Getting Started:
Perform the following steps to configure and use the HMC3000
Series unit:
1. Install MAPware-7000 software.
2. Create your project.
3. Connect a programming cable (USB or Ethernet).
4. Save your project.
5. Download project to HMC3070 (note: you must select the
Download Firmware option for the initial download).
6. The HMC3000 unit is ready to use in the system.
PC Requirements for MAPware-7000:
Processor: 1 GHz Pentium-based processor or equivalent
Operating System: Microsoft Windows 7 or 10
RAM: 1 GB
Hard Disk: 800 MB (including 200 MB for the .NET Framework
Redistributable)
Display: 1024x768 high color 16-bit
Mouse/Keyboard: Required
USB or Ethernet port: for project downloads
Installing the Software:
1. Insert MAPware-7000 CD into CD-ROM drive and follow
instructions.
2. If software installation does not automatically start, click
\SETUP.EXE from CD directory.
PLC Connecting Cables:
Contact Maple Systems to order any PLC Communications
Cables or to download a cable pinout diagram.
Additional Resources:
Detailed instructions on the operation and installation of the
HMC3000 Series are available in the HMC3000 Programming
Manual that is included with the MAPware-7000 configuration
software. MAPware-7000 also includes help files that provide
detailed information on using the configuration software.
Other Sources (visit Maple Systems Support Center website):
—
Controller Information Sheets- specific information on
connecting a particular manufacturer's PLC to the HMC3000
—
Cable Drawings- wiring diagrams to particular PLCs
—
Technical Notes- Provides additional information and examples
not covered in the operations manual
—
Software Upgrades- Upgrades to the MAPware-7000 software
Class I Division 2 Wiring Considerations:
Capacitance and inductance of the field wiring from the
nonincendive equipment to the associated apparatus shall be
calculated and must be included in the system calculations as
shown in Table 1.
Where the cable capacitance and inductance per foot are not
known, the following values shall be used: Ccable = 60 pF/ft,
Lcable = 0.2 µH/ft.
TABLE 1:
Wiring method must be in accordance with ANSI/NFPA70.
This equipment is suitable for use in Class I, Division 2, Groups A,
B, C and D or non-hazardous locations only.
WARNING – EXPLOSION HAZARD – Do not disconnect
equipment unless power has been removed or the area is known
to be non-hazardous.
WARNING – EXPLOSION HAZARD - Substitution of
components may impair suitability for Class I, Division 2.
WARNING - CAUTION, battery may explode if mistreated. Do
not recharge, disassemble or dispose of in fire.
It is recommended that the user periodically inspect the sealed
devices used, check for any degradation of properties, and
replace as necessary.
For Technical Support:
Please contact Maple Systems if you have any questions