14
10. Damper blade overlaps
9. To provide needed access space to the control device, all other objects must be situated at least 350
mm from the control parts of the damper. Inspection hole must be accessible.
7. The fire damper can be integrated into a solid or gypsum wall construction or into solid ceiling
construction. Damper blade has to be inside of construction (labelled BUILD IN EDGE on the damper
body). The fire damper can also be integrated outside the wall construction. Duct and the damper part
between the wall construction and the damper blade (labelled BUILD IN EDGE on the damper body)
must be protected with fire-fighting insulation.
8. All fire dampers has to be closed during installation process. The damper body should not be deformed
in the course of bricking in. Once the damper is built in, its blade should not grind on the damper body
during opening or closing.
c
a
c
a
Built in edge
Built in edge
37
5
28
0
37
5
26
0
50
50