
2.0 Configuration and Modbus map
User’s Manual GW-DLMS-232-ISK
Page 7
From this page, through the links at the top of the page, you can browse web pages that contain the
data for the single Meter or go on the configuration pages of the Gateway (
Home PLC
).
2.2 Communication with energy meter
In order to activate communication with energy meter user must insert in proper field
Serial coder
Meter x
the serial numbers of connected meters.
It’s possible to change baudrate of the port connected to meter from
Serial port baudrate selection
in case meter works with speed different from 9600 that usually is standard.
Time between readouts
can be set from 10 to 3600 seconds.
String debug
is useful to understand the communication with meters.
With
GATEWAY REBOOT
button you can force the gateway to reboot.
The confirmation of the changes is recorded using the
Submit
button.
2.3 Gateway Settings
To change the gateway settings, such as IP address, you need access to the configuration pages
through the link
HomePLC
in the header of web pages that contain the data read from the counters.
The
Home
page summarizes the main information concerning the gateway as the serial and with the
navigation bar on the left you can move between the pages.
Credentials to login and modify parameters are: Username =
Admin
, Password =
Admin
.
Changes in gateway settings
are applied to the gateway after a power reboot.