Motor Load

1. The corrected horsepower should be close to but not exceed the contract 

horsepower specified (see page 2). Determine corrected horsepower 

with this equation:

Actual volts and amperage must be obtained with the fan running and the 

specified rate of water flowing over the tower after the motor and Geareducer 

have reached operating temperature (approximately 30 minutes of opera-

tion).

2. The blade pitch can be changed to obtain contract horsepower. A one 

degree pitch change will change the power about eight horsepower. If 

blades are repitched, follow pitching and fastener tightening instructions 

detailed in the  Fan Assembly section of this manual.

Measurements taken on motors operating with Variable Frequency 

Drive controls may read up to 15% high from errors in measuring the 

approximated sine wave. Instruments capable of measuring a squared 

off wave form accurately should be used for measuring power in this 

situation.

When checking and/or changing blade pitch or cycling fan in normal 

operation, do not exceed 30 sec/hour total motor starting time as mo-

tor may be overheated.

Service

When contacting your Marley sales representative for repair or replacement 

parts, please refer to the tower serial number.

Replacement blades can be installed without rebalancing. The fan series—

HP7i—and diameter are required when ordering replacement  parts.

If rebalancing is required, return the fan hub to Marley for factory rebal-

ance.  Obtain  a 

Customer  Return  Material

  tag  from  your  Marley  sales 

representative.

  VOLTS

=  Nameplate Volts

  AMPS

=  Nameplate Amperage

  HP

=  Nameplate Horsepower

  DENSITY

=  Design Air Density

  HP

=  Corrected Horsepower

  VOLTS

=  Actual Volts

  AMPS

=  Actual Amperage

  DENSITY

=  Actual Air Density

VOLTS

A

 

×

 AMPS

A

 

× 

DENSITY

D

VOLTS

N

 

×

 AMPS

N

 

× 

DENSITY

A

  

HP

 

=

× 

 HP

N