.

After adjusting the value, press 

YES

to set the APO time, or

CANCEL

to discard the changes, and proceed to set the upper

limit.

Setting Upper Limit

After exiting the APO set up, the Upper Limit set up is
automatically entered. The display shows 

9999

, (if the upper limit

has been changed previously another number may be displayed)
with the right hand digit blinking.

LIMIT

and an upward triangle 

also blink in the middle-right, and lower-left, respectively on the
display. Use 

and 

to select the digit to be changed, and

increase or decrease the value with 

and 

. After adjusting the

value, press 

YES

to set the Upper Limit or 

CANCEL

to discard the

changes, and proceed to set the lower limit.

9

12

Содержание IN2103

Страница 1: ...s Thermometers Probes Test Leads Voltage Indicators Specialist Metrohm Testers 4 5kV Specialist Drummond Testers Check out what else you can get from Martindale Martindale Electric Company Limited Metrohm House Penfold Trading Estate Imperial Way Watford WD24 4YY UK Tel 44 0 1923 441717 Fax 44 0 1923 446900 E mail sales martindale electric co uk Website www martindale electric co uk Martindale Ele...

Страница 2: ...e purposes for which it has been constructed Particular attention should be paid to the Warnings Precautions and Technical Specifications Always check the unit is in good working order before use and that there are no signs of damage to it Do not use if damaged Where applicable other safety measures such as use of protective gloves goggles etc should be employed Please keep these instructions for ...

Страница 3: ...nd support martindale electric co uk CONTENTS 1 Introduction 2 1 1 Inspection 2 1 2 Description 2 2 Product Specific Safety Information 4 3 Operation 5 3 1 Installing or Replacing Batteries 5 3 2 Replacing Fuses 6 3 3 How it Works 6 4 Maintenance 13 4 1 Calibration 13 4 2 Cleaning 13 4 3 Repair Service 14 4 4 Storage Conditions 15 5 Warranty 15 Specifications For user notes 1 ...

Страница 4: ...rm testing in accordance with international standards including BS7671 Insulation testing can be undertaken at 250 500 1000V DC The tester is powered by six 1 5V alkaline batteries type LR6 To install or replace batteries refer to section 3 1 WARNING READ SAFETY INFORMATION BEFORE USING THIS METER 2 test Auto Discharge when TEST button released Buzzer 30Ω Buzzer disable option yes kΩ test Auto Dis...

Страница 5: ...0 300 400 500 600 700 800 900 x1000 0 0 5 1 2 3 4 5 6 7 10 15 20 30 50 100 APO mGΩ KMΩ V V z PI Polarization Index DAR Dielectric Absorption Ratio Auto Power Off user selectable default 5 mins APO Auto Power Off disable option 99 result Memory Safety Complies with BS EN 61010 and BS EN 61557 Overvoltage Category CAT III 600V Pollution Degree 2 Altitude Up to 2000M Protection IP44 Not for use in we...

Страница 6: ... a short period after releasing the TEST button The TEST button if latched must be released This discharges any capacitance via the tester Before disconnecting the tester ensure indicated voltage is zero Warning Before use check the unit for cracks or any other damage Make sure the unit is free from dust grease and moisture Also check any associated leads and accessories for damage Do not use if d...

Страница 7: ...d release the TEST button Remove the battery cover using a Phillips screwdriver and carefully remove the failed fuse from the metal clips fit the correct replacement and re fit cover DO NOT OPERATE THE TESTER WITH THE BATTERY COVER REMOVED WARNING When the meter shows the sign the batteries must be replaced to maintain correct operation Follow the procedure over 5 16 Since some jurisdictions do no...

Страница 8: ...y conditions away from direct sources of heat or sunlight and in such a manner as to preserve the working life of the unit It is strongly advised that the unit is not kept in a tool box where other tools may damage it 5 WARRANTY AND LIMITATION OF LIABILITY This Martindale product is warranted to be free from defects in material and workmanship under normal use and service The warranty period is 2 ...

Страница 9: ... be applied 250V 500V or 1000V DC Insert red test lead in VΩ and black lead in COM Connect the black and red test leads to the circuit to be measured Note If a voltage higher than 30V is present on the circuit under test the buzzer sounds and the high voltage indicator blinks in the upper right corner of the display In this event remove the test leads from the circuit under test and proceed with c...

Страница 10: ... polarization index is the ratio of the insulation resistance measured after one minute and ten minutes For good insulation the insulation resistance increases with time as the capacitive leakage current and absorption current decrease The higher the PI value the better the insulation The quality of the insulation is excellent for a PI that is greater than 4 0 good for 3 0 4 0 fair for 2 0 2 9 sus...

Страница 11: ...d for 60 seconds with measurements and data taken 10 seconds after the voltage is applied and then every 10 seconds A total of 6 measurements with data are taken DAR Last Value 3rd Value stored in location 00 of DAR memory LIMITS key Press this key to enable or disable the out of limits alarm This function causes an alarm to sound if the measured value is not within preset limits High and Low limi...

Страница 12: ...o scroll through the test data The PI memory locations are 00 to 15 in the PI MEM view location 00 is the PI value The other 15 are records of individual tests taken as part of the PI measurement set The DAR memory locations are 00 to 06 in the DAR MEM view location 00 is the DAR value The other 6 are records of individual tests taken as part of the DAR measurement set MEM CLR Function To clear th...

Отзывы: