Expelling the air in the pipes and the indoor unit

Pay attention to exact timings - use a digital watch for more exact timing.

You must expel the air from the system:
moisture or damp air in the pipework will cause
‘sludging’ problems with the compressor by
reducing efficiency and life expectancy of the
system.

Follow the steps below precisely to avoid system
failure.

a) Take off the valve covers from the stop valve
    and T-branch valve.
b) Take off the auxiliary cover from the T-branch
    valve.
c) Turn the stop valve (on small pipe using
    a hexagon wrench (Allen key), anti
    clock-wise to an angle of 90 degrees
   (Quarter of a turn) keep open for 4-5 
   seconds and then CLOSE the valve fully.
d) Check whether there is any refrigerant
    leakage from the pipe connections.
e) Next, push the ‘tyre inflator’ style valve on the
    T-branch (Larger pipe side) for 3-4 seconds 
    using a screwdriver or similar, to expel any left over air. CAUTION: Gas 
    might be cold. If you notice a slight oily residue on the tip of the screwdriver
    this is normal, do not worry and do not push in for more than 5 seconds even if no oil is present.
f) VERY IMPORTANT - Finally open the stop and T-branch valves with a Hexagon Key (Allen Key)
    fully anti clock-wise to allow the gas/ refrigerant to freely circulate around the system. They
    might be stiff, so be sure to open them fully and carefully. Then replace the 3 valve covers
    tightly.

Refrigerant must be added if the pipe measures more than 6 metres in length. This can only be
added by a professional airconditioning engineer.

30g per metre > 6m

15g per metre > 6m

Please call for larger pipe sizes.

Содержание airconditioningcentre KFR-23IW/AG

Страница 1: ...R32 Model No s KFR 23IW AG KFR 26IW AG KFR 33IW AG KFR 36IW AG KFR 53IW AG KFR 56IW AG KFR 63IW AG KFR 66IW AG ...

Страница 2: ... a qualified Air Conditioning Installer please give this guide to your installer This equipment should be installed correctly by professionally qualified technicians according to the manufacturer s specifications and requirements Please read the entire instructions before commencing so the full process is understoodbefore beginning Failure to install correctly as set out in these instructions may ren...

Страница 3: ...ectric shocks or fire Be sure to use only the specified accessories and parts for installation work Failure to use the specified parts may result in theunit falling water leakage electric shocks or fire Install the air conditioner on a foundation strong enough to withstand the weight of the unit A foundation of insufficient strength may result in the equipment falling and causing injury Electrical...

Страница 4: ...d a hazard After completing installation check for refrigerant gas leakage Toxic gas may be produced if the refrigerant gas leaks into the room and comes into contact with a source of fire such as a fan heater stove or cooker CAUTION Do not install the air conditioner at any place where there is a danger of flammable gas leakage In the event of a gas leakage build up of gas nearthe air conditioner...

Страница 5: ...3 5 ...

Страница 6: ...4 ...

Страница 7: ...5 ...

Страница 8: ...6 ...

Страница 9: ...ernal bending springs as you will damage the pipe internally by chafing the copper The copper pipes take a little patience and care to bend suitable curves without crushing or kinking There are 2 pipes one is smaller than the other The smaller is fairly soft and will bend reasonably easily to a gentle curve be careful not to kink the pipe All larger pipes require a bit more patience First of all cu...

Страница 10: ...hether there is any refrigerant leakage from the pipe connections e Next push the tyre inflator style valve on the T branch Larger pipe side for 3 4 seconds using a screwdriver or similar to expel any left over air CAUTION Gas might be cold If you notice a slight oily residue on the tip of the screwdriver this is normal do not worry and do not push in for more than 5 seconds even if no oil is prese...

Страница 11: ...s If the supply cord is damaged it must be replaced by the manufacturer or its service agent or simply qualified personnel only to avoid a hazard The plug should be accessible after installing the appliance or trunking W supplied Fill in the gap in the wall left by the pipe to prevent rain water and moisture from entering Pour water into the drip tray and follow this through the drain or an oily su...

Страница 12: ...m water with washing up liquid only dry naturally Check the outdoor unit and ensure no plants or leaves sticks etc can obstruct the fan operating and that air can flow freely through the rear cooling fins Wash the fins gently with a hosepipe to remove grit and dust that can collect on the fins Isolate from power supply first and allow to dry before reconnecting Your system should be serviced and refrig...

Страница 13: ...ll fixings often service or replace as required to prevent bracket failure and injury or death Air Conditioning Centre cannot accept any liability for damage to property or persons caused by insufficient servicing or checking fastness and safety of all components l Install the outdoor unit where it will not disturb your neighbo u rs You may require planning permission in some areas if in doubt alway...

Страница 14: ...ave a fault These are what the engineers use to identify and resolve your fault Indoor Unit Error Codes Meaning of fault Error code shown on display F1 F2 F3 F4 F5 F6 F7 F7 F8 F9 FA FC FD FH Note If your error code is not displayed here do not worry give us a call and we can help resolve the issue See back of guide ...

Страница 15: ...13 Circuit Diagrams ...

Страница 16: ...14 Circuit Diagrams ...

Страница 17: ... Centre New Milton Hampshire BH25 6RH If you have any problems or you are unsure of anything please give us a call before installing For service or installation please call 03703 344 345 Or alternatively email us support airconditioningcentre com ...

Отзывы: