background image

7

MANDÍK, a.s.
Dobříšská 550
26724 Hostomice
Czech Republic
Tel.: +420 311 706 706
e-mail: [email protected]
www.mandik.com

All rights reserved by Manufacturer. Changes to the product can be applied.

The current product information are available on www.mandik.cz

Содержание FDMC

Страница 1: ......

Страница 2: ...100 40 Fire damper FDMC Solid wall construction Mortar or gypsum Duct 100 40 Installation opening perimeter has to be reinforced by standard drywall profiles Fire damper FDMC Mortar or gypsum Fire pr...

Страница 3: ...stallation in a gypsum wall construction 40 100 50 Fire damper FDMC Gypsum plate Fire resistant insulation Mineral stone wool min density 140 kg m Fire protection mastic min thick ness 1 mm Glass fibe...

Страница 4: ...l perfectly in all the installation space volume installation gap 5 The distance between the fire damper and the construction wall ceiling must be minimum 75 mm according to EN 1366 2 In case that two...

Страница 5: ...er body during opening or closing 10 To provide needed access space to the control device all other objects must be situated at least 350 mm from the control parts of the damper Inspection hole must b...

Страница 6: ...ams The blade of fire damper exceeds body of fire damper by the value a There has to be enough space in duct for blade rotation 11 Damper blade overlaps 1 2 S3 S1 S2 S5 S4 S6 5 80 BAT Tf Tf LED 1 2 S3...

Страница 7: ...ly e g By releasing the RESET button or restoration of supply from ELECTRICAL FIRE SIGNALISATION 13 Before entering the dampers into operation after assembly and after sequential revisions checks and...

Страница 8: ...6724 Hostomice Czech Republic Tel 420 311 706 706 e mail mandik mandik cz www mandik com All rights reserved by Manufacturer Changes to the product can be applied The current product information are a...

Отзывы:

Похожие инструкции для FDMC