7. Starting the UPS
1.
Verify that the AC Input & Output and the Battery Circuit
Breaker on the UPS are Off.
2.
Place the Manual Bypass Switch in the UPS position.
3.
Turn ON the upstream Utility Input Circuit Breaker.
4.
Verify the load has power.
5.
Turn ON the AC Input & Output Circuit Breaker.
6.
Turn ON the Battery Circuit Breaker.
7.
LCD display shows STANDBY.
8.
In 30 seconds, The LCD display changes to "ON LINE",
9. T
he Green Output LED
should be l
it indicating
the
Input
power
is
within
an
acceptable
frequency
and voltage
range and the
output is powered from Utility.
8. LCD Home Screen Operation
9. Emergency Shut Down
1. Turn OFF the battery circuit breaker.
2. Unplug the AC INPUT cord and turn off the Utility Line power circuit breaker.
3. Turn OFF the AC input & output circuit breaker.