ICE-‐40
INSTALLATION MANUAL
Page 15
9.1.1.2
ID parameter
ID parameter determines time period of the pulse length to trigger the alarm. The pulse time can be
from 0,5 seconds to 9999 seconds. The default time is 0,5 seconds when the parameter value is 0.
9.1.1.3
DD parameter
This parameter is used to define the delay between the time that alarm input is trigged and the time
that alarm is reported.
9.1.1.4
Table of parameters
Name
Comment
IN1
Mode of operation for input 1
IN2
Mode of operation for input 2
ID1
Input time integration delay on input 1
ID2
Input time integration delay on input 2
DD1
Time delay for alarm reporting on input 1
DD2
Time delay for alarm reporting on input 2
Table 1: IN, ID and DD parameters
Example:
♦
Direct programming on the SIM card
ICE-40 PROGRAMMING TABLE
SIM CARD PHONE BOOK
Name
Number
Description
IN1
0
Alarm activated by connecting to GND
IN2
4
Alarm activated by connecting to GND + RST SMS
ID1
10
Input 1 has to be valid for 10 second to trigger the alarm
ID2
0
Input 2 has to be valid for 0,5 second to trigger the alarm
DD1
0
Reporting of the alarm on input 1 is delayed by 0s
DD2
15
Reporting of the alarm on input 1 is delayed by 15s
Table 2: IN, ID, DD parameters example
♦
Remote programming by SMS
;IN1=0;IN2=4;ID1=10;ID2=0;DD1=0;DD2=15;
9.1.2
REMOTE REPORTING ALARM EVENTS
Parameters used to define the way to report the alarm event.
Содержание Ice-40