background image

I

MPORTANT: READ THESE INSTRUCTIONS BEFORE COMMENCING THE INSTALLATION

DO NOT - install this product in areas where the following may be present or occur:
•  Excessive oil or a grease laden atmosphere.
•  Corrosive or flammable gases, liquids or vapours.
•  Ambient temperatures higher than 40°C or less than –5°C.
•  Possible obstructions which would hinder the access or removal of the Fan.

SAFETY AND GUIDANCE NOTES

1. When the Fan is used to remove air from a room containing a fuel-burning appliance, ensure that the air 

replacement is adequate for both the fan and the fuel-burning appliance.

2. The Fan should not be used where it is liable to be subject to direct water spray for prolonged periods of time.
3. Where ducted Fans are used to handle moisture-laden air, such as a bathroom, a condensation trap should 

be fitted in any vertical exhaust ducts.  Horizontal ducts should be arranged to slope slightly downwards away 
from the Fan. Ducts passing through cold voids must be suitably insulated.

4. This product should not be disposed of with household waste. Please recycle where facilities exist. Check 

with your local authority for recycling advice.

INSTALLATION

PANEL/CEILING MOUNTING

1. For panel/ceiling mounting the fan should be installed into a closed duct system of at least 1.2m long or 

protected by an exterior air grille that must comply with the standard requirements of your country to prevent 
access to the fans impeller.

2. Cut a 105mm diameter hole.
3. Loosen the screw at the bottom of the grille and remove the front grille.  Mark the screw centres through the 

holes in the fan back plate. Drill, plug and screw into position.

4. Attach ducting as required for the installation. 
5. Wire the fan as described in the Wiring section. 
6. After installation, ensure impeller rotates freely.
7. Replace the grille and tighten the retaining screw.

WALL MOUNTING 

1. For wall mounting cut a 115mm diameter hole through the wall and insert the wall sleeve. Slope the sleeve 

slightly downwards away from the fan. Cut to length and cement both ends into position flush with the wall 
faces. 

2. Loosen the screw in the bottom of the grille and remove the front grille. Mark the screw centres through the 

holes in the fan back plate. Drill, plug and screw into position. 

3. Fix exterior grille into position with the louvres positioned downwards. (Note:- The grille must comply with the 

standard requirements of your country to prevent access to the fans impeller). 

4. Wire the fan as described in Section B-Wiring. Adjust any settings as required (see Section C-Setup).
5. After installation, ensure impeller rotates freely.
6. Replace the grille and tighten the retaining screw.