Page 47
Version 2023-06-15
Fire damper - FDMR
TPM 140/19
Ø
D
min.
Ø
D+80
max.
Ø
D+800
EIS 60
EIS 90
≥ 100
variable
4
0
..
.4
0
0
≥
1
0
0
*
*
X
4
0
..
.4
0
0
≥
100
X
≥
2
0
** EIS 60
for DN 100 – DN 800 - thicknes 100 mm
EIS 90
for DN 100 – DN 315 - thicknes 120 mm (2x60 mm)
EIS 90
for DN 350 – DN 800 - thicknes 160 mm (100+60 mm)
* HILTI system can be replaced by a similar
system with the same or higher thickness,
density, fire reaction class, tested according
to EN 1366-3.
1
FDMR
2
Gypsum wall construction
3
Insulation board made of mineral wool, with a surface treatment of aluminum foil, min. density 66 kg/m³ (System ISOVER Ultimate Protect Wired Mat 4.0
Alu1)**
4
Standard air duct, made of galvanized sheet metal min. thickness 0,8 mm
5
ISOVER Protect BSK glue - apply on the insulation and fix it to the fire separation construction
6
Clamp with threaded rod
Weichschott system HILTI*
7
Mineral wool board - min. density 140 kg/m³ (HILTI CFS-CT B 1S 140/50...)
8
Fire stop coating - th. 1 mm (HILTI CFS-CT...) - coating is overcoated on the support construction and on the damper casing/duct
9
Fire-resistant mastic - (HILTI CFS-S ACR...) fill the gap from both sides of the fire separation construction and around the perimeter of penetration and
damper casing
■
For connection of following duct
■
Minimum and maximum distance between the wall and fire damper is unlimited
■
When installing the insulation, follow the ISOVER manufacturer's instructions
■
The damper and the duct must be suspended separately
■
The duct must be suspended on both sides of damper acc. to national rules
■
Duct between fire damper and fire separating construction must be suspended by using threaded rods and mounting profiles, or another
mounting system acc. to national standards
■
Load of the suspension system depends on weight of the fire damper and duct system
■
Max. distance between two suspension systems is 1500 mm
■
Duct at the point of penetration must be fixed to the fire separation structure
■
Following air-conditioning duct must be suspended or supported so that all load transfer from the following duct to the fire damper is absolutely
excluded. Adjacent duct must be suspended or supported, as required by the duct suppliers
■
If the threaded rod is located inside the duct insulation, distance between threaded rod and duct is max 30 mm
■
If the threaded rod is located outside the duct isolation, distance between threaded rod and isolation is max. 40 mm
Outside gypsum wall constrution - ISOVER Ultimate Protect - Weichsott system