MSD - multi smoke damper
TPM 159/22
■
Drill holes into the protection box (from outside to inside) and pull through field wiring cables (CAT 3 fire resistant cables
as BS 8519) to connect control module.. Protection box is made of calcium silicate plates.
■
Procedure
■
Use drill (drill size acc. to suit connecting cable Ø + 2 mm for seal up by mastic) and make holes (min. pitch of the holes
must be 30 mm), number of holes depends on the type of control module. It is possible to drill holes in any side of the
protection box.
■
Pull the heat resistant cable through the calcium silicate insulating plate (wall) and connect with cables from control
module.
■
Seal up the space around cable with fire resistant mastic (HILTI CFS-S ACR, PROMASTOP) or equivalent.
■
Let the mastic harden.
Drilling areas for routing the connection cable of modul to the actuator
Dimensions of protection box
Connection of the control module MDPM & MDCM interfaces inside protection box