RECEIVING AND INSPECTION
Upon receiving the product, check to make sure all
items are accounted for by referencing the Bill of Lading
to ensure all items were received. Inspect each carton
for shipping damage before accepting delivery. Notify
the freight carrier if any damage is noticed. The carrier
will
make
notification
on
the
delivery
receipt
acknowledging any damage to the product. All damage
should be noted on all copies of the Bill of Lading which
is countersigned by the delivering carrier. A Carrier
Inspection Report should be filled out by the carrier
upon arrival and a report given to the Traffic
Department. If damaged upon arrival, file a claim
immediately with the carrier. Any physical damage to
the unit after acceptance is not the responsibility of
Mars Air Systems.
UNPACKING
Verify that all parts, components and accessories, and
the correct quantities of each have been received. If
any items are missing, report shortages to Mars Air
Systems directly to arrange for obtaining the missing
items. Again, verify quantities received against those
on the Bill of Lading only, as multiple shipments may be
involved.
INSTALLATION
Typical Mounting
– Wall or Ceiling Mounted
Horizontally Above the Door Opening
1. Gently remove all packaging materials, hardware and
all other accessories from interior of unit prior to
operating. Severe unit damage will occur if these items
are not removed prior to operation.
2. The intake screen can be opened by removing the two
screws on the bottom of the unit. The screen can be
removed from the unit by pulling the spring loaded
piano hinges. (FIG. 1)
3. All Phantom series have the Motor Fan Assembly
(MFA) shipped internally mounted.
4. All units are equipped with (4)
3/8’’ threaded inserts on
top for overhead installation (FIG. 2)
5. Determine the exact mounting locations to suspend
the unit above the ceiling so that the unit is centered
and parallel with the door opening. Use (4) threaded
rods to suspend the enclosure to the ceiling.
Note:
When installed in the ceiling above the door, the
air curtain must be moved 3/8” away from the wall for
every 1" above the door height.
6. If applicable, extended wall mounting brackets are
available for attaching the unit to a wall.
7. If applicable, for tandem installation (units longer than
72”) of products mounted side by side, allow no more
than 6” between the two units. Note that (4) sets of
threaded rods are used to suspend each unit to the
ceiling or center mounting brackets are to be used for
joining and top mounting tandem units.
8. Mount the product such that the discharge is flush with
the ceiling.
9. All wires must be connected internal of the unit and
some knockouts are provided. However, it may be
necessary to create your own knockout, as required.
10. The unit must be wired per NEC and local codes.
Electrical Field Wiring
1. For electric models, reference the
Heated Products
Supplement
.
2. The unit and any optional accessories must be wired
with the proper voltage to the junction box per the
wiring diagram. (FIG. 3, unheated products only)
WARNING
Precaution should be taken in explosive atmospheres.
WARNING
When servicing the product, motor may be hot enough
to cause pain or injury. Allow motor to cool before
servicing.