background image

3

OPERATION INSTRUCTIONS

THERMOSTAT

Heaters include a bimetal thermostat for the automatic control
of the exiting air temperature. The thermostat knob controls the heating
elements and fan functions. The heater and fan are 
de-energized with the knob in the extreme clockwise position.
Turning the knob clockwise from the off position to the fan 
position will energize the fan only, for use in summer cooling.
The adjustment knob controls power to the heater and fan
when turned further in the clockwise direction, with the highest tempera-
ture setting in the extreme clockwise position.
The temperature setting in the heater mode is approximately
40°F in the low setting and 100°F at the highest setting.

Note:

The adjustment knob should be turned to the fan only 

setting after use for heating. The fan should be left on for at least 3 min-
utes to remove residual heat from the unit and to prevent overheating of
the housing.

Cord Preparation for Portable Heaters

1.

Determine the gage and number of conductors fromChart A using
amps and phase from the heater nameplate. It is not recommended
that cord exceed 50 feet in length.

2.

Strip off outer jacket of cord and insulation from lead wires. The tabu-
lation below provides the strip dimensions for the 
various Chromalox portable heaters. See the nameplate on the heater
for the Model number.

3.

Slide fitting onto cord and tighten knurled nut to secure fitting
to cord.

4.

Select plug to match electrical rating of cord.

5.

On opposite end of cord prepare end as directed by 
instructions that are provided with the plug.

6.

Attach cord assembly to heater as shown in Fig. 2 below:

Model No.

A

B

C

All Models

8”

1”

0.5”

Figure 2

Run wire tie through slots in bracket and over cord.
Pull tab of wire tie to provide cord strain relief.

Power
wires

Ground
wire

90° fitting

"A"

"B" (Insulation strip dimension for ground wire).

"C" (Insulation strip dimension for power wires).

T3
T2
T1

L3
L2
L1

2

1

3

Thermostat

Cord by others.
Type "SO" or equal
sized to meet nameplate
requirements

4

1

3

5

6

Front of
Heater

6

5

4

3

2

1

Red

Motor

Blu

Blk

Wht

Cutout

6

4

Diag. 1 – FACTORY WIRED 3 PHASE

T2
T1

L2
L1

2

Cord by others.
Type "SO" or equal
sized to meet nameplate
requirements

4

1

3

5

6

Front of
Heater

6

5

4

3

2

1

All control wiring

same as Diag. 1

Instructions:
    1. Loosen screws on load side of contactor. Remove all lead wire.
    2. Insert lead wires numbers 1, 3, and 5 into box lug connector "T1". Tighten screws
        on box lug connector.
    3. Insert lead wires numbers 2, 4, and 6 into box lug connector "T2". Tighten screws 
        on box lug connector.
    4. Examine wiring to make certain it is per above diagram.

Diag. 1a – FIELD CONVERSION TO 1 PHASE

All control wiring

same as Diag. 2

T2
T1

L2
L1

2

Cord by others.
Type "SO" or equal
sized to meet nameplate
requirements

4

1

3

5

6

Front of
Heater

6

5

4

3

2

1

All even numbered wires to T2

All odd numbered wires to T1

Contactor

Instructions:
    1. Loosen screws on load side of contactor. Remove all lead wire.
    2. Insert lead wires numbers 1, 3, and 5 into box lug connector "T1".
        Tighten screws on box lug connector.
    3. Insert lead wires numbers 2, 4, and 6 into box lug connector "T2".
        Tighten screws on box lug connector.
    4. Examine wiring to make certain it is per above diagram.

Diag. 2a – FIELD CONVERSION TO 1 PHASE

T3
T2
T1

L3
L2
L1

2

1

3

Thermostat

Cord by others.
Type "SO" or equal
sized to meet nameplate
requirements

4

1

3

5

6

Front of
Heater

6

5

4

3

2

1

Blk/Red or Grey

Motor

Blk

Wht

Cutout

6

4

Contactor

1

3

5

2

4

6

To T3

To T3

To T1

To T2

To T1

To T2

Fan Relay

A2

T2

T1

A1

L2

L1

XFMR

Blk

Black

White

Diag. 2 – FACTORY WIRED 3 PHASE

T3
T2
T1

L3
L2
L1

11

1

3

Thermostat

Cord by others.
Type "SO" or equal
sized to meet nameplate
requirements

9

10

7

8

12

Front of
Heater

10

9

4

3

2

1

Motor

Blue

Cutout

6

4

Contactor

1

3

5

2

4

6

To T3

To T3

To T1

To T2

To T1

To T2

Red

Black

White

6

5

12

11

8

7

Diag. 3 – FACTORY WIRED 3 PHASE

MAINTENANCE INSTRUCTIONS

Replace or repair damaged cords or plugs immediately. Check
tightness of all electrical connections prior to energizing the
heater. Blow out or vacuum away any dirt or debries that may
have accumulated around the control enclosure fan motor or
heating elements.

Electric Shock Hazard. Disconnect heater from power supply
before servicing and/or inspecting the heater; failure to do so
may result in electrical shock.

a

WARNING

!

Содержание DH1021C

Страница 1: ...nded 4 Always disconnect heater when not in use 5 Do not operate any heater with a damaged cord or plug or after the heater malfunctions has been dropped or damaged in any manner Return heater to authorized ser vice facility for examination electrical or mechanical adjustments or repair 6 Do not use outdoors 7 This heater is not intended for use in bathrooms laundry areas and similar indoor locati...

Страница 2: ...apes and other furnishings away from heater a WARNING Bolt Nut Support Leg Handle Direction of Airflow Figure 1 ELECTRIC SHOCK HAZARD Disconnect all power before installing or servicing heater Failure to do so could result in personal injury or property damage Heater must be effectively grounded in accordance with the National Electrical Code NFPA 70 v a WARNING 2 Fits Cable Dia Plug Type Model De...

Страница 3: ...d Motor Blu Blk Wht Cutout 6 4 Diag 1 FACTORY WIRED 3 PHASE T2 T1 L2 L1 2 Cord by others Type SO or equal sized to meet nameplate requirements 4 1 3 5 6 Front of Heater 6 5 4 3 2 1 All control wiring same as Diag 1 Instructions 1 Loosen screws on load side of contactor Remove all lead wire 2 Insert lead wires numbers 1 3 and 5 into box lug connector T1 Tighten screws on box lug connector 3 Insert ...

Страница 4: ...on may not apply to you This warranty gives you specific legal rights and you may also have other rights which vary from state to state For the address of your nearest authorized service center contact Marley Engineered Products in Bennettsville SC at 1 800 642 4328 Merchandise returned to the fac tory must be accompanied by a return authorization and service identification tag both available from...

Отзывы: