14
55908039-06
USING SUCTION AND EXPANSION LINES
The expansion assembly must be removed from the indoor unit and connected to the outdoor unit allowing a
pipe run of up to 80m, including a maximum lift of 20m.
Fully insulate both the suction and expansion lines, including the expansion device: ensure the pipes are
insulated well over the drain tray at the indoor unit.
MODEL
MAXIMUM LENGTH OF EQUIVALENT
SUCTION LINE PIPE (m)
SUCTION LINE PIPE SIZES
EXPANSION LINES
PIPE SIZES
UNIT SIZE
TYPE
⅜
½
⅝
¾
⅞
1⅛
1⅜
⅜
½
⅝
¾
50
Common
7.5
18
50
80
7.5
50
80
Twin
7.5
23
80
80
80
Common
11
30
80
50
80
Twin
15
50
80
50
80
90
Common
10
25
55
80
20
80
Twin
10
36
80
7.5
80
100
Common
7.5
22
45
80
15
80
Twin
7.5
18
50
80
7.5
50
80
Triple
15
50
80
50
80
130
Common
15
30
80
12
60
80
Twin
7.5
18
50
80
7.5
50
80
Triple
10
36
80
7.5
80
150
Common
12
27
80
8
50
80
Twin
14
36
80
7.5
50
80
Triple
10
36
80
7.5
80
165
Common
8
18
60
80
7.5
40
80
Triple
7.5
18
50
80
7.5
50
80
180
Common
7.5
16
55
80
7.5
35
80
Triple
7.5
18
50
80
7.5
50
80