Installation Instructions
Specifi cations are subject to change without notice
Page 3
[email protected] | www.manrose.co.nz
Distributed by Simx Limited
QUIET 150mm Extraction Fan
INSTALLATION
1. In a kitchen installation, do not install the fan any closer, laterally, than 2m from the cooktop.
Visit the Manrose website for fan kit options best suited for lateral kitchen installations within 2m of
a cooktop.
2. In a bathroom installation, the fan can be installed within 1.5m, laterally, of the steam source and
immediately above the bath or shower tray up to the higher of either 2.25m or the height of the
fi xed plumbing connection.
3. Cut a 140mm diameter hole through the wall. We recommend the use of semi-rigid ducting which
should be installed sloping slightly downwards away from the fan. Cut to length and tape both ends
into position fl ush with the wall faces. Push the two clips on the bottom of the fan and pull the grille
away from the chassis.
4. Using the built in spirit level bubble as an aid, mark the screw centres through the holes in the fan
back plate. Drill, plug and screw into position. Fix an exterior grille into position with the louvres
angled
downwards.
NOTE:
The grille must be fi tted to comply with the standard requirements to prevent access to
the fan’s impeller. The wall kit used in this installation should provide a minimum ducting length of
100mm from the fans back plate to the inside of the external grille.
5. After installation, ensure impeller rotates freely and the shutters can open.
6. Replace the grille and ensure the clips are engaged.
Open up the internal cover to access the spirit
level bubble and terminals
Fig 1
EXTRACTION FAN INSTALLATION AND ELECTRICAL CONNECTION MUST
BE CARRIED OUT BY A REGISTERED ELECTRICIAN IN ACCORDANCE
WITH THE LATEST WIRING RULES AS/NZS3000.
EXTRACTION FAN AND ANCILLARY CONTROL EQUIPMENT MUST BE
ISOLATED FROM THE POWER SUPPLY DURING INSTALLATION OR MAINTENANCE
IMPORTANT
• The fan should only be used in conjuction with fi xed wiring.
• The cross-sectional area of supply cord used should be ranged from 1 -1.5mm
2
with the appropriate sized protection device.
• Cable entry can only be made from the rear of the fan.
• The fan is suitable for connection to 220-240V AC 50Hz supply.
• The fan is a Class ll double insulated product and
MUST NOT
be earthed.
• Check all connections have been made correctly and securely fastened.
• Ensure the impeller rotates and is free of any obstructions.
MAINTENANCE
1. At regular intervals following installation, the fan should be inspected and cleaned to ensure there is no build up of dirt or other deposits.
2. The fascia can be cleaned without removal by wiping the inlets and front face with a damp cloth.
3. The fan has sealed for life bearings, which do not require lubrication.
DISPOSAL
This product should not be disposed of with household waste. Please recycle where facilities exist. Check with your local authority for recycling
advice.