Marley H3 Скачать руководство пользователя страница 2

FAN SERIAL NO.

FAN BLADE CLAMP FASTENER TIGHTENING INSTRUCTIONS

GENEROUSLY COAT CLAMP BOLT THREADS AND NUT

BEARING SURFACE WITH MARLEY THREAD LUBRICANT 

SPX COOLING TECHNOLOGIES, INC.  OVERLAND PARK, KS.

71-81-2 PW

TIGHTEN  TO

FT LB TORQUE

55

96      H3     6 — XXXX

Order No.

FAN SERIAL NO.

FAN BLADE CLAMP FASTENER TIGHTENING INSTRUCTIONS

GENEROUSLY COAT CLAMP BOLT THREADS AND NUT

BEARING SURFACE WITH MARLEY THREAD LUBRICANT 

SPX COOLING TECHNOLOGIES, INC.  OVERLAND PARK, KS.

71-81-2 PW

TIGHTEN  TO

FT LB TORQUE

55

96      H3     6 — XXXX

IMPORTANT

     A.   Each fan is statically balanced at the factory as an assembly. The fan hub is identified with the complete serial number 

and each blade socket is identified by number. Each fan blade is marked with the identification portion of the fan serial 

number and a sequential number indicating position of the fan blade in the fan hub.

     B.   Check and, if necessary, retighten blade clamping hardware to prescribed torque prior to startup and subsequently at  

6 month intervals.

     C.   When writing the Marley sales office or representative for repair or replacement parts, please refer to the tower order 

number and fan serial number. ConTACT your MArlEy sAlEs rEprEsEnTATivE for AssisTAnCE on ordEr 

plACEMEnT. 

TYPICAL FAN NAMEPLATE

(noTE: refer to Table for prescribed Torque)

Marley order no.

fan diameter

order no.

final pitch Angle 

speed, rpm 

Contract hp

Marley 

/

 H3

 

Fan

 

/

 

        