FDMR - Fire damper

Page 6

Version 2022-12-20

TPM 165/22

Design with actuating mechanism

The  dampers  are  equipped  by  Belimo  actuators  with
spring return and thermoelectric activation device of BFL,
BFN or BF depending on the damper size (further mentio-
ned as „actuators“).

After  being  connected  to  power  supply  230V  or  AC/DC
24V,  the  actuating  mechanism  displaces  the  damper
blade  into  operation  position  "OPEN"  and  at  the  same
time it pre-stretches its back spring.

When  the  actuating  mechanism  is  under  voltage,  the
damper  blade  is  in  the  position  "OPEN"  and  the  back
spring is pre-stretched.

Time needed for full opening of the flap blade from the
position  "CLOSED"  to  the  position  "OPEN"  is  maximum
120 sec. If the actuating power supply is cut off (due to
loss of supply voltage, or pushing the reset button on the
thermoelectrical  starting  mechanism  BAT),  the  back
spring  displaces  the  damper  blade  into  the  breakdown
position "CLOSED".

The time of displacing the blade from the position "OPEN"
to the position "CLOSED" takes maximum 20 sec.

In case that the power supply is restored again (the blade
can be in any position), the actuating mechanism starts to
re-displace the damper blade into the position "OPEN".

A  thermoelectrical  starting  mechanism  BAT,  which
contains  two  thermal  fuses  Tf1  and  Tf2,  is  a  part  of  the
actuating mechanism.

These  fuses  are  activated  when  temperature  +72°C  has
been  exceeded  (the  fuse  Tf1  when  the  temperature
around  the  damper  and  the  fuses  Tf2  when  the
temperature inside the air-conditioning ducting has been
exceeded).

After the thermal fuse Tf1 or Tf2 has been activated, the
power supply is permanently and irreversibly cut off and
the actuating mechanism, by means of the pre-stretched
spring,  displaces  the  damper  blade  into  the  breakdown
position "CLOSED".

Signalisation of damper blade position "OPEN" a "CLOSE"
is provided by two limit switches.

Design .40 and .50

Actuating mechanism

Thermoelectrical starting
mechanism BAT

Design .40 and .50

Содержание FDMR

Страница 1: ...andik mandik cz Manufacturer MANDIK UK Ltd 130 Aztec West Bristol BS32 4UB United Kingdom Tel 44 117 4526376 E Mail help mandik co uk Authorized representative FDMR Fire damper Technical Documentation...

Страница 2: ...hnical parameters 17 Placement and Assembly 18 Statement of installations 20 Installation in solid wall construction 21 Installation in gypsum wall construction 23 Installation in solid ceiling constr...

Страница 3: ...back spring of the actuating mechanism is started when the thermoelectrical starting mechanism BAT is activated when a reset button on BAT is pushed or when a power supply of the actuating mechanism...

Страница 4: ...er spring which closes the fire damper For the size of fire dampers is always assigned the size of mechanism see page 17 It is not recommended to use different size of mechanism than given by the manu...

Страница 5: ...rotection IP 67 Working temperature 25 C 120 C Limit switch G905 300E03W1 This limit switchis possibleto connect infollowing two versions CUT OFF if the arm is moving connect wire 1 2 SWITCH ON if the...

Страница 6: ...damper blade into the breakdown position CLOSED The time of displacing the blade from the position OPEN to the position CLOSED takes maximum 20 sec In case that the power supply is restored again the...

Страница 7: ...ax 8 3 A 5 ms Protection class II III Degree of protection IP 54 Running time motor spring return 60 s 20 s Ambient temperature normal duty safety duty non operating temperature 30 C 55 C The safe pos...

Страница 8: ...lass II III Degree of protection IP 54 Running time motor spring return 60 s 20 s Ambient temperature normal duty safety duty non operating temperature 30 C 55 C The safe position will be attained up...

Страница 9: ...egree of protection IP 54 Running time motor spring return 120 s 16 s Ambient temperature normal duty safety duty non operating temperature 30 C 50 C The safe position will be attained up to max 75 C...

Страница 10: ...ing mechanism BAT If the thermal fuse Tf1 breaks for a temperature close to the fire damper it is necessary to replace the actuating mechanism Thermoelectric starting mechanism BAT is integral part of...

Страница 11: ...ired with MANDIK control systems OVERRIDE MDCM 6 5 4 3 2 1 L N N L MOTOR POWER COMMS S S F1 S5 S6 S4 S3 S2 S1 COMMS OPEN CLOSED COMMAND L L N L S90C CONTROLLER S90 mounted in an addressablesmoke contr...

Страница 12: ...22 Dimensions SPIRO design with mechanical control 1 Damper casing 2 Mechanics 3 Damper blade 4 Inspection hole covering 5 Sensor sticker 6 Hole for camera 300 50 120 110 400 180 50 D 2 120 300 50 50...

Страница 13: ...per blade 4 Inspection hole covering 5 Sensor sticker 6 Hole for camera d mm d1 mm d2 mm n number of holes in the flange 100 130 10 4 125 155 10 8 160 195 10 8 180 215 10 8 200 235 10 8 225 260 10 8 2...

Страница 14: ...D 2 300 50 X 110 400 180 50 D 2 SPIRO design with actuating mechanism 1 Damper casing 2 Actuating mechanism 3 Damper blade 4 Inspection hole covering 5 BAT thermoelectrical starting mechanism 6 Hole...

Страница 15: ...12 500 545 12 16 560 605 12 16 600 650 12 16 630 680 12 16 710 760 12 20 800 860 12 20 d d1 d2 n 400 130 130 110 X D 400 D 110 136 39 X 400 X 110 180 D FLANGE design with actuating mechanism 1 Damper...

Страница 16: ...n chapter Technical parameters see page 17 Dimensions of damper connecting flanges are in accordance with EN 12 0505 Values a and c has to be respected when projecting related air conditioning ducts c...

Страница 17: ...BFL M1 200 4 3 4 5 3 0 0215 20 BFL M1 225 4 8 5 3 0 0275 25 BFL M1 250 9 5 1 5 3 3 0 0354 25 BFL M2 280 24 5 7 5 9 3 0 0462 25 BFL M2 300 34 6 2 6 4 3 0 0542 25 BFL M2 315 42 6 5 6 7 3 0 0606 25 BFL...

Страница 18: ...ected according to the certified install ation method see pages 21 to 25 During the installation and plastering process the control mechanism must be protected covered against damage and pollution The...

Страница 19: ...dge of installation of fire damper into the fire partition structure wall The damper must be installed so that the entire damper blade in the closed position is located inside the fire separating stru...

Страница 20: ...concrete with minimum thickness 100 mm or into solid ceiling construction made e g of normal concrete with minimum thickness 150 mm The fire damper can be integrated into a gypsum wall construction w...

Страница 21: ...minimum density 670 kg m 4 Damper bracket see page 27 5 Circular suspension with threaded rod see pages 26 to 28 6 Duct Solid wall construction mortar or gypsum EIS 120 40 1 50 40 150 100 D min D 80...

Страница 22: ...HILTI CFS S ACR or equivalent 4 Fire stop coating thickness 1 mm e g HILTI CFS CT PROMASTOP CC or equivalent 5 Duct 6 Fire resistant mastic fill the gap on both sides of the fire separation constructi...

Страница 23: ...stallation was tested without supports Supports are optional if are used follow the manufacturer s instructions and national standards X X 40 15 0 100 40 150 100 D min D 80 max D 300 1 FDMR 2 Gypsum w...

Страница 24: ...e g Firestop Board HILTI CFS CT B 1S 140 50 min density 140 kg m3 Firestop acrylic sealant HILTI CFS S ACR or equivalent 4 Fire stop coating thickness 1 mm e g HILTI CFS CT PROMASTOP CC or equivalent...

Страница 25: ...e 28 This installation was tested without supports Supports are optional if are used follow the manufacturer s instructions and national standards X X 150 40 150 A A D min D 80 max D 300 1 FDMR 2 Soli...

Страница 26: ...157 96 192 M18 192 117 234 M20 245 150 300 Without anchor With anchor Possible examples of anchoring to the ceiling construction Follow the instructions of fixing specialist or installation company Wi...

Страница 27: ...g air duct 10 Gypsum grid from C profile Dimension elements of the suspension system acc to the weight of the damper see page 26 Placing of mounting brackets 100 400 t mm 1 5 100 400 With slotted quic...

Страница 28: ...FDMR Fire damper Page 28 Version 2022 12 20 TPM 165 22 Duct connection 1 FDMR 2 Connecting air duct 3 Extension piece if required 4 Damping pad or breakaway connection as DW 144...

Страница 29: ...ss w m s air flow speed in nominal damper section kg m3 air density coefficient of local pressure loss for the nominal damper section D 100 125 140 150 160 180 200 225 250 280 300 2 736 2 099 1 781 1...

Страница 30: ...7 9 51 1 53 3 55 1 56 5 57 7 6 34 8 40 2 43 3 45 6 48 7 51 52 7 55 8 58 1 59 8 61 2 62 4 7 38 8 44 2 47 3 49 6 52 7 55 56 7 59 9 62 1 63 8 65 2 66 4 8 42 3 47 7 50 8 53 1 56 2 58 4 60 2 63 3 65 6 67 3...

Страница 31: ...lever 2 lock spring 8 dia stopper pin mechanics pin 5 Inspection hole cover including the clip and fasteners if they are parts of the cover 6 Bearing for torque transfer from the lever with pin on th...

Страница 32: ...SED position Dampers are stored indoor in environment without any aggressive vapours gases or dust Indoor temperature must be in the range from 30 C to 50 C and maximum relative humidity 95 avoid cond...

Страница 33: ...ice to the base plate of the damper The said facts must be recorded in the respective operation documentation of the damper record books of the damper fire logs etc and subsequently adequate function...

Страница 34: ...al plates 7 Mechanics 8 Fusible link 9 Sensor sticker 10 Hole for temperature sensor Sensor sticker 11 Inspection hole covering 12 Hole for camera Change of mechanical design for the motorised one or...

Страница 35: ...sition Release of the locking mechanism can be achieved manually or automatically by applying the supply voltage It is recommended to provide periodical checks main tenance and service actions on Fire...

Страница 36: ...tion checks of the fire dampers at least 1x a year For the function checks the dampers should be moved to CLOSED position with the fan off or with closed regulation valve situated between the fan and...

Страница 37: ...mechanism BF 24 TN BFL BFN 24 T voltage AC DC 24 V 50 design P with round duct flange PK with round duct flange and installation brackets SL spiro damper with rubber sealing SK spiro damper with rubb...

Страница 38: ...ual product information see www mandik co uk MAND K a s Dob sk 550 267 24 Hostomice Czech Republic Tel 420 311 706 742 E Mail mandik mandik cz Manufacturer MANDIK UK Ltd 130 Aztec West Bristol BS32 4U...

Отзывы: