5
Pushbutton
TURNED OFF/ON
Pushbutton for ventilation grades
switching
LED diodes for control levels:
TURNED OFF - in red
TURNED ON - in green
"Automatic operation" control lamp -
functional only with external sensor
³
³
30
140
60
190
80
320
■
Operational voltage 24V AC/DC, 50/60Hz, max. 1,0VA
■
Analog input 0...10V DC
■
Analog output0...10V DC
■
Temperature scale for operation 0-50°C, r.v.<95%, environment without condensing risks
■
Cover: IP40 - after wall installation, IP00 before wall installation
■
Manual control of ventilation intensity in four grades: TURNED OFF-MIN/1.GRADE/2.GRADE/MAX
■
Setting of ventilation intensities for respective grades is within the range of 0...10V (MIN=2V, 1.GRADE=4V, 2.GRADE=6V,
MAX=10V)
■
Remote control is pre-set from the factory. Different requirements for setting grades of the remote control should be specified
when making the order
■
Automatic switching from the MAX mode to the 2. GRADE after 120min
■
Designed for installation box, recommended height of assembly box from the floor is ca 1.5m
■
Remote space control may be reconfigured into different parameters by using an external maintenance device (maintenance
device is not included in this supply)
JP1 in the 1+2 position - turned off mode without voltage (closed)
JP1 in the 2+3 position - turned off mode ventilating in minutes air flow (MIN)
Содержание VBM-V 100
Страница 1: ......