background image

6

– REG 1 space controller

– N230-24 connector for VBM-V box

– servo drive for LMV-D3 air flow controller

– connecting cable of the supply voltage 1x230V/50Hz with EURO plug

Operational voltage 24V AC/DC, 50/60Hz, max. 1.5VA.

Analog input 0...10V DC

Analog output 0...10V DC.

Operational temperature range 0-50°C, r.v.<95%, environment without condensing risk.

Cover: IP30 - after wall installation, IP00 before wall installation.

Touchscreen with blue backlight.

Time schedule for each weekday.

Party mode activation with the possibility of its automatic turnoff after pre-set time (set for 10min).

Non-presence mode with optional ventilation intensity and time of operation.

Optional ventilation grades (5 grades)

Change of setting parameters, protected by password.

Designed for mounting into an installation box, recommended installation box position (height) from the floor is ca 1.5m.

PARTY / AUTO / MANUAL OPERATION

BACK IN MENU

CANCEL THE CHANGED VALUE

 activates time program.

longer  than  2s:  setting  the

 

time and mode within interval.

Real-time clock

 Increases the set value

(in settings menu it increases the pa-
rameter value)

 Decreases the set

value (in settings menu it decreases
the parameter value)

Ventilation grade indicator

 Activates the PARTY

operation: Outlet will be fully open.
(Program function: to select the menu
item, accepting changed value)

Содержание VBM-V Series

Страница 1: ......

Страница 2: ...ies assembly operation and maintenance Description 2 Construction 2 Size and weight 3 Installation and placement 4 Basic parameters 5 Electric elements connection diagram 5 Pressure losses 8 Noise dat...

Страница 3: ...size Each ventilation box may be controlled by a separate remote control In the box there is a power supply and control unit installed for the air flow control with a flexible connection with euro ty...

Страница 4: ...3 480 120 240 392 220 100 552 98 44 1250 480 120 240 392 220 100 552 123 44 1250 520 130 260 456 245 107 552 158 32 1400 Removable lid 24 26 31...

Страница 5: ...d anchors with load corresponding to the box weight Ceiling installation should be always performed by a removable lid in a downward direction i e to the floor Vertical wall fixing is possible in the...

Страница 6: ...RADE 2 GRADE MAX Setting of ventilation intensities for respective grades is within the range of 0 10V MIN 2V 1 GRADE 4V 2 GRADE 6V MAX 10V Remote control is pre set from the factory Different require...

Страница 7: ...et for 10min Non presence mode with optional ventilation intensity and time of operation Optional ventilation grades 5 grades Change of setting parameters protected by password Designed for mounting i...

Страница 8: ...e and select PRO confirm by select ON or OFF turn time schedule off or on select ON push large digits on the display will show PR01 small digits will show the beginning of the first time interval push...

Страница 9: ...60 70 80 90 100 110 120 130 140 150 160 170 180 190 LwA to the pipe for VBM V 125 del p 100Pa del p 250Pa V m3 h L wA dB A 10 15 20 25 30 35 40 30 40 50 60 70 80 90 100 110 120 130 140 LwA to the pipe...

Страница 10: ...18 17 14 6 4 D dB 12 11 20 19 20 19 11 6 Shell of the VBM V ventilation box is made of steel zinc plates Box is equipped by flanged with edge rubber sealing Flow rate controllers shells and valve damp...

Страница 11: ...er provides a warranty of 24 months for the box from the date of its shipment Such warranty will not apply in case of box use for any other purpose equipment and working conditions as allowed by this...

Страница 12: ...ght for innovations of the product For actual product information see www mandik com MAND K a s Dob sk 550 26724 Hostomice Czech Republic Tel 420 311 706 706 Fax 420 311 584 810 311 584 382 E Mail man...