Mark GTC E Скачать руководство пользователя страница 15

EN

15

 

15 

11.5 Sensor Error 

No sensor connected (sensor must be ordered), or the 

sensor is malfunctioning it must be replaced. 
 
 
 
 

11.6 Motor Error 

There is a motor error in the door air curtain, please con-

tact the technical support. 
 
 

 
 
11.7 Heater Error

 

If there is an overheating in the door air curtain, the fan 

will turn on or if it is on then it will switch to the next high-

er level. The heating will automatically be switched off af-

ter achieving the last fan level, (1 heating level per 30 

seconds) until all the heat goes away. 

 
 

12. Help 

Error 

Display notifi-

cation  

Possible Cause 

Solution 

Device without function 

Screen is off 

No voltage 

Switch voltage on 

 

No enabled 

BMS –

 

enable missing 

See point 11.3 

 

Frostalarm 

Inlet temperature too is low  Increase inlet temperature 

No temperature control 

Sensor defect 

U-  
K- 

No sensor connected 

Cable break 

Short circuit 

See point 11.5 

Replace sensor 
Replace sensor 

Too low airflow 

Engine overheat 

Fan defective 

See point 11.6 

 

Runtime filter 

Suction filter dirty 

Filter cleaning (See point 

11.4) 

 

COM error 

Error in the data transfer 

See point 11.1 

 

15 

11.5 Sensor Error 

No sensor connected (sensor must be ordered), or the 

sensor is malfunctioning it must be replaced. 
 
 
 
 

11.6 Motor Error 

There is a motor error in the door air curtain, please con-

tact the technical support. 
 
 

 
 
11.7 Heater Error

 

If there is an overheating in the door air curtain, the fan 

will turn on or if it is on then it will switch to the next high-

er level. The heating will automatically be switched off af-

ter achieving the last fan level, (1 heating level per 30 

seconds) until all the heat goes away. 

 
 

12. Help 

Error 

Display notifi-

cation  

Possible Cause 

Solution 

Device without function 

Screen is off 

No voltage 

Switch voltage on 

 

No enabled 

BMS –

 

enable missing 

See point 11.3 

 

Frostalarm 

Inlet temperature too is low  Increase inlet temperature 

No temperature control 

Sensor defect 

U-  
K- 

No sensor connected 

Cable break 

Short circuit 

See point 11.5 

Replace sensor 
Replace sensor 

Too low airflow 

Engine overheat 

Fan defective 

See point 11.6 

 

Runtime filter 

Suction filter dirty 

Filter cleaning (See point 

11.4) 

 

COM error 

Error in the data transfer 

See point 11.1 

11.5  Sensor Error

No sensor connected (sensor must be ordered), 
or the sensor is malfunctioning and it must be 
replaced.

11.6  Motor Error

There is a motor error in the door air curtain, 
please contact the technical support.

11.7  Heater Error

If there is an overheating in the door air curtain, 
the fan will turn on or if it is on then it will 
switch to the next higher level. The heating will 
automatically be switched off after achieving the 
last fan level, (1 heating level per 30 seconds) 
until all the heat goes away.

Содержание GTC E

Страница 1: ...GTC E 0699204 0664120 User Manual Gebruikshandleiding EN NL...

Страница 2: ...Overtime setting 7 6 Automatic Blow Temp AT 8 6 1 Turning Blow Temp AT on 8 6 2 Setting the target temperature for Blow Temp AT 8 6 3 Blow out temp AT fan level Setting 9 7 Timer 9 8 Combination of AS...

Страница 3: ...l and fan level will be displayed in blue Levels which are in operation are displayed in black 3 1 Entrance to the home menu When the power supply is switched on appears the company logo for about 5 s...

Страница 4: ...the selected Frost Protect temperature Frost Protect has priority even if the system is in standby mode 3 Automatic Frost Protect AS With the Frost Protect it prevents the room from cooling When the t...

Страница 5: ...lue DT Fan Level Heat Level PTC Heating element MV 0 0 0 OFF ON 1 K 1 1 ON ON 2 K 2 1 ON ON 3 K 3 2 ON ON 4 K 4 3 ON ON 5 k 5 3 ON ON 4 Automatic RoomTemp RT With the RT Automatics the selection of th...

Страница 6: ...s which are in operation are displayed in black With pressing on Home you will get to the Home screen 5 Automatic Door Swith TK With the TK Automatics the system is switched on after preselection of t...

Страница 7: ...the Home screen Fan Level Heat Level PTC Heating element MV 1 5 1 ON ON 3 5 1 2 ON ON 4 5 1 2 3 ON ON 5 3 Door Switch TK Heat Level setting With pressing on Heat Level the display changes and you can...

Страница 8: ...red outlet temperature With pressing on Home you will get to the Home screen current state temperature value Target temperature value 6 Automatic Door Swith TK With the AT Automatics the regulation of...

Страница 9: ...ve With the arrow you can set another switching time With pressing on Home you will get to the Home screen 6 3 Blow out temp AT fan level Setting With pressing on Fan Level the display changes and you...

Страница 10: ...he display changes and you can select a desired language The following languages are available Nederlands Francais English Deutsch Italiano Polski Dansk 8 Combination of AS RT TK and AT automatic All...

Страница 11: ...essing on screen the display changes Then press on Rotate to Rotate the display in clockwise direction 9 1 Runtime Filter If a filter time is preselected a note appears after the time expires This sho...

Страница 12: ...splay Use the arrows to set the desired date and time Confirm with OK 9 5 Overtime See under point 5 4 9 3 3 Screen lock With pressing on Screen the display changes Then press on lock To unlock press...

Страница 13: ...nutes The screen saver will be activated screen is dimmed Activation takes place by pressing the logo 9 6 Factory Setting This setting will RESET the controller to the factory settings All data will b...

Страница 14: ...ner Reset message With pressing on Clean filter the display changes and then the message will disappear 11 Error messages 11 1 COM Error There is a communication error between the individual component...

Страница 15: ...ror in the door air curtain please con tact the technical support 11 7 Heater Error If there is an overheating in the door air curtain the fan will turn on or if it is on then it will switch to the ne...

Страница 16: ...datacable 20 m 1 1 straight wired RJ 45 Stecker S 50 K1 K1 K2 K3 S 80 S 60 q q q q K1 Connectingbox Mains switch and fuses to be installed by third parties must comply to all applicable rules and requ...

Страница 17: ...10 19 18 20 CPU 0 Adress Schalter 0 MASTER 1 9 SLAVE 5 1 2 3 4 9 8 7 6 L1 N PE AUX MON optional Mainsswitchandfuses tobeinstalledby third parties must comply toall applicablerulesand requirements the...

Страница 18: ...met uitschakelvertraging 23 6 Automatische uitblaastemperatuur AT 24 6 1 Uitblaastemperatuur AT inschakelen 24 6 2 Gewenste uitblaastemperatuur UT instellen 24 6 3 Ventilatiestanden AT instellen 25 7...

Страница 19: ...ventilatie om het systeem traploos te regelen alleen mogelijk bij gebruik van EC motoren Druk op Home om terug te keren naar het startscherm 2 2 Verwarmingsstand instellen Druk op Verwarmingsstand om...

Страница 20: ...eiliging om deze in te schakelen Op het scherm Automatisch wordt nu weergegeven dat de afkoelbeveiliging actief is AS Druk op Home om terug te keren naar het startscherm 3 2 Afkoelbeveiligingstemperat...

Страница 21: ...g PTC MV 0 0 0 OFF ON 1K 1 1 ON ON 2K 2 1 ON ON 3K 3 2 ON ON 4K 4 3 ON ON 5K 5 3 ON ON Op het scherm Automatisch wordt nu weerge geven dat de automatische ruimtetemperatuur actief is Druk op Home om t...

Страница 22: ...en het automatisch deurcontact in te schakelen Op het scherm Automatisch wordt nu weergegeven dat het deurcontact actief is Druk op Home om terug te keren naar het startscherm 5 2 Ventilatiestand van...

Страница 23: ...TK instellen met uitschakel vertraging Druk op het tandwiel pictogram Instellingen om de weergave te wijzigen en de uitschakelvertraging te wijzigen Daarmee stelt u in dat het systeem ook nadat de de...

Страница 24: ...akelen Druk op Automatisch om de weergave te wijzigen en de uitblaastemperatuur in te schakelen Op het scherm Automatisch wordt nu weergegeven dat de uitblaastemperatuur actief is Druk op Home om teru...

Страница 25: ...ltijden programmeren De actieve tijd wordt groen weergegeven de inactieve tijd wordt rood weergegeven Druk op Timer om de weergave te wijzigen en de schakeltijden in te schakelen Druk op Nieuw om de w...

Страница 26: ...rden gecombineerd wordt de uitblaastemperatuur geregeld volgens de geselecteerde ventilatiestand als de deur is geopend Aanwijzing 3 Indien RT ruimtetemperatuur en TK deurcontact worden gecombineerd h...

Страница 27: ...druk op Opslaan U kunt kiezen uit 0 tot 999 uur 9 3 Beeldscherm 9 3 1 Helderheid Druk op Scherm om de weergave te wijzigen Druk vervolgens op Helderheid De weergave verandert opnieuw Gebruik de pijle...

Страница 28: ...beeldscherm te blokkeren Om de blokkering op te heffen drukt u op het logo en vervolgens nog drie keer op het logo 9 4 Datum tijd Druk op Datum tijd om de weergave te wijzigen Gebruik de pijlen om de...

Страница 29: ...igen Druk op OK om te bevestigen 9 7 Geheugenfunctie De GTC is voorzien van een geheugenfunctie waardoor het systeem bij een stroomuitval weer met de eerder ingestelde waarden wordt herstart U kunt de...

Страница 30: ...E 1 9 COM fout E is voor overige busfouten U kunt een RESET doorvoeren door de voeding uit en vervolgens weer in te schakelen Let er daarbij op dat u SLAVE systemen eerst van stroom voorziet 11 2 Vors...

Страница 31: ...Druk op Filter reinigen om de weergave te wijzigen en het foutbericht te annuleren 11 5 Sensor defect Er is geen sensor aangesloten sensor moet worden besteld of de sensor is defect en moet worden ve...

Страница 32: ...Vorstbeveiliging Luchtaanvoertemperatuur te laag Luchtaanvoertempe ratuur verhogen Geen temperatuur regeling Sensor defect U K Geen sensor aangelosten Kabelbreuk Kortsluiting zie punt 11 5 Sensor ver...

Страница 33: ...datacable 20 m 1 1 straight wired RJ 45 Stecker S 50 K1 K1 K2 K3 S 80 S 60 q q q q K1 Connectingbox Mains switch and fuses to be installed by third parties must comply to all applicable rules and req...

Страница 34: ...19 18 20 CPU 0 Adress Schalter 0 MASTER 1 9 SLAVE 5 1 2 3 4 9 8 7 6 L1 N PE AUX MON optional Mainsswitchandfuses tobeinstalledby third parties must comply toall applicablerulesand requirements thermo...

Страница 35: ...NL 35...

Страница 36: ...rkbelgium be MARK DEUTSCHLAND GmbH MAX PLANCK STRASSE 16 46446 EMMERICH AM RHEIN DEUTSCHLAND TELEFON 49 0 2822 97728 0 TELEFAX 49 0 2822 97728 10 info mark de www mark de MARK POLSKA Sp z o o UL JASNO...

Отзывы: