2. Connecting the Solar
Hard wire the Solar in accordance with the selected wiring options
on the pages overleaf.
Terminals allow the connection of up to 4mm² solid copper conductor or
multi-strand cable.
Ensure terminals are fully tightened and cable is clamped using the cable
clamps provided. Where necessary, invert the plastic cable clamp to provide
the correct grip
.
Replace the terminal cover, do not switch on power at this stage (go to
section 3)
The Solar installation must be protected against overcurrent by connecting it via a
16A MCB or 13A fused outlet.
Remove the terminal cover, terminals are arranged as follows:
FAN UNIT
SUPPLY
HTR 1
HTR 2
220-240V 50Hz Max 3kW
!
+
_
+
_
L
N
cut-outs for
rear cable
entry
Terminal Description:
SUPPLY
L
220-240V Live Input—must be protected by 16A MCB or 13A fused outlet
N
Neutral
Earth (all earth terminals common)
HTR 1 Terminals (Connect to Immersion Heater at Top of Tank)
+
Connect to the Live terminal of the immersion heater, max 13A
-
Connect to the Neutral terminal of the immersion heater
Earth
HTR 2 Terminals (Connect to Lower Immersion Heater, if fitted)
+
Connect to the Live terminal of the immersion heater, max 13A
-
Connect to the Neutral terminal of the immersion heater
Earth