DKR Drive Controllers
Planning the electrical connections
6-21
DOK-DIAX03-DKR********-PR02-EN-P
X9: Control inputs for internal power contactors
SBX9DKR
1
2
3
4
5
6
OFF
ON
X9
inside
the unit
open external
contact effects:
closed external
contact effects:
power off
External contact requirements: DC 24 V/625 mA
Maximum core cross section: 2,5 mm
2
inhibit to
regenerate energy
outside
the unit
ready for power off
power on
Fig. 6-21:
Inputs at X9
Only use input X9.1 in exceptional cases. Please contact us for a detailed
description of how to use this input.
The internal power contactor can only be switched when this input is
closed (see ON contact).
Opening the OFF contact immediately switches the internal power
contactor off.
Note:
The power contactor has not been designed to switch always
under load, i. e. it is only appropriate for de-energization and
occasional E-stop. Use the "E-stop" function for emergency
switch-off (see DIAX03 Function Description for details).
When the ON contact is activated, the internal power contactor is
switched on, if
•
the OFF contact is closed and
•
a machine-internal ready state is being signaled (see Bb1 contact
also).
The internal power contactor is a self-holding contact.
X5 and X10: Power voltage, control voltage and brake resistor
connections
SBX5u10DKR
A1 A2 A3
3 x AC 400 … 480 V,
50…60 Hz
mains earthed
N L K
control
voltage
AC 230 V,
50…60 Hz
±10%, 200 VA
L1 L2 L3
F1
X5
B1 B2
X10
mains connection
motor connection
+ -
DC bus
voltage
500...600 V
R1 R2
+ -
bleeder-
connection
(with DKR04)
L1 L2 L3
Fig. 6-22: Terminal connector assignments at X5 and X10
If the internal main contactor K1 to increase safety is switched off directly,
in other words, not via the attached auxiliary relays, then the contactor coil
may also be directly isolated from the mains. This means that the bridge
between X10/L and X10/K must be removed and the contactor coil K
must be externally connected to L via a switch.
Inhibit to regenerate energy
OFF contact
ON contact
Terminal connector X10/K