Maple Systems HMI5043DL Скачать руководство пользователя страница 3

HMI5000L Installation Guide                                                                                                3

1010-1018 Rev 13                                                                          www.maplesystems.com

Technical Support 

This manual is designed to provide the necessary information for trouble-
free installation and operation of the HMI. For assistance, please contact 
Maple Systems as follows:

Phone: 425-745-3229

Email: [email protected]

Web:

www.maplesystems.com

Installation of HMIs

Information furnished by Maple Systems is believed to be accurate and 
reliable. However, no responsibility is assumed by Maple Systems for the 
use of this information, or for any infringements of patents or other rights 
of third parties which may result from its use. No license is granted by 
implication, or otherwise, under any patent or patent rights of Maple 
Systems. Maple Systems retains the right to revise or change its 
products and documentation at any time without notice. 

CE Compliance

The HMIs have been tested to conform to European CE requirements, 
which meet or exceed the noise emissions and immunity requirements 
as set forth in the EN55022 (Emissions) and EN55024 (Immunity) 
standards. The products are designed to withstand electrical noise in 
harsh industrial environments. They also conform to requirements that 
limit electrical emissions. However, this does not guarantee that the 
products will be totally immune from possible malfunction in cases where 
severe electrical noise occurs. Therefore, follow these guidelines for 
proper wire routing and grounding to ensure the proper operation of the 
HMI.

NEMA Rating

The HMI is rated for NEMA 4 (indoor) or IP65/IP66 installations. This 
means that when the HMI is properly mounted to a NEMA 4 panel or 
other NEMA 4 rated enclosure, the front enclosure of the HMI will 
provide protection to the inside of the panel from splashing water, wind-
blown dust, rain, or hose-directed water. The HMI must be installed 
according to the instructions in this manual to be properly sealed.

Содержание HMI5043DL

Страница 1: ...ies touchscreens are configured using the EasyBuilder Pro Software For information on programming and configuring the HMI please refer to the EasyBuilder Pro Programming Manual available for free download on the Maple Systems website in the Support Center For additional information please refer to the Support Center section of the Maple Systems website www maplesystems com support The Support Cent...

Страница 2: ...ll material in the container against the packing list Maple Systems will not accept responsibility for shortages against the packing list unless notified within 30 days The equipment and accessories were inspected and tested by Maple Systems before shipment Examine the equipment carefully if any shipping damage is evident notify the carrier immediately Maple Systems is not responsible for claim ne...

Страница 3: ...pliance The HMIs have been tested to conform to European CE requirements which meet or exceed the noise emissions and immunity requirements as set forth in the EN55022 Emissions and EN55024 Immunity standards The products are designed to withstand electrical noise in harsh industrial environments They also conform to requirements that limit electrical emissions However this does not guarantee that...

Страница 4: ...ational electrical standards when installing the HMI Failure to comply with these restrictions could result in loss of life serious personal injury or equipment damage Warning Do not connect the HMI to an AC power source This will cause permanent damage to the HMI Warning A Hard wired EMERGENCY STOP should be fitted in any system using an HMI to comply with ICS Safety Recommendations Warning Do no...

Страница 5: ...upply used to power the HMI should provide an output of at least 24 VDC 20 measured at the HMI power connector HMI5043Lv2 HMI5043LBv2 should be powered with 22 28VDC only and HMI5043DL should be powered with 10 5 28VDC only A DC regulated power supply dedicated to the HMI is recommended Use a power supply with adequate current rating for the provided voltage A power line filter installed at the AC...

Страница 6: ...nd strap Quiet ground isolated AC Power Line Filter HMI Power Supply Shielded power cable Control panel is tied to a reliable earth ground 2 1 3 4 5 rear side HMI5100L 1 rear side HMI5070L 2 2 3 1 Also HMI5102L HMI5103L HMI5120XL HMI5121XL and HMI5150XL 2 Also HMI5043Lv2 HMI5043LBv2 HMI5043DL HMI5070DL HMI5070LB HMI5070NL HMI5071L HMI5097DXL and HMI5097NXL ...

Страница 7: ...ground Note If the control panel is made of a non conductive material it is essential that the chassis ground terminal of the HMI is connected to a clean earth ground point located close to the panel Connect the power cable s shield wire to the HMI s chassis ground terminal Connect the control panel to earth ground using a copper grounding rod close to the HMI and control panel Hinged doors on con...

Страница 8: ... the power cable from the HMI to the power supply The power cable should not be any longer than necessary 2 Install the cable wires referencing the chart below with colors shown for Maple Systems Cable 6030 0009 a Strip the power cable shield to expose 2 of the black and red wires b Strip about of insulation from the black and red wires c Connect the red wire to the positive input of the HMI power...

Страница 9: ...hes pits and other features that prevent the gasket from sealing properly If the panel or mounting surface is not uniform thick flat stiff or smooth enough then a sealant such as silicone may be required Note Clean and deburr the panel cutout before the HMI is installed Mount the HMI to the Panel Note The clamps for some models may be slightly different than shown here but operate essentially the ...

Страница 10: ... included with the EasyBuilder Pro software must be installed when downloading from the PC to the HMI via USB connection Caution When connecting two powered devices via USB a difference in potential can exist between the ground reference on each device If there is a difference in ground potential voltage making a connection via a USB cable can complete a ground loop that may damage the HMI and PC ...

Страница 11: ... arrow icon located in the lower right corner of the screen 3 Click the gear icon to enter the system settings menu 4 When prompted enter the system password default 111111 5 Navigate to the Network tab 6 Enter the desired IP address or select Obtain an IP Address Automatically to enable DHCP 7 Click Apply to save the changes and OK to exit the system settings menu 8 The updated IP address will ap...

Страница 12: ...PEN Hide System Toolbar OPEN OPEN SHORT OPEN Boot Loader mode OPEN OPEN OPEN SHORT Reserved OPEN OPEN OPEN OPEN Normal operation Note Place a jumper cap between the respective header pins to set the jumper mode HMI Power must be cycled to enable the selected DIP switch or jumper mode Touchscreen Calibration mode This mode allows calibration of the touchscreen This mode can also be entered by press...

Страница 13: ...r up remove power An internal fuse except 4 3 display models will prevent damage if the polarity of the DC power is incorrect Check wiring to ensure proper connections and try to power up again USB Stick Clamp not on all models The USB Stick Clamp prevents a USB stick from disconnecting from the HMI due to vibration Steps 1 Insert the USB stick connector into the clamp and secure with the included...

Страница 14: ... wire RS COM3 1 RX DATA 2 RX DATA 3 TX 4 TX 5 GND 6 TXD 7 DATA 8 DATA 9 RXD Pin COM1 232 RS 1 2 RXD 3 TXD 4 5 GND 6 7 RTS 8 CTS 9 HMI XL 5150 DE9S DE9P HMI5100L HMI HMI LB 5070L 5070 HMI XL 5121 Pin COM1 485 2 wire RS COM1 485 4 wire RS COM3 485 2 wire RS 1 DATA RX 2 DATA RX 3 TX 4 TX 5 GND COM 1 6 7 DATA 8 DATA 9 GND COM 3 HMI 0XL 512 Note COM1 RS 485 2W and COM3 RS 485 2W support the Siemens MPI...

Страница 15: ... 485 4W RS COM2 COM3 485 2W RS RS 485 4W COM3 1 DATA RX 2 DATA RX 3 TX 4 TX 5 GND 6 DATA RX 7 DATA TX 8 DATA TX 9 DATA RX Pin COM1 RS 232 232 RS COM3 1 2 RXD 3 TXD 4 5 GND 6 7 RTS TXD 8 CTS RXD 9 GND Pin COM1 RS 485 2W COM2 485 2W RS COM2 485 4W RS 485 2W RS COM3 COM3 RS 485 4W Note COM1 RS 485 2W and COM3 RS 485 4W available on HMI5102L and HMI5103L units manufactured after July 2018 with OS vers...

Страница 16: ...3 Enter the desired IP address or select Obtain an IP Address Automatically to enable DHCP 4 Navigate to the LAN2 tab 5 Enter the desired IP address or select Obtain an IP Address Automatically to enable DHCP Note LAN1 and LAN2 must be on separate subnets in order for both ports to operate simultaneously 6 Click Apply to save the changes and OK to exit the system settings menu 7 The updated IP add...

Страница 17: ...in addition to the standard RJ45 Ethernet port Supported Wi Fi modes are IEEE 802 11 b g n with WPA PSK WPA2 PSK encryption Wi Fi is off by default To enable and configure Wi Fi 1 Enter the System Settings menu 2 Navigate to the Wireless tab 3 Enter the desired IP address or select Obtain an IP Address Automatically to enable DHCP 4 Select the Wi Fi Setting button ...

Страница 18: ... 10 Tap Close to exit the Wi Fi setting window 11 Click Apply to save the changes and OK to exit the system settings menu 12 The updated IP addressing will appear in the Wi Fi tabs of the System Information window also accessed via the arrow icon Note When using the Wi Fi simultaneously with the wired Ethernet port ensure that the connections are on different subnets Detailed instructions of the H...

Страница 19: ......

Страница 20: ...v 13 www maplesystems com 2022 Maple Systems Inc All rights reserved Maple Systems Inc 808 134th Street SW Suite 120 Everett WA 98204 7333 Phone 425 745 3229 Email support maplesystems com Web www maplesystems com ...

Отзывы: