background image

ADJUSTING AIR FLOW DIRECTION

You can adjust the direction of air flow by:

A. Turning the unit. If the unit has been installed

with a single lag bolt, as shown in Figure 6,

simply turn the entire unit as needed to adjust

air flow.

B. Tilting the unit. Loosen the bracket screws, tilt

the heater to the desired position, and re-tighten

the bracket screws (see Figure 4).

NOTE: To tilt the heater it must be mounted in

bottom keyhole slots of mounting bracket to

maintain adequate clearance and prevent possible

overheating.

C. Adjusting the louvers to the desired position.

NOTE: The louvers are designed so they can not be

completely closed. Do not attempt to defeat this feature,

damage to the unit can result.

ADJUSTING HEAT OUTPUT

Heat output can be increased or decreased by switching wires at

the wattage change terminal board. The heater is factory wired to

deliver the maximum heat output for the model used. Should your

particular application require less heat output, refer to Table 1

and change the wires at the wattage change terminal board as

shown in Wiring Diagram Fig. 7.

MAINTENANCE

Because of its rugged design, superior engineering, and high-

quality craftsmanship, the UH heater requires little maintenance.

With proper care, your electric heater should last a lifetime, but

seasonal cleaning is recommended to maintain the efficiency of

the heater.

Cleaning the Heating Element

To clean the heating element, loosen (but do not remove) the four

Phillips head screws located behind the louvers in the corners of

the louver housing (See Fig. 8, page 5).

TO PREVENT POSSIBLE ELECTRIC SHOCK, DIS-

CONNECT POWER TO THE HEATER AT THE MAIN

SERVICE BOX BEFORE ATTEMPTING TO ADJUST

THE HEAT OUTPUT OF THIS UNIT.

Fig. 6

USE CARE TO PREVENT DAMAGE TO INTERNAL

HEATER WIRING WHEN CLEANING ELEMENT. MAKE

SURE ALL CONNECTIONS REMAIN TIGHT AND ALL

WIRING IS ROUTED AWAY FROM ELEMENT FINS

WHEN REASSEMBLING THE UNIT. ALLOWING

WIRING TO TOUCH THE ELEMENT FINS COULD

RESULT IN A FIRE HAZARD.

4

!

!

WARNING

WARNING

TABLE 1. HEAT OUTPUT ADJUSTMENTS

BTU/HR VOLTS

WATTS

MAX

FUSE

SIZE

HEATER

AMPS

MOVE JUMPERS

FROM C-D TO A-B

25,598

240

7500

45

31.3

NONE

21,331

240

6250

35

26.1

BLUE

17,065

240

5000

30

20.9

BLUE & YELLOW

12,799

240

3750

20

15.7

BLUE, YELLOW & RED

19,198

208

5625

40

27.1

NONE

15,990

208

4685

30

22.3

BLUE

12,799

208

3750

25

18.1

BLUE & YELLOW

9,598

208

2812

20

13.6

BLUE, YELLOW & RED

GND

4

6

5

2

3

1

MOTOR

FAN

2

1

11

12

9

10

8

7

L1

L2

D

C

B

A

ELEMENT

FAN

CONTROL

HI LIMIT

FIELD WIRING

POWER

TERMINAL

BLOCK

THERMOSTAT

WATTAGE CHANGE

TERMINAL BOARD

RED

YEL

BLU

BLK

T

3

T

2

T

1

CONTACTOR

L

3

2

L

2

1

L

1

Fig. 7

UH724ST Wiring Diagram

Содержание UH Series

Страница 1: ...sed the mounting bracket 6 All electrical power must be disconnected at the main service box before installing inspecting cleaning or servicing the heater This is a precaution to prevent serious electrical shock Installation Maintenance Instructions SAVE THESE INSTRUCTIONS UH Series Electric Space Heater WARNING FILE E21609 Heater is shipped from factory wired for these wattages Heater can be fiel...

Страница 2: ... for proper supply wire selection Proper size fuses and circuit breakers in accor dance with the National Electrical Code Also see Table 1 page 4 Note For certain applications conduit may be required see Fig 1 Check local electrical codes Also if you run the wiring in conduit and wish to be able to turn the heater be sure to pur chase enough flexible conduit to allow the heater to be turned INSTAL...

Страница 3: ...red comfort level rotate thermostat knob counter clockwise until the thermostat clicks off Note that the fan delay will keep the fan running until the elements cool Heater will cycle on and off to maintain room temperature NOTE THE FIRST TIME YOU OPERATE THE UNIT IT MAY SMOKE SLIGHTLY THIS IS DUE TO THE RESIDUAL CLEAN ING AGENTS USED TO CLEAN THE ELEMENT WHEN THE HEATER IS MANUFACTURED THIS IS NOR...

Страница 4: ...ntenance With proper care your electric heater should last a lifetime but seasonal cleaning is recommended to maintain the efficiency of the heater Cleaning the Heating Element To clean the heating element loosen but do not remove the four Phillips head screws located behind the louvers in the corners of the louver housing See Fig 8 page 5 TO PREVENT POSSIBLE ELECTRIC SHOCK DIS CONNECT POWER TO TH...

Страница 5: ...qlyElyoExzâzá ÉázâpnâtépErátww Fig 9 5 spl âtyrEpwpxpyâ Heating Element Bezel Assembly Louver Housing Fig 8 TABLE 2 REPLACEMENT PARTS FOR UH SERIES ELECTRIC HEATERS QUANTITY KEY NO DESCRIPTION PART NUMBER UH724 1 Element 302006810 1 2 Motor 3900 2008 000 1 3 Fan Control Assembly 410148000 1 4 High Temp Limit Control 410027000 1 5 Thermostat 5813 2050 000 1 6 Thermostat Knob 3301 2014 006 1 7 Motor...

Страница 6: ...Products THE ABOVE WARRANTIES ARE IN LIEU OF ALL OTHER WARRANTIES EXPRESSED OR IMPLIED AND ALL IMPLIED WARRANTIES OF MER CHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE WHICH EXCEED THE AFORESAID EXPRESSED WARRANTIES ARE HEREBY DISCLAIMED AND EXCLUDED FROM THIS AGREEMENT MARLEY ENGINEERED PRODUCTS SHALL NOT BE LIABLE FOR CONSEQUENTIAL DAMAGES ARISING WITH RESPECT TO THE PRODUCT WHETHER BASED UPO...

Отзывы: