Before entering the dampers into operation after assembly and after sequential revisions, checks
and functionality tests of all designs including operation of the electrical components must be
done. After entering into operation, these revisions must be done according to requirement set
by national regulations.
In case that dampers are found unable to serve for their function for any cause, it must be clearly
marked. The operator is obliged to ensure so that the damper is put into condition in which it is
able to function and meanwhile he is obliged to provide the fire protection another appropriate
way.
Results of regular checks, imperfections found and all-important facts connected with the damper
function must be recorded in the "FIRE BOOK" and immediately reported to the operator.
Before entering the dampers into operation after their assembly and by sequential checks, the
following checks must be carried out for all designs.
Visual inspection of proper damper integration, inside damper area, damper blade, contact
surfaces and silicon sealing.
Inspection hole disassembly: release the covering lid by turning the wing nut and while turning
the lid right or left release it from the security belt. Then tilt the lid and remove it from its original
position.
For designs 4Mx or 5Mx check of blade displacement into the position "CLOSED" can be done
after connecting the electromagnet impuls. Check of blade displacement back into the "OPEN"
position can be done after connection of actuating mechanism power supply. After check
actuating mechanism power supply has to be cutting off.
For designs .44, .54 and .66 check of damper blade displacement can be realize after actuating
mechanism supply connection or signal connection from higher level control systems. Blade
displacement from position “OPEN” to position “CLOSED” and return displacement is checked.
Spare parts are supplied only on basis of an order.
Data label is placed on the damper body.
WEIGHT (kg):
Dobříšská 550, 267 24 Hostomice, Czech Republic
MANDÍK, a.s.
ACTUATING SYSTEM:
YEAR/SER.NO.:
DIMENSION:
1391
EN 12101-8:2011
TPM 109/15
R
FIRE PROTEC. CLASS:
MANUAL
Cert. No.: 1391-CPR-2016/0123, DoP: PM/MSD/01/20/1
WEIGHT (kg):
Dobříšská 550, 267 24 Hostomice, Czech Republic
MANDÍK, a.s.
ACTUATING SYSTEM:
YEAR/SER.NO.:
DIMENSION:
1391
EN 12101-8:2011
TPM 109/15
R
FIRE PROTEC. CLASS:
MANUAL
Cert. No.: 1391-CPR-2015/0058, DoP: PM/MSD-W/01/20/1