Recommended Installation Procedures: 
 
Support Framing:

 We strongly 

recommend that prior to the installation of 
this Roof mounted Pedestal Hydrant that a 
field provided welded angle frame be 
installed at the bottom surface of the roof 
decking.  This framing should be of 
sufficient size to permit the provided under-
deck flange to slide freely yet firmly into the 
frame and rest firmly against its top.  The 
framing should be of sufficient strength to 
prevent any dislodging of the Hydrant 
during normal operation. Refer to 

Figure 1

 
Installation Sequencing:

   

We recommend that the Hydrant not be 
installed until the roof decking and all roof 
insulation is in place.  A round hole should 
be cut in the roof insulation and deck to 
permit the hydrant to pass from the roof 
surface through this opening to below the 
roofline with the base resting squarely on 
the insulation.  We do not recommend 
making final piping connections to the 
Hydrant until all roof work associated with making the hydrant  
base watertight to the roof is completed and then not until the  
under-deck clamp has been installed. 
 

Connections to the Water Source:

   

We recommend that a valve be installed on the 
supply piping serving the hydrant.  This valve should 
be in a convenient and easily accessible location.  In 
order for the venturi to properly operate, we 
recommend that the supply piping be minimum ¾”.  
Optimal water pressure at the hydrant supply should 
be 60 PSI (typical city water pressure), however it will 
still operate properly at a minimum of 20 PSI. 
 

Installation of the Hydrant:

  A hole approximately 

seven inches (7”) in diameter should be cut in the 
roof decking.  The hole should be centered on an 
angle frame welded to the roof structure below the 
decking.  Once roof insulation is in place, cut through 
the insulation and place the Hydrant base squarely 
onto the roof surface.  Square the Hydrant, pointing 
the outlet nozzle in the desired direction.   
Refer to 

Figure 2 

of the Instructions. 

 
Caution should be taken to assure that the Hydrant is 
vertically level above the roof.  We do not 
recommend installing the Hydrant within four feet of 
the edge of the roof or within three feet of other roof 
top equipment or on any sloping surfaces of the roof.  
If recommended by the roofing manufacturer, holes 
can be drilled along the outer edge of the flange to 
permit anchoring of the hydrant to the roof membrane 
prior to final flashing of the hydrant to the roofing 
surface.

 

 

 

 

Содержание MPH-24-FP:24/9

Страница 1: ...on is made at the fitting on the reservoir located at the base of the Hydrant Unpacking the Hydrant Parts Included Hydrant Assembly Under deck flange Assembly Hardware Installation Instructions Assembly Hardware is located in a plastic bag that is attached to the underside of the under deck flange Parts 4 X 2 set screws 4 X 1 hex head bolts Verify that all assembly parts are present How the Hydran...

Страница 2: ...r deck clamp has been installed Connections to the Water Source We recommend that a valve be installed on the supply piping serving the hydrant This valve should be in a convenient and easily accessible location In order for the venturi to properly operate we recommend that the supply piping be minimum Optimal water pressure at the hydrant supply should be 60 PSI typical city water pressure howeve...

Страница 3: ...tion be made to the hydrant than as stated here To connect the disconnect fitting to the hydrant pull back on the spring loaded female end of the disconnect at the hydrant s outlet and insert the male end that is attached to the vacuum breaker Release the spring on the female end Attach the female fitting of a garden hose to the end of the vacuum breaker Winterizing for Severe Weather It is recomm...

Страница 4: ...MAPA Products LLC Box 129 Naples Texas 75568 Phone 903 897 2371 Watts 877 897 2371 Fax 903 897 2781 Page 4 of 5 ...

Страница 5: ... the amounts paid for the product by the purchaser DISCLAIMER OF IMPLIED WARRANTY THERE ARE NO WARRANTIES THAT EXTEND BEYOND THE DESCRIPTION HEREIN SELLER DISCLAIMS ANY IMPLIED WARRANTY OF MERCHANTABILITY OF THE GOODS OR OF THE FITNESS OF THE GOODS FOR ANY PURPOSE AND BUYER AGREES THAT THE GOODS ARE SOLD AS IS Limits of Liability MAPA s liability shall be limited to costs of repair or replacement ...

Отзывы: