7. Starting the UPS

1.

Verify that the AC Input & Output and the Battery Circuit

Breaker on the UPS are Off.

2.

Place the Manual Bypass Switch in the UPS position.

3.

Turn ON the upstream Utility Input Circuit Breaker.

4.

Verify the load has power.

5.

Turn ON the AC Input & Output Circuit Breaker.

6.

Turn ON the Battery Circuit Breaker.

7.

LCD display shows STANDBY.

8.

In 30 seconds, The LCD display changes to "ON LINE",

9. T

he Green Output LED 

should be l

it indicating 

the 

Input

power 

is 

within 

an 

acceptable 

frequency

 and voltage

range and the

 

output is powered from Utility.

8. LCD Home Screen Operation

9. Emergency Shut Down

1. Turn OFF the battery circuit breaker.

2. Unplug the AC INPUT cord and turn off the Utility Line power circuit breaker.

3. Turn OFF the AC input & output circuit breaker.

FOR SUPPORT QUESTIONS CONTACT 310-689-2328 x 103

BATTERY CIRCUIT 

BREAKER

 

AC INPUT & OUTPUT 

Indicator Lights 

Output 

Fault 

Alarm 

Operating Modes 

Output Voltage 

Battery Voltage 

Date 

Time 

Buck / Boost Status 

Output Power (Watts) 

Temperature 

Menu Controls 

ESC, UP / DOWN, ENTER 