The Ranco® ETC is a microproc-
essor-based electronic temperature 
control designed to handle the 
OFF/ON functions of the NOR-
DIC® EMDX unit. The ETC is 
equipped with an LCD display 
which provides a constant readout 
of the sensed temperature and a 
touch keypad that allows the user 
to easily and accurately select the 
setpoint temperatures and differen-
tials for the first and second stages 
of operation. 

Programming  Steps and Dis-
play 

Step 1– To start programming, press the 

SET

 key 

once to access the Fahrenheit/Celsius mode. The 
display will show the current status, either F for de-
grees Fahrenheit or C for degrees Celsius. Then 
press either the 

UP

 arrow or 

DOWN

 arrow key to 

toggle between the F° or C° des-
ignation. For closer regulation of 
your PC temperatures we recom-
mend you program in the Fahr-
enheit mode. 

STAGE 1 

Step 2– Press the 

SET

 key again 

to access the stage1 setpoint. 
The LCD will display the current 
setpoint and the S1 annunciator 
will be blinking on and off to in-
dicate that the control is in the 
setpoint mode. Then press either 
the 

UP

 arrow key to increase or 

the 

DOWN

 arrow key to de-

crease the setpoint to the desired 
temperature. 
Step 3– Press the 

SET

 key again 

to access the stage1 differential. The LCD will dis-
play the current differential and the 

Dif 1 

annuncia-

tor will be blinking on and off to indicate that the 
control is in the differential mode. Then press ei-
ther the 

UP

 arrow key to increase or the 

DOWN 

arrow key to decrease the differential to the desired 
setting. 
Step4– Press the 

SET

 key again to access the 

stage1 cooling or heating mode. 
The LCD will display the current 
mode, either 

C1

 for cooling or 

H1

 

for heating. Then press the 

UP

 or 

DOWN

 key to toggle between the 

C1

 or 

H1

 designation. 

(NOTE: For  purposes both 
stages of both  aquastat are set to 
the H1 or H2 designation. ) 

 

STAGE 2 

Step 5– Press the SET key again to 
access the stage 2 setpoint. The 
LCD will display the current set-
point and the 

S2 

annunciator will 

be blinking on and off to indicate the control is in 
the setpoint mode. Then press either the 

UP

 key to 

increase or the 

DOWN

 key to decrease the setpoint 

to the desired temperature.  
Step 6– Press the 

SET 

key again to access the 

stage2 differential . The LCD will display the cur-

rent differential and the 

DIF 2 

an-

nunciator will be blinking on and 
off to indicate that the control is in 
the differential mode. Then press 
either the 

UP

 arrow key to increase 

or the 

DOWN 

arrow key to de-

crease the differential to the desired 
setting. 
Step 7– Press the 

SET

 key again to 

access the stage 2 cooling or heat-
ing mode. The LCD will display 
the current mode, either 

C2

 for 

cooling or 

H2 

for heating. Then 

press either the up or down key to 
toggle between the 

C2

 and 

H2

 des-

ignation. Press the 

SET

 key once 

more and programming is com-
plete. 

NOTE: The ETC will automatically end program-
ming if no keys are depressed  for a period of  30 
seconds. Any settings that have been input to the 
control will be accepted at that point. 
All control settings are retained in non-volatile 
memory if power to ETC is interrupted for any rea-
son. Re-programming is  not necessary after power 
outages or disconnects unless different control set-

 

Ranco® ETC Thermostat Controls

 

ETC Location 

EMDX 
Electrical Box 

Содержание EM (DX) 45-55-65

Страница 1: ...e Shooting Guide 21 Conceptual Overview 5 Starting the Heat Pump 15 Performance Curves 24 Technology Explanation 7 Component Layout 17 Setting the Aquastat 27 Installing DX linesets 11 Dimensions Pipi...

Страница 2: ...pansion Heat Pump System Energy Input Solar Geothermal Storage System Earth s Mass Extraction Rejection System EM heat pump Heat Distribution Infloor Heating Fan Coil Distribution NORDIC DX Energy Mod...

Страница 3: ...pump Unless you are sure there will be sufficient moisture pre sent in the loop field area during the summer a soaker hose is recommended in all horizontal trench systems which will used for air condi...

Страница 4: ...Page 4 Maritime Geothermal Ltd 17 Feb 00 NORDIC EMDX Series Typical Plumbing Domestic HOT Water Tank HOT Water OUT to home DX copper lines to outdoor loops Check Valve...

Страница 5: ...ost of these components were outside the heat pump and had to be procured and in stalled by the plumber Energy Machines are superior to a built up system in the following ways 1 Installed first cost i...

Страница 6: ...heat pump to approx 1 m down the drop pipes in the vertical boreholes Install spacers to keep the pipes separated as far as possible from one another in the boreholes Install 30 to 35 m of dual tubin...

Страница 7: ...gerant re quired during the cooling operation but not needed during the heating mode 6 Inefficient and ineffective method to account for vastly varying condenser capability depending on ground tem per...

Страница 8: ...Page 8 Maritime Geothermal Ltd 17 Feb 00 Piping Layout of Vertical Style DXW Vertical Loop HOME...

Страница 9: ...ll distribute the weight of the NOR DIC unit evenly over the Styrofoam This process will also deaden the compressor noise emitted from the bottom of the cabinet As an alternative several pieces of 50...

Страница 10: ...Page 10 Maritime Geothermal Ltd 17 Feb 00 NORDIC EMDX Horizontal Trench Design...

Страница 11: ...un the pipe insulated up the outside wall making a 90 degree turn above ground and entering the dwelling between the floor joists just below the first floor These pipes should be insu lated with a min...

Страница 12: ...Page 12 Maritime Geothermal Ltd 17 Feb 00 Horizontal EMDX Loop Field Plan View...

Страница 13: ...ire system should be pressurized to 700 kPa with dry nitrogen and all joints made by the installer checked for leaks using soap suds or some other technique that the installer feels comfortable with I...

Страница 14: ...e a excavated area or an existing area which needs to be filled as part of general excavation Loops should be buried approxi mately 2 m underground for best performance Example Nordic DX 45 should hav...

Страница 15: ...lectrical panel 7 Have the following tools on hand and know how to use them A refrigeration gauge set An electronic or other accurate thermometer An amprobe 1 Connect your refrigeration gauge set 2 Tu...

Страница 16: ...ses straight through the valve to ports G where it exits to the vapor line header From the vapor line header the refrigerant gas enters the reversing valve at point H and exits to the common suction l...

Страница 17: ...in Hot Water In Expansion Tank Expansion Valves 40 Gal Stainless Distribution Tank Electric Heat Elements 3 x 3KW Ranco 2 stage Digital Aquastat EMDX Front Side Compressor Contactor Right Electric Hea...

Страница 18: ...Page 18 Maritime Geothermal Ltd 17 Feb 00 NORDIC Series EMDX 45 55 65 HW Engineering and Performance Data Feb 00...

Страница 19: ...Ltd 17 Feb 00 Maritime Geothermal Ltd Date Feb 1999 Revision 4 35 Color Caissie Grey EM Direct Expansion to Water Heat Pumps Models EMDX 45 65 Style Horizontal Drawn By G Kaye Title Piping Electrical...

Страница 20: ...p Electrical Service Requirements Second row lists requirements with 9KW internal back up heat installed Model EMDX 45 HW EMDX 55 HW EMDX 65 HW Voltage 230 1 208 3 230 1 208 3 230 1 208 3 Min Circuit...

Страница 21: ...eter shows no resistance be tween common and run terminals or between common and start terminals Note Be sure compressor overload has had a chance to reset If comp is hot this may take several hours D...

Страница 22: ...erant level Refrigeration gauges show suction pressure dipping below 138 kPa Check refrigerant level Add refrig erant slowly Check for possible leaks Normal charge is 1 8 kg per ton Faulty low pressur...

Страница 23: ...age or restriction in the water line or hot water heat exchanger Check water flow and power to pump Check water lines for obstruc tion Remove obstruction in water lines Acid treat the domestic hot wat...

Страница 24: ...3296 3697 3 9 62 250 45 32607 100 107 6 10 45594 17 3 3178 3584 3 7 57 240 41 30635 100 107 3 10 43956 17 4 3129 3543 3 6 54 234 35 26674 100 106 3 10 38008 16 6 2963 3378 3 3 45 219 30 22677 100 106...

Страница 25: ...108 9 10 53868 18 8 3943 3 4 356 4288 3 7 60 250 45 38208 100 108 3 10 49602 18 4 3764 3 4 329 4083 3 6 54 240 40 35795 100 107 8 10 46611 17 6 3594 3 5 338 3923 3 5 50 230 35 31942 100 107 1 10 4239...

Страница 26: ...9 27 8 5721 4 2 413 6134 3 37 62 8 245 50 46511 100 111 2 10 67164 26 7 5428 4 1 414 5842 3 37 57 2 234 45 42117 100 110 4 10 62200 25 4 5173 4 1 415 5588 3 26 52 4 224 40 38521 100 109 7 10 58167 24...

Страница 27: ...setting Step4 Press the SET key again to access the stage1 cooling or heating mode The LCD will display the current mode either C1 for cooling or H1 for heating Then press the UP or DOWN key to toggle...

Страница 28: ...1 relay 24v Power Connection Stage 1 NC NO C Stage 2 NC C NO Cover screws 4 Mounting Holes Shown Below NOTE The temperature sensor can be extended up to 400 ft by cutting the sen sor extension cable...

Страница 29: ...Page 29 Maritime Geothermal Ltd 17 Feb 00 NORDIC EMDX 45 55 65 HW Series Schematic 208v 3ph 60Hz Greyed Circled Items Optional...

Страница 30: ...208v 3 60 Box Heating Domestic Hot Water Versions NOTE A Electric Heat Back up is An option which can be activated or deactivated by the customer by discon necting the breaker as re quired To disconne...

Страница 31: ...a Sheet have it endorsed by the owner and return it to Maritime Geothermal Ltd within 21 days after the in stallation of the unit 3 It is the responsibility of the building or general contractor to su...

Страница 32: ...Environmentally sound solutions to today s Heating and Cooling needs NORDIC NORDIC Maritime Geothermal Ltd has the solution for all your heating and cooling projects Vertical Liquid to Air Liquid to L...

Отзывы: