Dampers are transported by box freight vehicles without direct weather impact, there must not
occur  any  sharp  shocks  and  ambient  temperature  must  not  exceed  +40°C.  Dampers  must  be
protected against mechanic damages when transported and manipulated. During transportation,
the damper blade must be in the "CLOSED" position.

 

Dampers are stored indoor in environment without any aggressive vapours, gases or dust. Indoor
temperature  must  be  in  the  range  from  -5°C  to  +40°C  and  maximum  relative  humidity  80%.
Dampers must be protected against mechanic damages when transported and manipulated.

 

All effective safety standards and directives must be observed during fire damper assembly.

 

To ensure reliable fire damper function it is necessary to avoid blocking the closing mechanism
and contact surfaces with collected dust, fibre and sticky materials and solvents.

 

Manual operation

 

  

Without  power  supply,  the  damper  can  be  operated  manually  and  fixed  in  any  required

  

position.  Release  of  the  locking  mechanism  can  be  achieved  manually  or  automatically

  

by applying the supply voltage.

  In case that dampers are found unable to serve for their function for any cause, it must be clearly

marked. The operator is obliged to ensure so that the damper is put into condition in which it is
able to function and meanwhile he is obliged to provide the fire protection another appropriate
way.

 

Before entering the dampers into operation after their assembly and by sequential checks, the
 following checks must be carried out.

  Results of regular checks, imperfections found and all-important facts connected with the damper

function must be recorded in the "FIRE BOOK" and immediately reported to the operator.

 

Before entering the dampers into operation after assembly and after sequential revisions, checks
and  functionality  tests  of  all  designs  including  operation  of  the  electrical  components  must  be
done. After entering into operation, these revisions must be done according to requirement set
by national regulations.

  Visual  inspection  of  proper  damper  integration,  inside  damper  area,  damper  blade,  contact

surfaces and silicon sealing.

  Inspection hole disassembly: release the covering lid by unscrewing screws. Then tilt remove lid

from its original position.

  Check of blade displacement into the breakdown position "CLOSED" can be done after cutting

off the actuating mechanism supply (e.g. by pressing the RESET button at the thermoelectrical
starting  mechanism  BAT  or  cutting  off  the  supply  from  ELECTRICAL  FIRE  SIGNALISATION).
Check  of  blade  displacement  back  into  the  "OPEN"  position  can  be  done  after  restoration  of
power supply (e.g. by releasing the RESET button or restoration of supply from ELECTRICAL
FIRE SIGNALISATION).

Содержание FDMC Series

Страница 1: ......

Страница 2: ...t is valid for production designing ordering delivery assembly and operation 1 Description 2 2 Design 3 3 Dimensions weights 3 4 Placement and Assembly 5 5 Statement of installations 6 6 Pressure loss...

Страница 3: ...ice and the inspection hole can be set into the most advantageous position with respect to the operation and manipulation with the control device Damper characteristics CE certified acc to EN 15650 Te...

Страница 4: ...upply voltage activation of thermoelectrical actuating mechanism or pushing the reset button on the thermoelectrical starting mechanism BAT the back spring displaces the damper blade into the breakdow...

Страница 5: ...0 0293 BFL 9 5 5 0 0374 BFL 24 6 0 0 0484 BFL 41 5 6 6 0 0630 BFL 59 7 0 0 0793 BFL 61 5 7 3 0 0821 BFL 84 8 2 0 1065 BFL Weight and effective area The Blade overlaps For fire damper the open damper...

Страница 6: ...per body is absolutely excluded Back to back air conditioning piping must be hung or supported so as all load transfer from the back to back piping to the damper is absolutely excluded To provide need...

Страница 7: ...top P K or equal min thickness 1 mm EIS 60 6 Damper installed in a gypsum wall construction Space between damper and wall is filled by mineral stone wool min density 140 kg m or another approved fire...

Страница 8: ...tion mastic min thickness 1 mm 2 Stuffing box mineral stone wool min density 140 kg m or another approved fire sealing system for damper installation Protecta FR Akryl or Isover U Protect BSF or other...

Страница 9: ...ed fire sealing system for damper installation Position 1 Fire damper FDMC 3 Fire protection mastic min thickness 1 mm 2 Stuffing box mineral stone wool min density 140 kg m or another approved fire s...

Страница 10: ...1 Fire damper FDMC 4 Duct 2 Stuffing box mineral stone wool min density 140 kg m or another approved fire sealing system for damper installation 5 Installation shaft inner space 3 Fire protection mas...

Страница 11: ...4 2 191 254 318 382 445 509 573 636 842 1122 1403 1683 1964 2244 2525 2806 4 9 6 5 8 1 9 7 11 3 13 0 14 6 16 2 3 7 4 9 6 2 7 4 8 7 9 9 11 1 12 4 20 3 27 8 33 6 38 3 42 4 45 8 48 9 51 6 8 9 16 4 22 2 2...

Страница 12: ...C 40 C 55 C Connecting motor auxiliary switch cable 1 m 2 x 0 75 mm BFL 24 T ST with 3 pin plug in connectors cable 1 m 6 x 0 75 mm BFL 24 T ST with 6 pin plug in connectors Thermal trips Tf1 duct ou...

Страница 13: ...so that the damper is put into condition in which it is able to function and meanwhile he is obliged to provide the fire protection another appropriate way Before entering the dampers into operation a...

Страница 14: ...13 Park All 366 DK 2605 Brondby Telefon 70 20 19 11 E mail oeland oeland dk technical specifications size type...

Страница 15: ...oeland oeland dk The producer reserves the right for innovations of the product For actual product information see www mandik com MAND K a s Dob sk 550 26724 Hostomice Czech Republic Tel 420 311 706 7...

Отзывы: