Mantis BF28BM-4 Скачать руководство пользователя страница 9

27297-1-1010

Page 9

GAS SUPPLY

All  gas  piping  must  be  installed  in  compliance  with  local 

 

codes and utility regulations.  In the absence of local codes 

the  installation  must  comply  with  NFCG  NFPA  54/ANSI 

Z223.1.  

Note:

 Never use plastic pipe. Check to confirm whether your 

 

local codes allow copper tubing or galvanized.

Where permittted, flexible gas connectors must be certified 

to the following standards:  

—  ANS Z21.24 Appliance Connectors of Corrugated Metal 

Tubing and Fittings

—  ANS Z21.45 Assembled Flexible Appliance Connectors 

of Other Than All-Metal Construction

The  above  connectors  may  be  used  if  acceptable  by  the  

uthority  having  jurisdiction.  The  state  of  Massachusetts 

 

requires that a flexible appliance connector cannot exceed 

three feet in length.

A drip leg should be installed in the vertical gas supply pipe 

run to the unit.  

Manual Shut-off Valve

Some  local  regulations  require  the  installation  of  a  

manual shut-off valve and ground joint union external to the 

 

appliance.    The  shutoff  should  be  accessible  for  service 

and/or    emergency  use.    Consult  the  local  utility  or  gas 

 

supplier  for  additional  requirements  regarding  the  

placement of the manual shut off valve.  Compounds used 

on  threaded  joints  of  gas  piping  shall  be  resistant  to  the 

 

action of liquefied petroleum gases.

Leak Testing

WARNING - FIRE OR EXPLOSION HAZARD

Never  test  for  leaks  with  an  open  flame.    Check  all 

connections  using  a  commercially  available  soap  

solution.    A  fire  or  explosion  may  result  causing 

 

property  damage,  personal  injury  or  loss  of  life.   

Failure  to  follow  the  safety  warnings  exactly  could  

result in serious injury, death or property damage. 

 

After gas piping to the heater is complete, all connections 

must be tested for gas leaks.  This includes pipe connec-

tions at the main gas valve, emergency shutoff valve and 

flexible gas connectors (if applicable).  The soap and water 

solution can be applied on each joint or union using a small 

paintbrush.  If any bubbling is observed, the connection is 

not  sealed  adequately  and  must  be  retightened.    Repeat 

the  tightening  and  soap  check  process  until  the  bubbling 

ceases.  

Important Note:

When pressure testing the gas supply lines at pressures  

greater  than  ½  psig  (14  in.  w.c.),  the  gas  supply  pip-

ing system must be disconnected from the appliance 

to prevent damage to the gas control valve.  If the test 

pressure is less than or equal to ½ psig (14 in. w.c.), 

close the manual shut-off valve.

Pressure Testing of the Gas Supply System

1.  To check the inlet pressure to the gas valve, a 1/8 inch 

N.P.T.  plugged  tapping,  accessible  for  test  gauge  

connection,  must  be  placed  immediately  upstream  of 

the gas supply connection to the appliance.

2.   The appliance and its individual shutoff valve must be 

disconnected from the gas supply piping system during 

any pressure testing of that system at test pressures in 

excess of 1/2 psig.

3.   The  appliance  must  be  isolated  from  the  gas  supply 

piping system by closing its individual manual shutoff 

valve  during  any  pressure  testing  of  the  gas  supply  

piping  system  at  test  pressures  equal  to  or  less  than 

1/2 psig.

Recommended Gas Pipe Diameter

Pipe Length Schedule 40 Pipe

Inside Diameter

In Inches

Tubing, Type L 

Outside Diameter

In Inches

Nat.

L.P.

Nat.

L.P.

0-10 feet

1/2

3/8

1/2

3/8

10-40 feet

1/2

1/2

5/8

1/2

40-100 feet

1/2

1/2

3/4

1/2

100-150 feet

3/4

1/2

7/8

3/4

Содержание BF28BM-4

Страница 1: ...be performed by a qualified installer service agency or the gas sup plier WARNING If the information in these instructions are not followed exactly a fire or explosion may result causing property dam...

Страница 2: ...Mantis Clearance to Combustibles 18 Fireplace Mantis Clearance to Combustibles 19 Bay Window Mantis Specifications 20 21 Fireplace Mantis Specifications 22 23 Gas Connection Installation 24 Bay Window...

Страница 3: ...WARNING Installation and repair should be done by a QUALIFIED SERVICE PERSON The appliance should be inspected before use and at least annually by a qualified service person More frequent cleaning ma...

Страница 4: ...d gas can adsorb or absorb onto or into walls masonry and other materials and fabrics in a room That will take some of the odorant out of the gas reducing its odor intensity LP Gas may stratify in a c...

Страница 5: ...IAS certified 3 SIGNAGE A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight 8 feet above grade directly in line with the e...

Страница 6: ...codes Always con sult with local authorities before installing any gas appliance Combustion and Ventilation Air U S NationalFuelGasCodeNFPA54 ANSIZ223 1 NFGC Air for Combustion and Ventilation Electr...

Страница 7: ...ermostat FRBTP Battery Operated Remote with Programmable Thermo stat PVCA Colinear Adapter PVCT Colinear Transition Kit PVVK24H Direct Vent 24 Vent Kit PVVK48H Direct Vent 48 Vent Kit PVVK CFA Flex Ve...

Страница 8: ...t shock hazard and should be plugged directly into a properly grounded three prong receptacle Do not cut or remove the grounding prong from this plug For an ungrounded receptacle purchase an adapter w...

Страница 9: ...arnings exactly could result in serious injury death or property damage After gas piping to the heater is complete all connections must be tested for gas leaks This includes pipe connec tions at the m...

Страница 10: ...gulator vent outlet J Clearance to non mechanical air supply inlet to building or the combustion air inlet to any other appliance 6 in 15 cm for appliances 10 000 Btu h 3 kW 9 in 23 cm for appliances...

Страница 11: ...system will be the equivalent to 3 feet and each 45 elbow is equivalent to 1 5 feet The minimum vent length is 12 inches It is recommended that the Mantis Power Vent High Efficiency Fireplace be loca...

Страница 12: ...he total horizontal vent length of the flue system is 7 feet and the total vertical length is 27 feet The two 90 elbows are equivalent to 6 feet bringing the total to 40 feet Figure 4 is an example of...

Страница 13: ...eet The three 90 elbows are equivalent to 9 feet bringing the total to 40 feet Note The exhaust must be a minimum of 3 inches above the inlet air pipe The flue must be at least 12 inches from the roof...

Страница 14: ...inlet can be terminated with either a PTrap or two 90 elbows as shown in Figures 8 11 and 12 The Vertical Termination Cap Part number PVVTC can also be used H FLASHING REQUIRED H REQUIRED HEIGHT IS 12...

Страница 15: ...HEIGHT IS 12 MINIMUM IT IS RECOMMENDED TO BE 12 ABOVE THE MAXIMUM EXPECTED SNOW LEVEL Installation of the Colinear Transition Plate 1 Attach the plate to chimney chase flat roof or outside wall with...

Страница 16: ...um 12 5 8 minimum 17 7 8 minimum B 25 1 4 minimum 27 maximum when using PVE 1 or PVE 2 Surround Kits C 28 1 2 minimum 33 minimum recommended for service 34 1 2 maximum when using PVE 1 Surround Kit 37...

Страница 17: ...B 25 1 4 minimum 27 maximum when using PVE 1 or PVE 2 Surround Kits C 28 1 2 minimum 33 minimum recommended for service 34 1 2 maximum when using PVE 1 Surround Kit 37 maximum when using PVE 2 Surroun...

Страница 18: ...y Fireplace has been tested and approved for zero clearance to combustible materials It is recommended that clearances as listed above should be maintained to allow for removal of the product for serv...

Страница 19: ...ace has been tested and approved for zero clearance to combustible materials It is recommended that clearances as listed above should be maintained to allow for removal of the product for servicing Fi...

Страница 20: ...ater with Pedestal and Single Flue Adaptor Figure 26 28 25 1 4 27 3 4 FLUE OUTLET 16 15 16 17 5 8 3 9 16 9 0cm Heater without pedestal Figure 27 6 17 13 16 6 1 2 PVE 1 or PVE 2 SURROUND PVVK CFA FLEX...

Страница 21: ...5 7 16 OR 38 LOUVER 29 3 4 5 15 16 23 13 16 PV 2H SLIM TOP COVER KIT 11 5 16 3 3 9 16 6 Fireplace Insert with Mantel Surround with PV 2H Slim Top Cover Kit Figure 29 Fireplace Insert with Mantel Surro...

Страница 22: ...SS Contains surround hood and lower front Heater 35 Inch Surround Kit FFK28 BL CM HP SS Contains surround hood lower front Figure 34 Figure 35 Figure 32 Heater with Flex Vent PVVK CFA FLEX VENT KIT 2...

Страница 23: ...AIR INLET ELECTRIC CORD FLEX HOSE OPENING 1 1 8 7 5 16 4 3 16 2 5 8 6 1 8 3 9 16 13 16 1 28 Heater 38 Inch Surround FIK28 BL CM HP SS Contains surround hood lower front Figure 36 Figure 37 4 8 Figure...

Страница 24: ...y excess flexible line can be pushed back into the heater 3 Place rubber grommet that is supplied in hardware packet over the flexible gas line and secure in the hole in the back of the appliance Gas...

Страница 25: ...C into the groove on A Log and locate into the left corner of firebox See Figure 43 6 Place the Middle Log D over the flame sensors that are located in the middle of the firebox 7 Locate the Front Ri...

Страница 26: ...flame sensor See Figure 50 5 Place the Front Left Log E on left side of the firebox bottom The notch in bottom of Front Left Log fits over front Igniter See Figure 50 6 Place the Right Log C on the r...

Страница 27: ...hould be plugged directly into a properly grounded three prong receptacle Do not cut or remove the grounding prong from this plug For an ungrounded receptacle an adapter which has two prongs and a wir...

Страница 28: ...ee Figures 45 and 50 5 Check and verify that logs are place correctly See pag es 25 to 26 The logs must be in the correct position or the heater will not operate correctly DO NOT light heater without...

Страница 29: ...gas control which has been under water LIGHTING INSTRUCTIONS 1 STOP Read the safety information above on this la bel 2 Set the thermostat if used to the lowest setting 3 Turn off all electric power t...

Страница 30: ...his sequence may result in the heater needing to be reset See page 33 Resetting the Heater Sequence of Operations One Burner Only 1 The Display Panel will be energized and the light for either the fro...

Страница 31: ...ltitude The Mantis can be installed to altitudes up to 10 000 feet in the U S The installation must meet the requirements of the National Fuel Gas Code or local jurisdictions See the instruc tions pro...

Страница 32: ...he T24V thermostat screws There is no polarity at this connection See Figure 59 REMOTE CONTROL RECEIVER OR T24V THERMOSTAT BLACK BLACK WHITE WHITE RED JUNCTION BLOCK TO TRANSFORMER BLUE TO T2 REAR BUR...

Страница 33: ...r latches on both the left and right sides of the firebox 4 Carefully grab the glass frame and pull towards you Do not damage or remove the gasket from the door FIREPLACE MANTIS MODELS Removing the Gl...

Страница 34: ...side of the heat er The heat exchanger should be inspected and cleaned annually by a qualified service person Replacement Logs If for any reason a log should need replacement contact your Mantis deale...

Страница 35: ...Parts Heater Hearth and Grills Victor Division of F W Webb Company 200 Locust Street Hartford CT 06114 Phone 860 722 2433 Toll Free 800 243 9360 Fax 860 293 0479 Toll Free Fax 800 274 2004 Websites w...

Страница 36: ...5 COVER INLET AIR DUCT 25 22780 INLET AIR DUCT ASSEMBLY 26 R8810 GASKET INLET AIR DUCT 27 21641 BRACKET ASSEMBLY THERMISTER SPRING CLIP INCLUDED 28 R4053 CLAMP DOOR 4 USED ON UNIT 29 22773 THERMISTER...

Страница 37: ...Y 70 R8840 WIRE HARNESS ASSEMBLY WITH ECONOMY SWITCH 71 R8809 SWITCH DOUBLE ROCKER 72 R8904 CIRCUIT BOARD 73 25226 CIRCUIT BOARD PLATE 74 R8905 RIBBON CABLE 75 R8872 CIRCUIT BOARD WIRE HARNESS 76 R101...

Страница 38: ...27297 1 1010 Page 38 BAY WINDOW MANTIS PARTS VIEW 1 31 4A 5 6 9 7 30 28 5 21 27 24 28 19 11 12 9 34 16 14 26 25 22 17 8 3 2 13 36 18 35 23 4B 15...

Страница 39: ...BAY WINDOW MANTIS PARTS VIEW 69 67 32 61 50 47 48 53 54 53 51 60 20 56 55 48 47 80 52 65 39 40 41 42 38 45 46 89 85 86 87 88 81 84 78 77 83 76 90 44 43 49 37 82 70 71 64 79 63 62 57 59 30 10 74 75 68...

Страница 40: ...24 R8804 TRANSFORMER 24V 25 R10079 CONDENSATE PUMP BOX 26 R8832 CONDENSATE PUMP 27 R10080 CONDENSATE PUMP LID 28 25226 CIRCUIT BOARD PLATE 29 R8809 DOUBLE ROCKER SWITCH 30 R8840 WIRE HARNESS ASSEMBLY...

Страница 41: ...63 R10381 LEFT LOG 64 R10380 RIGHT LOG 65 R10379 MIDDLE LOG 66 R10378 FRONT LEFT LOG 67 R10377 FRONT RIGHT LOG 68 R10383 LEFT TOP LOG 69 R10382 RIGHT TOP LOG 70 25216 BRACKET STANDOFF 2 REQUIRED INDEX...

Страница 42: ...IS PARTS VIEW 1 2 3 4 5 6 7 8 9 11 12 13 14 15 16 17 18 19 60 20 21 22 23 24 25 53 54 55 56 58 57 52 26 27 28 29 30 31 32 61 33 37 38 39 59 40 43 44 48 45 46 47 50 49 41 42 42 41 40 36 10 35 35 34 51...

Страница 43: ...h the appliance Ready access to the appliance for service is the responsibility of the owner Travel diagnostic costs and freight charges on warranted parts to and from the factory is the responsibilit...

Страница 44: ...s Empire Comfort Systems Inc 918 Freeburg Ave Belleville IL 62220 If you have a general question about our products please e mail us at info empirecomfort com If you have a service or repair question...

Отзывы: